GD incident on 2019-07-31 — PA

Operator
Columbia Gas Of Pennsylvania
Cause
Incorrect Operation
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities 1 injury
Property damage (nominal)
$337
Incident datetime
2019-07-31 16:03
Report number
Location
PA, WASHINGTON
Narrative
On july 31, 2019 a home at 100 park lane, washington, pa exploded. Three emergency responders and the customer at 100 park lane were sent to the hospital, one of whom required admittance. There were no life threatening injuries. The company was in the final stages of a pressure uprate project. The gas system pressure was being increased from low pressure (inches of water column) to medium pressure (40 psig). Service and mainline records did not indicate that 100 park lane was served from the system being uprated. Therefore a service regulator was not installed at the meter on the premises to control elevated pressure. Since no service regulator was installed, gas entered the house and reached appliances at a line pressure of 40 psig. The fire marshal's report indicates that the furnace in the home was the source of ignition. After the incident, it was discovered the service line for 100 park lane was tapped into a mainline that was part of the uprate project.
Detailed record list
Occurred At
2019-07-31 16:03:00
Year
2019
Report Received Date
2019-08-30 00:00:00
Iyear
2019.0
Report Number
20190095.0
Supplemental Number
36146.0
Report Type
Supplemental Final
Operator Id
Name
Columbia Gas Of Pennsylvania
Operator Street Address
121 Champion Way Suite 100
Operator City Name
Canonsburg
Operator State Abbreviation
PA
Operator Postal Code
15317
Local Datetime
2019-07-31 15:45:00
Time Zone
Eastern
Daylight Savings Ind
Yes
Location Street Address
100 Park Lane
Location City Name
Washington
Location County Name
Washington
Location State Abbreviation
PA
Location Postal Code
15301
Location Latitude
Location Longitude
Flow Cont Key Crit Ind
Yes
Nrc Rpt Datetime
2019-07-31 16:29:00
Nrc Rpt Num
Commodity Released Type
Natural Gas
Unintentional Release
3.0
Intentional Release
0.0
Fatality Ind
No
Fatal
0
Injury Ind
Yes
Num Emp Injuries
0
Num Contr Injuries
0
Num Er Injuries
1
Num Worker Injuries
0
Num Gp Injuries
0
Injure
1
Ignite Ind
No
Num Pub Evacuated
0.0
Incident Identified Datetime
2019-07-31 16:03:00
On Site Datetime
2019-07-31 16:03:00
Federal
No
Location Type
Private Property
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
24.0
Other Underground Facilities
No
Crossing
No
Pipe Facility Type
Privately Owned
System Part Involved
Service
Installation Year
2013.0
Customer Type
Single Family Residential
Was Efv Installed Before Ind
No
Curb Valve Inst Before Inc Ind
No
Pipe Diameter
1.0
Pipe Specification
Unknown
Pipe Manufacturer
Unknown
Material Involved
Plastic
Plastic Type
Polyethylene (Pe)
Wt Plastic Unknown Ind
Unknown
Material Pe Pipe Code
Unknown
Release Type
Leak
Leak Type
Other
Leak Type Other
No Regulator For Uprate
Class Location Type
Class 3 Location
Est Cost Oper Paid
272000.0
Est Cost Prop Damage
337.0
Est Cost Emergency
10000.0
Est Cost Other
0.0
Gas Cost In Mcf
0.0
Est Cost Unintentional Release
0.0
Est Cost Intentional Release
0.0
Prpty
282337.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
63.0
Num Persons Hosp Not Ovnght
2.0
Num Injured Treated By Emt
0.0
Num Resident Building Affctd
1.0
Num Business Building Affctd
0.0
Accident Psig
40.0
Normal Psig
40.0
Mop Psig
45.0
Mop Cfr Section
192.619(A)(2)
Maop Established Date
1982-07-15 00:00:00
Accident Pressure
Pressure Did Not Exceed Maop
Gas Odorized System Type
Odorized By Others
Gas Odorized Level
4
Scada In Place Ind
No
Accident Identifier
Notification From Emergency Responder
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
Yes
Num Employees Tested
9
Num Employees Failed
0
Contractor Drug Test Ind
Yes
Num Contractors Tested
8
Num Contractors Failed
0
Cause
Incorrect Operation
Cause Details
Other Incorrect Operation
Operation Type
Other Incorrect Operation
Operation Details
Service Regulator Was Not Installed At 100 Park Lane, Washington, Pa Before Increasing Line Pressure As Part Of An Uprate Operation.
Related Other Ind
Yes
Operation Related Details
While The Company Has Established Procedures And Processes To Be Taken For Uprates That Include Review Of Materials, Maps, And Records, In This Instance That Review Did Not Identify 100 Park Lane, Washington, Pa As Being Served From The System That Was Involved In The Uprate Project.
Category Type
Construction
Operator Qualification Ind
Yes
Qualified Individuals
Yes, They Were Qualified For The Task(S)
Preparer Name
R****** B****
Preparer Title
Operations Compliance Manager
Preparer Email
R*****@n*******.com
Preparer Telephone
17243217155
Authorizer Name
C***** J* A******
Authorizer Telephone
4199576404
Authorizer Email
C********@n*******.com
Narrative
On july 31, 2019 a home at 100 park lane, washington, pa exploded. Three emergency responders and the customer at 100 park lane were sent to the hospital, one of whom required admittance. There were no life threatening injuries. The company was in the final stages of a pressure uprate project. The gas system pressure was being increased from low pressure (inches of water column) to medium pressure (40 psig). Service and mainline records did not indicate that 100 park lane was served from the system being uprated. Therefore a service regulator was not installed at the meter on the premises to control elevated pressure. Since no service regulator was installed, gas entered the house and reached appliances at a line pressure of 40 psig. The fire marshal's report indicates that the furnace in the home was the source of ignition. After the incident, it was discovered the service line for 100 park lane was tapped into a mainline that was part of the uprate project.
Occurred At 2019-07-31 16:03:00
Year 2019
Report Received Date 2019-08-30 00:00:00
Iyear 2019.0
Report Number 20190095.0
Supplemental Number 36146.0
Report Type Supplemental Final
Operator Id 2600 PHMSA Enforcement
Name Columbia Gas Of Pennsylvania
Operator Street Address 121 Champion Way Suite 100
Operator City Name Canonsburg
Operator State Abbreviation PA
Operator Postal Code 15317
Local Datetime 2019-07-31 15:45:00
Time Zone Eastern
Daylight Savings Ind Yes
Location Street Address 100 Park Lane
Location City Name Washington
Location County Name Washington
Location State Abbreviation PA
Location Postal Code 15301
Location Latitude 40.163007 Google Maps OpenStreetMap
Location Longitude -80.252453 Google Maps OpenStreetMap
Flow Cont Key Crit Ind Yes
Nrc Rpt Datetime 2019-07-31 16:29:00
Nrc Rpt Num 1253797 NRC Report How to search
Commodity Released Type Natural Gas
Unintentional Release 3.0
Intentional Release 0.0
Fatality Ind No
Fatal 0
Injury Ind Yes
Num Emp Injuries 0
Num Contr Injuries 0
Num Er Injuries 1
Num Worker Injuries 0
Num Gp Injuries 0
Injure 1
Ignite Ind No
Num Pub Evacuated 0.0
Incident Identified Datetime 2019-07-31 16:03:00
On Site Datetime 2019-07-31 16:03:00
Federal No
Location Type Private Property
Incident Area Type Underground
Incident Area Subtype Under Soil
Depth Of Cover 24.0
Other Underground Facilities No
Crossing No
Pipe Facility Type Privately Owned
System Part Involved Service
Installation Year 2013.0
Customer Type Single Family Residential
Was Efv Installed Before Ind No
Curb Valve Inst Before Inc Ind No
Pipe Diameter 1.0
Pipe Specification Unknown
Pipe Manufacturer Unknown
Material Involved Plastic
Plastic Type Polyethylene (Pe)
Wt Plastic Unknown Ind Unknown
Material Pe Pipe Code Unknown
Release Type Leak
Leak Type Other
Leak Type Other No Regulator For Uprate
Class Location Type Class 3 Location
Est Cost Oper Paid 272000.0
Est Cost Prop Damage 337.0
Est Cost Emergency 10000.0
Est Cost Other 0.0
Gas Cost In Mcf 0.0
Est Cost Unintentional Release 0.0
Est Cost Intentional Release 0.0
Prpty 282337.0
Commercial Affected 0.0
Industrial Affected 0.0
Residences Affected 63.0
Num Persons Hosp Not Ovnght 2.0
Num Injured Treated By Emt 0.0
Num Resident Building Affctd 1.0
Num Business Building Affctd 0.0
Accident Psig 40.0
Normal Psig 40.0
Mop Psig 45.0
Mop Cfr Section 192.619(A)(2) View CFR 49 §192
Maop Established Date 1982-07-15 00:00:00
Accident Pressure Pressure Did Not Exceed Maop
Gas Odorized System Type Odorized By Others
Gas Odorized Level 4
Scada In Place Ind No
Accident Identifier Notification From Emergency Responder
Investigation Status No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind Yes
Num Employees Tested 9
Num Employees Failed 0
Contractor Drug Test Ind Yes
Num Contractors Tested 8
Num Contractors Failed 0
Cause Incorrect Operation
Cause Details Other Incorrect Operation
Operation Type Other Incorrect Operation
Operation Details Service Regulator Was Not Installed At 100 Park Lane, Washington, Pa Before Increasing Line Pressure As Part Of An Uprate Operation.
Related Other Ind Yes
Operation Related Details While The Company Has Established Procedures And Processes To Be Taken For Uprates That Include Review Of Materials, Maps, And Records, In This Instance That Review Did Not Identify 100 Park Lane, Washington, Pa As Being Served From The System That Was Involved In The Uprate Project.
Category Type Construction
Operator Qualification Ind Yes
Qualified Individuals Yes, They Were Qualified For The Task(S)
Preparer Name R****** B****
Preparer Title Operations Compliance Manager
Preparer Email R*****@n*******.com
Preparer Telephone 17243217155
Authorizer Name C***** J* A******
Authorizer Telephone 4199576404
Authorizer Email C********@n*******.com
Narrative On july 31, 2019 a home at 100 park lane, washington, pa exploded. Three emergency responders and the customer at 100 park lane were sent to the hospital, one of whom required admittance. There were no life threatening injuries. The company was in the final stages of a pressure uprate project. The gas system pressure was being increased from low pressure (inches of water column) to medium pressure (40 psig). Service and mainline records did not indicate that 100 park lane was served from the system being uprated. Therefore a service regulator was not installed at the meter on the premises to control elevated pressure. Since no service regulator was installed, gas entered the house and reached appliances at a line pressure of 40 psig. The fire marshal's report indicates that the furnace in the home was the source of ignition. After the incident, it was discovered the service line for 100 park lane was tapped into a mainline that was part of the uprate project.