Incident details
Operator, cause, commodity and consequences with raw source fields.
GD incident on 2019-07-03 — NM
Operator
New Mexico Gas Company
Cause
Pipe, Weld, Or Joint Failure
Commodity
Natural Gas
Program
GD
Damage and Injuries
1 fatality
0 injuries
Property damage (nominal)
$182
Incident datetime
2019-07-03 15:40
Report number
Location
NM, CHAVEZ
Narrative
On july 3, 2019, an explosion occurred at 08:18 at 5204 n. Atkinson in roswell, nm 88201. At 8:34, nm gas was notified by dispatch that there was a house fire at the address. Nm gas arrived at the property at 08:53. The gas meter for the property had already been turned off at the service valve by the roswell fire department. Nm gas removed, capped off, and plugged the meter and customer service line. The service riser was soaped and no leaks were observed. Nm gas removed the meter and then probed that area where the meter was located for the presence of gas. No gas was detected. Nm gas left because the structure was still burning, preventing any further investigation. Nm gas returned to the scene at 12:15 after local authorities suppressed the structure fire. Nm gas began probing for gas at 12:45. At 13:10, gas odorant testing with a heath odorometer was conducted revealing sufficient odorant at 0.38% gas-in-air. At 13:20, the leak was pinpointed near the main and service at the sw corner of the intersection of isler and atkinson. Subsurface in ground gas concentration readings of 96% were registered at the sw corner of the intersection of isler and atkinson. At 15:15 excavation began at the sw corner of the intersection of isler and atkinson. At 15:40 nm gas uncovered the leak at the sw corner of the intersection of isler and atkinson. At 16:00 and 16:05, additional gas odorant testing with a heath odorometer was performed showing appropriate odorant levels at 0.32% gas-in-air. At 16:14, the leak was sealed off by squeezing off flow 54 feet upstream of the leak location. The leak was repaired at 18:40 by replacement of a 2" tee fitting. Re-lighting of the surrounding homes began at 19:00 for the 13 customers affected by the outage for repairs and was completed by 21:00. Five no access tags were left on customers' doors. Gas odorant testing was performed by nm gas one last time at 21:30. Readings confirmed proper odorant at 0.24% gas-in-air. Additional nrc report #1250929. Estimated damages were $262,687. Regarding questions part a #7 and part a #21c the form does not allow an entry of "unknown" because a calculation cannot be performed due to limited or unknown information needed to perform the calculation, PHMSA approved the amount entered in response to each of these questions.
Detailed record list
Occurred At
2019-07-03 15:40:00
Year
2019
Report Received Date
2019-08-02 00:00:00
Iyear
2019.0
Report Number
20190087.0
Supplemental Number
35282.0
Report Type
Supplemental Final
Operator Id
6141
Name
New Mexico Gas Company
Operator Street Address
7120 Wyoming Blvd N.e. Suite 20
Operator City Name
Albuquerque
Operator State Abbreviation
NM
Operator Postal Code
87109
Local Datetime
2019-07-03 08:34:00
Time Zone
Mountain
Daylight Savings Ind
No
Location Street Address
5204 N. Atkinson
Location City Name
Roswell
Location County Name
Chavez
Location State Abbreviation
NM
Location Postal Code
88201
Location Latitude
33.459478
Location Longitude
-104.506227
Flow Cont Squeeze Off Ind
Yes
Nrc Rpt Datetime
2019-07-03 15:52:00
Nrc Rpt Num
1250910
Commodity Released Type
Natural Gas
Unintentional Release
1.0
Intentional Release
0.0
Fatality Ind
Yes
Num Emp Fatalities
0
Num Contr Fatalities
0
Num Er Fatalities
0
Num Worker Fatalities
0
Num Gp Fatalities
1
Fatal
1
Injury Ind
No
Injure
0
Ignite Ind
Yes
Ignite Datetime
2019-07-03 08:34:00
How Extinguished
Local/state/federal Emergency Responder
Gas Consumed By Fire In Mcf
1
Explode Ind
Yes
Num Pub Evacuated
10.0
Incident Identified Datetime
2019-07-03 15:40:00
On Site Datetime
2019-07-03 15:40:00
Federal
No
Location Type
Public Property
Incident Area Type
Underground
Incident Area Subtype
Under A Building
Depth Of Cover
36.0
Other Underground Facilities
No
Crossing
No
Pipe Facility Type
Investor Owned
System Part Involved
Main
Installation Year
1990.0
Pipe Diameter
2.0
Pipe Specification
Astm D2513
Pipe Manufacturer
Drisco Pipe
Material Involved
Plastic
Plastic Type
Polyethylene (Pe)
Wt Plastic
0.216
Material Pe Pipe Code
3408
Release Type
Leak
Leak Type
Pinhole
Class Location Type
Class 2 Location
Est Cost Oper Paid
250000.0
Est Cost Prop Damage
182.0
Est Cost Emergency
12505.0
Est Cost Other
0.0
Gas Cost In Mcf
0.0
Est Cost Unintentional Release
0.0
Est Cost Intentional Release
0.0
Prpty
262687.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
13.0
Num Persons Hosp Not Ovnght
0.0
Num Injured Treated By Emt
0.0
Num Resident Building Affctd
13.0
Num Business Building Affctd
0.0
Accident Psig
45.0
Normal Psig
45.0
Mop Psig
51.0
Mop Cfr Section
192.619(A)(1)
Maop Established Date
2013-05-07 00:00:00
Accident Pressure
Pressure Did Not Exceed Maop
Gas Odorized System Type
Injection Pump
Gas Odorized Level
0.4
Scada In Place Ind
No
Accident Identifier
Notification From Emergency Responder
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Pipe, Weld, Or Joint Failure
Cause Details
Fusion Joint
Pwjf Failure Type
Fusion Joint
Plastic Joint Subtype
Butt, Electrofusion
Fpw Installed Year
1990
Fpw First Plastic Type
Polyethylene (Pe)
Fpw Second Plastic Type
Polyethylene (Pe)
Additional Pipe Bend Ind
Yes
Additional Crack Ind
Yes
Result Construction Ind
Yes
Result Construction Subtype
Poor Workmanship
Hydrotest Conducted Ind
Yes
Hydrotest Conducted Year
1990
Hydrotest Pressure
112
Preparer Name
A***** M*******
Preparer Title
Pipeline Safety Management Systems Manager
Preparer Email
A**************@n****.com
Preparer Telephone
505-697-3518
Authorizer Name
T** B******
Authorizer Title
Vp Eng-Gas Mgmt-Tech Services
Authorizer Telephone
5056973599
Authorizer Email
T**********@n****.com
Narrative
On july 3, 2019, an explosion occurred at 08:18 at 5204 n. Atkinson in roswell, nm 88201. At 8:34, nm gas was notified by dispatch that there was a house fire at the address. Nm gas arrived at the property at 08:53. The gas meter for the property had already been turned off at the service valve by the roswell fire department. Nm gas removed, capped off, and plugged the meter and customer service line. The service riser was soaped and no leaks were observed. Nm gas removed the meter and then probed that area where the meter was located for the presence of gas. No gas was detected. Nm gas left because the structure was still burning, preventing any further investigation. Nm gas returned to the scene at 12:15 after local authorities suppressed the structure fire. Nm gas began probing for gas at 12:45. At 13:10, gas odorant testing with a heath odorometer was conducted revealing sufficient odorant at 0.38% gas-in-air. At 13:20, the leak was pinpointed near the main and service at the sw corner of the intersection of isler and atkinson. Subsurface in ground gas concentration readings of 96% were registered at the sw corner of the intersection of isler and atkinson. At 15:15 excavation began at the sw corner of the intersection of isler and atkinson. At 15:40 nm gas uncovered the leak at the sw corner of the intersection of isler and atkinson. At 16:00 and 16:05, additional gas odorant testing with a heath odorometer was performed showing appropriate odorant levels at 0.32% gas-in-air. At 16:14, the leak was sealed off by squeezing off flow 54 feet upstream of the leak location. The leak was repaired at 18:40 by replacement of a 2" tee fitting. Re-lighting of the surrounding homes began at 19:00 for the 13 customers affected by the outage for repairs and was completed by 21:00. Five no access tags were left on customers' doors. Gas odorant testing was performed by nm gas one last time at 21:30. Readings confirmed proper odorant at 0.24% gas-in-air. Additional nrc report #1250929. Estimated damages were $262,687. Regarding questions part a #7 and part a #21c the form does not allow an entry of "unknown" because a calculation cannot be performed due to limited or unknown information needed to perform the calculation, PHMSA approved the amount entered in response to each of these questions.
| Occurred At | 2019-07-03 15:40:00 |
|---|---|
| Year | 2019 |
| Report Received Date | 2019-08-02 00:00:00 |
| Iyear | 2019.0 |
| Report Number | 20190087.0 |
| Supplemental Number | 35282.0 |
| Report Type | Supplemental Final |
| Operator Id | 6141 PHMSA Enforcement |
| Name | New Mexico Gas Company |
| Operator Street Address | 7120 Wyoming Blvd N.e. Suite 20 |
| Operator City Name | Albuquerque |
| Operator State Abbreviation | NM |
| Operator Postal Code | 87109 |
| Local Datetime | 2019-07-03 08:34:00 |
| Time Zone | Mountain |
| Daylight Savings Ind | No |
| Location Street Address | 5204 N. Atkinson |
| Location City Name | Roswell |
| Location County Name | Chavez |
| Location State Abbreviation | NM |
| Location Postal Code | 88201 |
| Location Latitude | 33.459478 Google Maps OpenStreetMap |
| Location Longitude | -104.506227 Google Maps OpenStreetMap |
| Flow Cont Squeeze Off Ind | Yes |
| Nrc Rpt Datetime | 2019-07-03 15:52:00 |
| Nrc Rpt Num | 1250910 NRC Report How to search |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 1.0 |
| Intentional Release | 0.0 |
| Fatality Ind | Yes |
| Num Emp Fatalities | 0 |
| Num Contr Fatalities | 0 |
| Num Er Fatalities | 0 |
| Num Worker Fatalities | 0 |
| Num Gp Fatalities | 1 |
| Fatal | 1 |
| Injury Ind | No |
| Injure | 0 |
| Ignite Ind | Yes |
| Ignite Datetime | 2019-07-03 08:34:00 |
| How Extinguished | Local/state/federal Emergency Responder |
| Gas Consumed By Fire In Mcf | 1 |
| Explode Ind | Yes |
| Num Pub Evacuated | 10.0 |
| Incident Identified Datetime | 2019-07-03 15:40:00 |
| On Site Datetime | 2019-07-03 15:40:00 |
| Federal | No |
| Location Type | Public Property |
| Incident Area Type | Underground |
| Incident Area Subtype | Under A Building |
| Depth Of Cover | 36.0 |
| Other Underground Facilities | No |
| Crossing | No |
| Pipe Facility Type | Investor Owned |
| System Part Involved | Main |
| Installation Year | 1990.0 |
| Pipe Diameter | 2.0 |
| Pipe Specification | Astm D2513 |
| Pipe Manufacturer | Drisco Pipe |
| Material Involved | Plastic |
| Plastic Type | Polyethylene (Pe) |
| Wt Plastic | 0.216 |
| Material Pe Pipe Code | 3408 |
| Release Type | Leak |
| Leak Type | Pinhole |
| Class Location Type | Class 2 Location |
| Est Cost Oper Paid | 250000.0 |
| Est Cost Prop Damage | 182.0 |
| Est Cost Emergency | 12505.0 |
| Est Cost Other | 0.0 |
| Gas Cost In Mcf | 0.0 |
| Est Cost Unintentional Release | 0.0 |
| Est Cost Intentional Release | 0.0 |
| Prpty | 262687.0 |
| Commercial Affected | 0.0 |
| Industrial Affected | 0.0 |
| Residences Affected | 13.0 |
| Num Persons Hosp Not Ovnght | 0.0 |
| Num Injured Treated By Emt | 0.0 |
| Num Resident Building Affctd | 13.0 |
| Num Business Building Affctd | 0.0 |
| Accident Psig | 45.0 |
| Normal Psig | 45.0 |
| Mop Psig | 51.0 |
| Mop Cfr Section | 192.619(A)(1) View CFR 49 §192 |
| Maop Established Date | 2013-05-07 00:00:00 |
| Accident Pressure | Pressure Did Not Exceed Maop |
| Gas Odorized System Type | Injection Pump |
| Gas Odorized Level | 0.4 |
| Scada In Place Ind | No |
| Accident Identifier | Notification From Emergency Responder |
| Investigation Status | No, the facility was not monitored by a controller(s) at the time of the incident |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Pipe, Weld, Or Joint Failure |
| Cause Details | Fusion Joint |
| Pwjf Failure Type | Fusion Joint |
| Plastic Joint Subtype | Butt, Electrofusion |
| Fpw Installed Year | 1990 |
| Fpw First Plastic Type | Polyethylene (Pe) |
| Fpw Second Plastic Type | Polyethylene (Pe) |
| Additional Pipe Bend Ind | Yes |
| Additional Crack Ind | Yes |
| Result Construction Ind | Yes |
| Result Construction Subtype | Poor Workmanship |
| Hydrotest Conducted Ind | Yes |
| Hydrotest Conducted Year | 1990 |
| Hydrotest Pressure | 112 |
| Preparer Name | A***** M******* |
| Preparer Title | Pipeline Safety Management Systems Manager |
| Preparer Email | A**************@n****.com |
| Preparer Telephone | 505-697-3518 |
| Authorizer Name | T** B****** |
| Authorizer Title | Vp Eng-Gas Mgmt-Tech Services |
| Authorizer Telephone | 5056973599 |
| Authorizer Email | T**********@n****.com |
| Narrative | On july 3, 2019, an explosion occurred at 08:18 at 5204 n. Atkinson in roswell, nm 88201. At 8:34, nm gas was notified by dispatch that there was a house fire at the address. Nm gas arrived at the property at 08:53. The gas meter for the property had already been turned off at the service valve by the roswell fire department. Nm gas removed, capped off, and plugged the meter and customer service line. The service riser was soaped and no leaks were observed. Nm gas removed the meter and then probed that area where the meter was located for the presence of gas. No gas was detected. Nm gas left because the structure was still burning, preventing any further investigation. Nm gas returned to the scene at 12:15 after local authorities suppressed the structure fire. Nm gas began probing for gas at 12:45. At 13:10, gas odorant testing with a heath odorometer was conducted revealing sufficient odorant at 0.38% gas-in-air. At 13:20, the leak was pinpointed near the main and service at the sw corner of the intersection of isler and atkinson. Subsurface in ground gas concentration readings of 96% were registered at the sw corner of the intersection of isler and atkinson. At 15:15 excavation began at the sw corner of the intersection of isler and atkinson. At 15:40 nm gas uncovered the leak at the sw corner of the intersection of isler and atkinson. At 16:00 and 16:05, additional gas odorant testing with a heath odorometer was performed showing appropriate odorant levels at 0.32% gas-in-air. At 16:14, the leak was sealed off by squeezing off flow 54 feet upstream of the leak location. The leak was repaired at 18:40 by replacement of a 2" tee fitting. Re-lighting of the surrounding homes began at 19:00 for the 13 customers affected by the outage for repairs and was completed by 21:00. Five no access tags were left on customers' doors. Gas odorant testing was performed by nm gas one last time at 21:30. Readings confirmed proper odorant at 0.24% gas-in-air. Additional nrc report #1250929. Estimated damages were $262,687. Regarding questions part a #7 and part a #21c the form does not allow an entry of "unknown" because a calculation cannot be performed due to limited or unknown information needed to perform the calculation, PHMSA approved the amount entered in response to each of these questions. |