GD incident on 2019-08-25 — MD

Operator
Baltimore Gas And Electric Company
Cause
Other Outside Force Damage
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$15,000
Incident datetime
2019-08-25 07:09
Report number
Location
MD, HOWARD
Narrative
On august 25th, 2019 at 07:09 the howard county fire department notified bge of an outside gas odor at the location of 8865 stanford blvd. Bge immediately dispatched a gas fitter to the premise for investigation. A gas maintenance and repair crew was also dispatched there was an explosion in the building at 08:00. The gas emergency plan was put into affect and notifications were implemented starting at 08:02. The maryland public service commission was notified and a report to the national response center was issued. The service was abandoned on 8/26/2020 12:00pm. There are multiple facilities near and/or crossing bge's facilities which were evaluated along with bge's facilities. The facilities which cross bge's facilities are communications facilities, private area lighting facilities, and the building's electrical service. The explosion was the result of a diffuse fuel and air mixture. The fuel was natural gas. The source of the fugitive natural gas was a compromise in the integrity of the gas service caused by thermal degradation of its polyethylene tubing from an electrical fault of unknown origin. A comprehensive analysis was conducted of all the facilities in the area, including the communications facilities and the private area lighting facilities in the area, but did not yield additional relevant information.
Detailed record list
Occurred At
2019-08-25 07:09:00
Year
2019
Report Received Date
2019-09-24 00:00:00
Iyear
2019.0
Report Number
20190108.0
Supplemental Number
34650.0
Report Type
Supplemental Final
Operator Id
Name
Baltimore Gas And Electric Company
Operator Street Address
110 W Fayette St
Operator City Name
Baltimore
Operator State Abbreviation
MD
Operator Postal Code
21201
Local Datetime
2019-08-25 08:00:00
Time Zone
Eastern
Daylight Savings Ind
No
Location Street Address
8865 Stanford Blvd
Location City Name
Columbia
Location County Name
Howard
Location State Abbreviation
MD
Location Postal Code
21045
Location Latitude
Location Longitude
Flow Cont Service Valve Ind
Yes
Nrc Rpt Datetime
2019-08-25 10:00:00
Nrc Rpt Num
Commodity Released Type
Natural Gas
Unintentional Release
360.0
Intentional Release
0.0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
Yes
Ignite Datetime
2019-08-25 07:09:00
How Extinguished
Local/state/federal Emergency Responder
Gas Consumed By Fire In Mcf
360
Explode Ind
Yes
Num Pub Evacuated
0.0
Incident Identified Datetime
2019-08-25 07:09:00
On Site Datetime
2019-08-25 07:36:00
Federal
No
Location Type
Private Property
Incident Area Type
Underground
Incident Area Subtype
Under Pavement
Depth Of Cover
34.0
Other Underground Facilities
Yes
Crossing
No
Pipe Facility Type
Privately Owned
System Part Involved
Service
Installation Year
1997.0
Customer Type
Non-Residential With Meter Capacity 1,000 Scfh Or Higher
Was Efv Installed Before Ind
No
Curb Valve Inst Before Inc Ind
Yes
Pipe Diameter
2.0
Pipe Specification
D2513
Pipe Manufacturer
Drisco
Material Involved
Plastic
Plastic Type
Polyethylene (Pe)
Plastic Sdr
11
Material Pe Pipe Code
3408
Release Type
Other
Release Type Details
Burn Through - An Apparent Quarter Size Hole Was Found In The Gas Pipe During The Excavation And Pressure Testing. The Cause Of The Hole Is From An Electrical Fault Of Unknown Origin.
Class Location Type
Class 1 Location
Est Cost Oper Paid
7000000.0
Est Cost Prop Damage
15000.0
Est Cost Emergency
5000.0
Est Cost Other
0.0
Gas Cost In Mcf
1.53
Est Cost Unintentional Release
551.0
Est Cost Intentional Release
0.0
Prpty
7020551.0
Commercial Affected
22.0
Industrial Affected
0.0
Residences Affected
0.0
Num Persons Hosp Not Ovnght
0.0
Num Injured Treated By Emt
0.0
Num Resident Building Affctd
0.0
Num Business Building Affctd
22.0
Accident Psig
90.0
Normal Psig
90.0
Mop Psig
90.0
Mop Cfr Section
192.619(A)(4)
Maop Established Date
1997-10-03 00:00:00
Accident Pressure
Pressure Did Not Exceed Maop
Gas Odorized System Type
Injection Pump
Gas Odorized Level
0.3
Scada In Place Ind
No
Accident Identifier
Notification From Emergency Responder
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Other Outside Force Damage
Cause Details
Electrical Arcing From Other Equipment Or Facility
Outside Force Type
Electrical Arcing From Other Equipment Or Facility
Preparer Name
R***** R**
Preparer Title
Manager - Gas Engineering And Standards
Preparer Email
R*********@d*******.com
Preparer Telephone
410-470-6933
Preparer Fax
410-470-9549
Authorizer Name
D***** A* N*****
Authorizer Title
Manager - Gas Engineering And Program Management
Authorizer Telephone
410-470-6435
Authorizer Email
D**************@b**.com
Narrative
On august 25th, 2019 at 07:09 the howard county fire department notified bge of an outside gas odor at the location of 8865 stanford blvd. Bge immediately dispatched a gas fitter to the premise for investigation. A gas maintenance and repair crew was also dispatched there was an explosion in the building at 08:00. The gas emergency plan was put into affect and notifications were implemented starting at 08:02. The maryland public service commission was notified and a report to the national response center was issued. The service was abandoned on 8/26/2020 12:00pm. There are multiple facilities near and/or crossing bge's facilities which were evaluated along with bge's facilities. The facilities which cross bge's facilities are communications facilities, private area lighting facilities, and the building's electrical service. The explosion was the result of a diffuse fuel and air mixture. The fuel was natural gas. The source of the fugitive natural gas was a compromise in the integrity of the gas service caused by thermal degradation of its polyethylene tubing from an electrical fault of unknown origin. A comprehensive analysis was conducted of all the facilities in the area, including the communications facilities and the private area lighting facilities in the area, but did not yield additional relevant information.
Occurred At 2019-08-25 07:09:00
Year 2019
Report Received Date 2019-09-24 00:00:00
Iyear 2019.0
Report Number 20190108.0
Supplemental Number 34650.0
Report Type Supplemental Final
Operator Id 1088 PHMSA Enforcement
Name Baltimore Gas And Electric Company
Operator Street Address 110 W Fayette St
Operator City Name Baltimore
Operator State Abbreviation MD
Operator Postal Code 21201
Local Datetime 2019-08-25 08:00:00
Time Zone Eastern
Daylight Savings Ind No
Location Street Address 8865 Stanford Blvd
Location City Name Columbia
Location County Name Howard
Location State Abbreviation MD
Location Postal Code 21045
Location Latitude 39.191001 Google Maps OpenStreetMap
Location Longitude -76.818052 Google Maps OpenStreetMap
Flow Cont Service Valve Ind Yes
Nrc Rpt Datetime 2019-08-25 10:00:00
Nrc Rpt Num 1256316 NRC Report How to search
Commodity Released Type Natural Gas
Unintentional Release 360.0
Intentional Release 0.0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Ignite Ind Yes
Ignite Datetime 2019-08-25 07:09:00
How Extinguished Local/state/federal Emergency Responder
Gas Consumed By Fire In Mcf 360
Explode Ind Yes
Num Pub Evacuated 0.0
Incident Identified Datetime 2019-08-25 07:09:00
On Site Datetime 2019-08-25 07:36:00
Federal No
Location Type Private Property
Incident Area Type Underground
Incident Area Subtype Under Pavement
Depth Of Cover 34.0
Other Underground Facilities Yes
Crossing No
Pipe Facility Type Privately Owned
System Part Involved Service
Installation Year 1997.0
Customer Type Non-Residential With Meter Capacity 1,000 Scfh Or Higher
Was Efv Installed Before Ind No
Curb Valve Inst Before Inc Ind Yes
Pipe Diameter 2.0
Pipe Specification D2513
Pipe Manufacturer Drisco
Material Involved Plastic
Plastic Type Polyethylene (Pe)
Plastic Sdr 11
Material Pe Pipe Code 3408
Release Type Other
Release Type Details Burn Through - An Apparent Quarter Size Hole Was Found In The Gas Pipe During The Excavation And Pressure Testing. The Cause Of The Hole Is From An Electrical Fault Of Unknown Origin.
Class Location Type Class 1 Location
Est Cost Oper Paid 7000000.0
Est Cost Prop Damage 15000.0
Est Cost Emergency 5000.0
Est Cost Other 0.0
Gas Cost In Mcf 1.53
Est Cost Unintentional Release 551.0
Est Cost Intentional Release 0.0
Prpty 7020551.0
Commercial Affected 22.0
Industrial Affected 0.0
Residences Affected 0.0
Num Persons Hosp Not Ovnght 0.0
Num Injured Treated By Emt 0.0
Num Resident Building Affctd 0.0
Num Business Building Affctd 22.0
Accident Psig 90.0
Normal Psig 90.0
Mop Psig 90.0
Mop Cfr Section 192.619(A)(4) View CFR 49 §192
Maop Established Date 1997-10-03 00:00:00
Accident Pressure Pressure Did Not Exceed Maop
Gas Odorized System Type Injection Pump
Gas Odorized Level 0.3
Scada In Place Ind No
Accident Identifier Notification From Emergency Responder
Investigation Status No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Other Outside Force Damage
Cause Details Electrical Arcing From Other Equipment Or Facility
Outside Force Type Electrical Arcing From Other Equipment Or Facility
Preparer Name R***** R**
Preparer Title Manager - Gas Engineering And Standards
Preparer Email R*********@d*******.com
Preparer Telephone 410-470-6933
Preparer Fax 410-470-9549
Authorizer Name D***** A* N*****
Authorizer Title Manager - Gas Engineering And Program Management
Authorizer Telephone 410-470-6435
Authorizer Email D**************@b**.com
Narrative On august 25th, 2019 at 07:09 the howard county fire department notified bge of an outside gas odor at the location of 8865 stanford blvd. Bge immediately dispatched a gas fitter to the premise for investigation. A gas maintenance and repair crew was also dispatched there was an explosion in the building at 08:00. The gas emergency plan was put into affect and notifications were implemented starting at 08:02. The maryland public service commission was notified and a report to the national response center was issued. The service was abandoned on 8/26/2020 12:00pm. There are multiple facilities near and/or crossing bge's facilities which were evaluated along with bge's facilities. The facilities which cross bge's facilities are communications facilities, private area lighting facilities, and the building's electrical service. The explosion was the result of a diffuse fuel and air mixture. The fuel was natural gas. The source of the fugitive natural gas was a compromise in the integrity of the gas service caused by thermal degradation of its polyethylene tubing from an electrical fault of unknown origin. A comprehensive analysis was conducted of all the facilities in the area, including the communications facilities and the private area lighting facilities in the area, but did not yield additional relevant information.