Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2019-05-31 — TX
Operator
Enterprise Crude Pipeline Llc
Cause
Material Failure Of Pipe Or Weld
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$170,000
Incident datetime
2019-05-31 19:20
Report number
Location
TX
Narrative
Enterprise pipeline technician responded to a third party call observing an oil mist on 5/31/19 at approximately 19:20 at the giddings pump station. Local pipeline technician arrived at 19:27 and found a cracked socket weld on a 1" thermal bypass line on the station discharge valve. The pipeline technician closed the 1" gate valves on the bypass line, which stopped the leak at 20:05. The cause of the cracked weld was determined to be fatigue-related. A vibration study is being performed at giddings pump station to identify and possibly mitigate future fatigue related occurrences. Incident was determined to be nrc reportable at 20:30 on 5/31/19. Initial nrc notification made on 5/31/19 is #1247476 and 48 hour nrc update made on 6/2/19 is #1247609. Release volume was subsequently determined to be 10 barrels, following initial estimates of 20-30 barrels.
Detailed record list
Report Received Date
2019-06-27 00:00:00
Iyear
2019
Report Number
20190206
Supplemental Number
32645
Report Type
Supplemental Final
Operator Id
30829
Name
Enterprise Crude Pipeline Llc
Operator Street Address
1100 Louisiana Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2019-05-31 19:20:00
Location Latitude
30.280692
Location Longitude
-96.948503
Commodity Released Type
Crude Oil
Unintentional Release Bbls
10
Recovered Bbls
10
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Notification From Public
Incident Identified Datetime
2019-05-31 19:20:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Shutdown Due Accident Ind
No
Shutdown Explain
The Affected Pump Station Was Isolated From The Pipeline.
On Site Datetime
2019-05-31 19:27:00
Nrc Rpt Datetime
2019-05-31 20:55:00
Nrc Rpt Num
1247476
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Giddings Pump Station
Segment Name
Midland To Sealy Pipeline/c-129
Onshore State Abbreviation
Tx
Onshore Postal Code
78948
Onshore City Name
Lincoln
Onshore County Name
Lee
Designated Location
Milepost/valve Station
Designated Name
347.99
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Intrastate
Item Involved
Weld, Including Heat-Affected Zone
Weld Subtype
Other
Weld Details
Socket Weld
Installation Year
2018
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Crack
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
535
Est Cost Prop Damage
170000
Est Cost Emergency
0
Est Cost Environmental
0
Est Cost Other
0
Prpty
170535
Accident Psig
1074
Mop Psig
1480
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Neither controller nor control room contributed to the incident.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Material Failure Of Pipe Or Weld
Cause Details
Design-, Construction-, Installation-, Or Fabrication-Related
Field Exam Ind
Yes
Metallurgical Ind
Yes
Failure Type
Design-, Construction-, Installation-, Or Fabrication-Related
Fatigue Vibr Related
Yes
Failure Subtype
Mechanical Vibration
Additional Lack Fusion Ind
Yes
Collected Data Ind
No
Has Hydrtst Conduc Before Ind
No
Direct Asmnt Conducted
No
Non Destructive Exam Ind
Yes
Exm Dry Mgnt Partcl Rcnt Year
2017
Exm Dry Mgnt Partcl Rcnt Ind
Yes
Preparer Name
T****** A* G********
Preparer Title
Senior Staff Pipeline Compliance Engineer
Preparer Email
T**********@e****.com
Preparer Telephone
713-381-6433
Prepared Date
2019-09-03 00:00:00
Authorizer Name
T****** A* G********
Authorizer Telephone
713-381-6433
Authorizer Title
Senior Staff Pipeline Compliance Engineer
Authorizer Email
T**********@e****.com
Narrative
Enterprise pipeline technician responded to a third party call observing an oil mist on 5/31/19 at approximately 19:20 at the giddings pump station. Local pipeline technician arrived at 19:27 and found a cracked socket weld on a 1" thermal bypass line on the station discharge valve. The pipeline technician closed the 1" gate valves on the bypass line, which stopped the leak at 20:05. The cause of the cracked weld was determined to be fatigue-related. A vibration study is being performed at giddings pump station to identify and possibly mitigate future fatigue related occurrences. Incident was determined to be nrc reportable at 20:30 on 5/31/19. Initial nrc notification made on 5/31/19 is #1247476 and 48 hour nrc update made on 6/2/19 is #1247609. Release volume was subsequently determined to be 10 barrels, following initial estimates of 20-30 barrels.
| Report Received Date | 2019-06-27 00:00:00 |
|---|---|
| Iyear | 2019 |
| Report Number | 20190206 |
| Supplemental Number | 32645 |
| Report Type | Supplemental Final |
| Operator Id | 30829 PHMSA Enforcement |
| Name | Enterprise Crude Pipeline Llc |
| Operator Street Address | 1100 Louisiana Street |
| Operator City Name | Houston |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77002 |
| Local Datetime | 2019-05-31 19:20:00 |
| Location Latitude | 30.280692 Google Maps OpenStreetMap |
| Location Longitude | -96.948503 Google Maps OpenStreetMap |
| Commodity Released Type | Crude Oil |
| Unintentional Release Bbls | 10 |
| Recovered Bbls | 10 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Notification From Public |
| Incident Identified Datetime | 2019-05-31 19:20:00 |
| System Part Involved | Onshore Pump/meter Station Equipment And Piping |
| On Off Shore | Onshore |
| Shutdown Due Accident Ind | No |
| Shutdown Explain | The Affected Pump Station Was Isolated From The Pipeline. |
| On Site Datetime | 2019-05-31 19:27:00 |
| Nrc Rpt Datetime | 2019-05-31 20:55:00 |
| Nrc Rpt Num | 1247476 NRC Report How to search |
| Ignite Ind | No |
| Explode Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Giddings Pump Station |
| Segment Name | Midland To Sealy Pipeline/c-129 |
| Onshore State Abbreviation | Tx |
| Onshore Postal Code | 78948 |
| Onshore City Name | Lincoln |
| Onshore County Name | Lee |
| Designated Location | Milepost/valve Station |
| Designated Name | 347.99 |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
| Crossing | No |
| Pipe Facility Type | Intrastate |
| Item Involved | Weld, Including Heat-Affected Zone |
| Weld Subtype | Other |
| Weld Details | Socket Weld |
| Installation Year | 2018 |
| Material Involved | Carbon Steel |
| Release Type | Leak |
| Leak Type | Crack |
| Wildlife Impact Ind | No |
| Soil Contamination | No |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | No |
| Commodity Reached Hca | No |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 535 |
| Est Cost Prop Damage | 170000 |
| Est Cost Emergency | 0 |
| Est Cost Environmental | 0 |
| Est Cost Other | 0 |
| Prpty | 170535 |
| Accident Psig | 1074 |
| Mop Psig | 1480 |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Cpm In Place Ind | Yes |
| Cpm Operating Ind | Yes |
| Cpm Functional Ind | Yes |
| Cpm Detection Ind | No |
| Cpm Conf Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | Neither controller nor control room contributed to the incident. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Material Failure Of Pipe Or Weld |
| Cause Details | Design-, Construction-, Installation-, Or Fabrication-Related |
| Field Exam Ind | Yes |
| Metallurgical Ind | Yes |
| Failure Type | Design-, Construction-, Installation-, Or Fabrication-Related |
| Fatigue Vibr Related | Yes |
| Failure Subtype | Mechanical Vibration |
| Additional Lack Fusion Ind | Yes |
| Collected Data Ind | No |
| Has Hydrtst Conduc Before Ind | No |
| Direct Asmnt Conducted | No |
| Non Destructive Exam Ind | Yes |
| Exm Dry Mgnt Partcl Rcnt Year | 2017 |
| Exm Dry Mgnt Partcl Rcnt Ind | Yes |
| Preparer Name | T****** A* G******** |
| Preparer Title | Senior Staff Pipeline Compliance Engineer |
| Preparer Email | T**********@e****.com |
| Preparer Telephone | 713-381-6433 |
| Prepared Date | 2019-09-03 00:00:00 |
| Authorizer Name | T****** A* G******** |
| Authorizer Telephone | 713-381-6433 |
| Authorizer Title | Senior Staff Pipeline Compliance Engineer |
| Authorizer Email | T**********@e****.com |
| Narrative | Enterprise pipeline technician responded to a third party call observing an oil mist on 5/31/19 at approximately 19:20 at the giddings pump station. Local pipeline technician arrived at 19:27 and found a cracked socket weld on a 1" thermal bypass line on the station discharge valve. The pipeline technician closed the 1" gate valves on the bypass line, which stopped the leak at 20:05. The cause of the cracked weld was determined to be fatigue-related. A vibration study is being performed at giddings pump station to identify and possibly mitigate future fatigue related occurrences. Incident was determined to be nrc reportable at 20:30 on 5/31/19. Initial nrc notification made on 5/31/19 is #1247476 and 48 hour nrc update made on 6/2/19 is #1247609. Release volume was subsequently determined to be 10 barrels, following initial estimates of 20-30 barrels. |