Incident details
Operator, cause, commodity and consequences with raw source fields.
GD incident on 2019-08-24 — NY
Operator
Consolidated Edison Co Of New York
Cause
Other Outside Force Damage
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$200
Incident datetime
2019-08-24 07:52
Report number
Location
NY, WESTCHESTER
Narrative
At 07:52 on august 24, 2019, the croton-on-hudson fire department (chfd) contacted con edison's gas emergency response center (gerc) and reported a building fire at 1007 half bay moon drive. The gerc immediately dispatched con edison gas distribution services (gds) personnel and supervisors to the location. The building involved was supplied by a 1-inch high-pressure high-density polyethylene (hdpe) gas service (installed in 2004). At 07:58, the chfd reported a secondary gas ignition at the meter set up located outside the building. Additional con edison personnel from gds, gas construction, and the gas emergency response group (erg) were then dispatched to the location by the gerc. Gds arrived at 08:06 and confirmed the reported secondary gas ignition. At 08:35, gds closed the curb valve on the 1-inch hdpe gas service to 1007 half bay moon drive, thereby extinguishing the secondary fire at the outdoor gas meter set up; however, the structural fire remained ongoing at that time. As a precaution, gds also closed the head-of-service valves to 1004, 1005, and 1006 half moon bay drive at their outdoor meter sets. In addition, nearby radial high-pressure main valve #39289 was located and staffed for contingency isolation purposes. At 11:25, gds reported that the chfd had extinguished the structural fire. A special leak survey was performed by con edison and no gas odors or readings were detected. Gds performed an integrity test on the house piping inside 1007 half moon bay drive downstream of the gas meter and the test passed. Con edison gas construction also performed a pressure test on the gas service line, from the curb valve to the head-of service valve, under line pressure (60 psi), and the test passed. Pressure and odorant readings were within the acceptable ranges. Con edison personnel cut and capped the gas service line to 1007 half moon bay drive at the curb valve and issued a warning tag. Based on their investigation, the chfd reported the primary cause of the fire is undetermined. It was noted, however, that interior renovations were ongoing in 1007 half moon bay drive at the time of the fire. There were no reported injuries. Multiple media outlets were on location. Nyspsc and usdot were notified. Nyspsc responded to the location.
Detailed record list
Occurred At
2019-08-24 07:52:00
Year
2019
Report Received Date
2019-09-19 00:00:00
Iyear
2019.0
Report Number
20190104.0
Supplemental Number
32757.0
Report Type
Supplemental Final
Operator Id
2704
Name
Consolidated Edison Co Of New York
Operator Street Address
4 Irving Place
Operator City Name
New York
Operator State Abbreviation
NY
Operator Postal Code
10003
Local Datetime
2019-08-24 07:52:00
Location Street Address
1007 Half Moon Bay Drive
Location City Name
Croton-On-Hudson
Location County Name
Westchester
Location State Abbreviation
NY
Location Postal Code
10520
Location Latitude
41.191679
Location Longitude
-73.889588
Nrc Rpt Datetime
2019-08-24 11:35:00
Nrc Rpt Num
1256244
Commodity Released Type
Natural Gas
Unintentional Release
10.0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
Yes
Explode Ind
No
Num Pub Evacuated
0.0
Incident Identified Datetime
2019-08-24 07:52:00
On Site Datetime
2019-08-24 08:06:00
Federal
No
Location Type
Private Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance (E.g. Value Or Regulator Station, Outdoor Meter Set)
Crossing
No
Pipe Facility Type
Privately Owned
System Part Involved
Other
System Part Details
Outside Meter/regulator Set.
Material Involved
Other
Material Details
Meter Set.
Release Type
Leak
Leak Type
Other
Leak Type Other
Meter Melted.
Class Location Type
Class 4 Location
Est Cost Oper Paid
50000.0
Est Cost Prop Damage
200.0
Est Cost Emergency
800.0
Est Cost Other
500.0
Est Cost Other Details
0
Est Cost Unintentional Release
10.0
Prpty
51510.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
1.0
Accident Psig
60.0
Normal Psig
60.0
Mop Psig
90.0
Accident Pressure
Pressure Did Not Exceed Maop
Scada In Place Ind
No
Accident Identifier
Notification From Emergency Responder
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Secondary ignition at gas meter set during ongoing building fire.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Other Outside Force Damage
Cause Details
Nearby Industrial, Man-Made, Or Other Fire/explosion As Primary Cause Of Incident
Outside Force Type
Nearby Industrial, Man-Made, Or Other Fire/explosion As Primary Cause Of Incident
Preparer Name
O**** L***
Preparer Title
Gas Emergency Response Center-Operations Manager
Preparer Email
L****@c****.com
Preparer Telephone
718-319-2310
Preparer Fax
718-824-2219
Authorizer Name
N******* H*****
Authorizer Title
Gas Emergency Response Center-Department Manager
Authorizer Telephone
718-319-2350
Authorizer Email
H******@c****.com
Narrative
At 07:52 on august 24, 2019, the croton-on-hudson fire department (chfd) contacted con edison's gas emergency response center (gerc) and reported a building fire at 1007 half bay moon drive. The gerc immediately dispatched con edison gas distribution services (gds) personnel and supervisors to the location. The building involved was supplied by a 1-inch high-pressure high-density polyethylene (hdpe) gas service (installed in 2004). At 07:58, the chfd reported a secondary gas ignition at the meter set up located outside the building. Additional con edison personnel from gds, gas construction, and the gas emergency response group (erg) were then dispatched to the location by the gerc. Gds arrived at 08:06 and confirmed the reported secondary gas ignition. At 08:35, gds closed the curb valve on the 1-inch hdpe gas service to 1007 half bay moon drive, thereby extinguishing the secondary fire at the outdoor gas meter set up; however, the structural fire remained ongoing at that time. As a precaution, gds also closed the head-of-service valves to 1004, 1005, and 1006 half moon bay drive at their outdoor meter sets. In addition, nearby radial high-pressure main valve #39289 was located and staffed for contingency isolation purposes. At 11:25, gds reported that the chfd had extinguished the structural fire. A special leak survey was performed by con edison and no gas odors or readings were detected. Gds performed an integrity test on the house piping inside 1007 half moon bay drive downstream of the gas meter and the test passed. Con edison gas construction also performed a pressure test on the gas service line, from the curb valve to the head-of service valve, under line pressure (60 psi), and the test passed. Pressure and odorant readings were within the acceptable ranges. Con edison personnel cut and capped the gas service line to 1007 half moon bay drive at the curb valve and issued a warning tag. Based on their investigation, the chfd reported the primary cause of the fire is undetermined. It was noted, however, that interior renovations were ongoing in 1007 half moon bay drive at the time of the fire. There were no reported injuries. Multiple media outlets were on location. Nyspsc and usdot were notified. Nyspsc responded to the location.
| Occurred At | 2019-08-24 07:52:00 |
|---|---|
| Year | 2019 |
| Report Received Date | 2019-09-19 00:00:00 |
| Iyear | 2019.0 |
| Report Number | 20190104.0 |
| Supplemental Number | 32757.0 |
| Report Type | Supplemental Final |
| Operator Id | 2704 PHMSA Enforcement |
| Name | Consolidated Edison Co Of New York |
| Operator Street Address | 4 Irving Place |
| Operator City Name | New York |
| Operator State Abbreviation | NY |
| Operator Postal Code | 10003 |
| Local Datetime | 2019-08-24 07:52:00 |
| Location Street Address | 1007 Half Moon Bay Drive |
| Location City Name | Croton-On-Hudson |
| Location County Name | Westchester |
| Location State Abbreviation | NY |
| Location Postal Code | 10520 |
| Location Latitude | 41.191679 Google Maps OpenStreetMap |
| Location Longitude | -73.889588 Google Maps OpenStreetMap |
| Nrc Rpt Datetime | 2019-08-24 11:35:00 |
| Nrc Rpt Num | 1256244 NRC Report How to search |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 10.0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Ignite Ind | Yes |
| Explode Ind | No |
| Num Pub Evacuated | 0.0 |
| Incident Identified Datetime | 2019-08-24 07:52:00 |
| On Site Datetime | 2019-08-24 08:06:00 |
| Federal | No |
| Location Type | Private Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance (E.g. Value Or Regulator Station, Outdoor Meter Set) |
| Crossing | No |
| Pipe Facility Type | Privately Owned |
| System Part Involved | Other |
| System Part Details | Outside Meter/regulator Set. |
| Material Involved | Other |
| Material Details | Meter Set. |
| Release Type | Leak |
| Leak Type | Other |
| Leak Type Other | Meter Melted. |
| Class Location Type | Class 4 Location |
| Est Cost Oper Paid | 50000.0 |
| Est Cost Prop Damage | 200.0 |
| Est Cost Emergency | 800.0 |
| Est Cost Other | 500.0 |
| Est Cost Other Details | 0 |
| Est Cost Unintentional Release | 10.0 |
| Prpty | 51510.0 |
| Commercial Affected | 0.0 |
| Industrial Affected | 0.0 |
| Residences Affected | 1.0 |
| Accident Psig | 60.0 |
| Normal Psig | 60.0 |
| Mop Psig | 90.0 |
| Accident Pressure | Pressure Did Not Exceed Maop |
| Scada In Place Ind | No |
| Accident Identifier | Notification From Emergency Responder |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | Secondary ignition at gas meter set during ongoing building fire. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Other Outside Force Damage |
| Cause Details | Nearby Industrial, Man-Made, Or Other Fire/explosion As Primary Cause Of Incident |
| Outside Force Type | Nearby Industrial, Man-Made, Or Other Fire/explosion As Primary Cause Of Incident |
| Preparer Name | O**** L*** |
| Preparer Title | Gas Emergency Response Center-Operations Manager |
| Preparer Email | L****@c****.com |
| Preparer Telephone | 718-319-2310 |
| Preparer Fax | 718-824-2219 |
| Authorizer Name | N******* H***** |
| Authorizer Title | Gas Emergency Response Center-Department Manager |
| Authorizer Telephone | 718-319-2350 |
| Authorizer Email | H******@c****.com |
| Narrative | At 07:52 on august 24, 2019, the croton-on-hudson fire department (chfd) contacted con edison's gas emergency response center (gerc) and reported a building fire at 1007 half bay moon drive. The gerc immediately dispatched con edison gas distribution services (gds) personnel and supervisors to the location. The building involved was supplied by a 1-inch high-pressure high-density polyethylene (hdpe) gas service (installed in 2004). At 07:58, the chfd reported a secondary gas ignition at the meter set up located outside the building. Additional con edison personnel from gds, gas construction, and the gas emergency response group (erg) were then dispatched to the location by the gerc. Gds arrived at 08:06 and confirmed the reported secondary gas ignition. At 08:35, gds closed the curb valve on the 1-inch hdpe gas service to 1007 half bay moon drive, thereby extinguishing the secondary fire at the outdoor gas meter set up; however, the structural fire remained ongoing at that time. As a precaution, gds also closed the head-of-service valves to 1004, 1005, and 1006 half moon bay drive at their outdoor meter sets. In addition, nearby radial high-pressure main valve #39289 was located and staffed for contingency isolation purposes. At 11:25, gds reported that the chfd had extinguished the structural fire. A special leak survey was performed by con edison and no gas odors or readings were detected. Gds performed an integrity test on the house piping inside 1007 half moon bay drive downstream of the gas meter and the test passed. Con edison gas construction also performed a pressure test on the gas service line, from the curb valve to the head-of service valve, under line pressure (60 psi), and the test passed. Pressure and odorant readings were within the acceptable ranges. Con edison personnel cut and capped the gas service line to 1007 half moon bay drive at the curb valve and issued a warning tag. Based on their investigation, the chfd reported the primary cause of the fire is undetermined. It was noted, however, that interior renovations were ongoing in 1007 half moon bay drive at the time of the fire. There were no reported injuries. Multiple media outlets were on location. Nyspsc and usdot were notified. Nyspsc responded to the location. |