GD incident on 2019-04-04 — PA
Operator
Ugi Utilities, Inc
Cause
Excavation Issue
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$1,000
Incident datetime
2019-04-04 10:29
Report number
Location
PA, DAUPHIN
Narrative
On april 4, 2019 3rd party contractor was performing excavation using horizontal directional drilling (hdd) methods along the 200 block of west chocolate avenue. In the process of hdd work, the 3rd party contractor failed to expose a properly marked ugi facility in the public right of way, that happened to be in the bore path. The drill subsequently pierced our main which was part of a distribution network in a commercial area. This event is being reported as an incident due to the cost of this repair exceeding the $50,000 reporting threshold. Please note ugi updated the nrc on april 5, 2019 at approximately 16:16 with gas lost calculations and the amount of individuals evacuated. The updated nrc number is 1241967.
Detailed record list
Occurred At
2019-04-04 10:29:00
Year
2019
Report Received Date
2019-05-03 00:00:00
Iyear
2019.0
Report Number
20190046.0
Supplemental Number
32074.0
Report Type
Original Final
Operator Id
20010
Name
Ugi Utilities, Inc
Operator Street Address
1 Ugi Drive
Operator City Name
Denver
Operator State Abbreviation
PA
Operator Postal Code
17517
Local Datetime
2019-04-04 10:29:00
Location Street Address
201 W Chocolate Avenue
Location City Name
Derry
Location County Name
Dauphin
Location State Abbreviation
PA
Location Postal Code
17033
Location Latitude
40.2841
Location Longitude
-76.6544
Nrc Rpt Datetime
2019-04-04 22:03:00
Nrc Rpt Num
1241904
Commodity Released Type
Natural Gas
Unintentional Release
225.0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
75.0
Incident Identified Datetime
2019-04-04 10:29:00
On Site Datetime
2019-04-04 10:39:00
Federal
No
Location Type
Public Property
Incident Area Type
Underground
Incident Area Subtype
Under Pavement
Depth Of Cover
36.0
Crossing
No
Pipe Facility Type
Investor Owned
System Part Involved
Main
Installation Year
2003.0
Pipe Diameter
4.0
Pipe Specification
Astm D2513
Pipe Manufacturer
Driscoplex
Material Involved
Plastic
Plastic Type
Polyethylene (Pe)
Plastic Sdr
11
Material Pe Pipe Code
2406
Release Type
Mechanical Puncture
Puncture Axial
4.0
Puncture Circum
2.0
Class Location Type
Class 3 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
1000.0
Est Cost Emergency
59000.0
Est Cost Other
0.0
Est Cost Unintentional Release
1000.0
Prpty
61000.0
Commercial Affected
223.0
Industrial Affected
2.0
Residences Affected
24.0
Accident Psig
54.0
Normal Psig
54.0
Mop Psig
60.0
Accident Pressure
Pressure Did Not Exceed Maop
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Accident Identifier
Notification From Emergency Responder
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
This incident occurred as a result of a 3rd party excavation damage on a medium pressure distribution line. Actions by the controller were not needed to detect or respond to the incident.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Excavation Damage
Cause Details
Excavation Damage By Third Party
Ex Party Type
Excavation Damage By Third Party
Prior Notification Ind
Yes
One Call System Ind
Yes
Notify Cga Dirt
No
Public Row Ind
Yes
Public Subtype
State Highway
Excavator Type
Contractor
Excavator Equipment
Directional Drilling
Work Performed
Electric
One Call Notified Ind
Yes
One Call Ticket Num
20190864239
Locator Type
Utility Owner
Visible Marks
Yes
Service Interruption
Yes
Service Interruption Hours
22.0
Root Cause Category
Excavation Issue
Root Cause Type
Improper Excavation Practice Not Listed Above
Preparer Name
J*** T*****
Preparer Title
Senior Engineer
Preparer Email
J******@u**.com
Preparer Telephone
717 675 4606
Authorizer Name
K**** A** B*****
Authorizer Title
Vp Engineering And Operations Support
Authorizer Telephone
6107963601
Authorizer Email
K******@u**.com
Narrative
On april 4, 2019 3rd party contractor was performing excavation using horizontal directional drilling (hdd) methods along the 200 block of west chocolate avenue. In the process of hdd work, the 3rd party contractor failed to expose a properly marked ugi facility in the public right of way, that happened to be in the bore path. The drill subsequently pierced our main which was part of a distribution network in a commercial area. This event is being reported as an incident due to the cost of this repair exceeding the $50,000 reporting threshold. Please note ugi updated the nrc on april 5, 2019 at approximately 16:16 with gas lost calculations and the amount of individuals evacuated. The updated nrc number is 1241967.
| Occurred At | 2019-04-04 10:29:00 |
|---|---|
| Year | 2019 |
| Report Received Date | 2019-05-03 00:00:00 |
| Iyear | 2019.0 |
| Report Number | 20190046.0 |
| Supplemental Number | 32074.0 |
| Report Type | Original Final |
| Operator Id | 20010 PHMSA Enforcement |
| Name | Ugi Utilities, Inc |
| Operator Street Address | 1 Ugi Drive |
| Operator City Name | Denver |
| Operator State Abbreviation | PA |
| Operator Postal Code | 17517 |
| Local Datetime | 2019-04-04 10:29:00 |
| Location Street Address | 201 W Chocolate Avenue |
| Location City Name | Derry |
| Location County Name | Dauphin |
| Location State Abbreviation | PA |
| Location Postal Code | 17033 |
| Location Latitude | 40.2841 Google Maps OpenStreetMap |
| Location Longitude | -76.6544 Google Maps OpenStreetMap |
| Nrc Rpt Datetime | 2019-04-04 22:03:00 |
| Nrc Rpt Num | 1241904 NRC Report How to search |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 225.0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Ignite Ind | No |
| Explode Ind | No |
| Num Pub Evacuated | 75.0 |
| Incident Identified Datetime | 2019-04-04 10:29:00 |
| On Site Datetime | 2019-04-04 10:39:00 |
| Federal | No |
| Location Type | Public Property |
| Incident Area Type | Underground |
| Incident Area Subtype | Under Pavement |
| Depth Of Cover | 36.0 |
| Crossing | No |
| Pipe Facility Type | Investor Owned |
| System Part Involved | Main |
| Installation Year | 2003.0 |
| Pipe Diameter | 4.0 |
| Pipe Specification | Astm D2513 |
| Pipe Manufacturer | Driscoplex |
| Material Involved | Plastic |
| Plastic Type | Polyethylene (Pe) |
| Plastic Sdr | 11 |
| Material Pe Pipe Code | 2406 |
| Release Type | Mechanical Puncture |
| Puncture Axial | 4.0 |
| Puncture Circum | 2.0 |
| Class Location Type | Class 3 Location |
| Est Cost Oper Paid | 0.0 |
| Est Cost Prop Damage | 1000.0 |
| Est Cost Emergency | 59000.0 |
| Est Cost Other | 0.0 |
| Est Cost Unintentional Release | 1000.0 |
| Prpty | 61000.0 |
| Commercial Affected | 223.0 |
| Industrial Affected | 2.0 |
| Residences Affected | 24.0 |
| Accident Psig | 54.0 |
| Normal Psig | 54.0 |
| Mop Psig | 60.0 |
| Accident Pressure | Pressure Did Not Exceed Maop |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Accident Identifier | Notification From Emergency Responder |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | This incident occurred as a result of a 3rd party excavation damage on a medium pressure distribution line. Actions by the controller were not needed to detect or respond to the incident. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Excavation Damage |
| Cause Details | Excavation Damage By Third Party |
| Ex Party Type | Excavation Damage By Third Party |
| Prior Notification Ind | Yes |
| One Call System Ind | Yes |
| Notify Cga Dirt | No |
| Public Row Ind | Yes |
| Public Subtype | State Highway |
| Excavator Type | Contractor |
| Excavator Equipment | Directional Drilling |
| Work Performed | Electric |
| One Call Notified Ind | Yes |
| One Call Ticket Num | 20190864239 |
| Locator Type | Utility Owner |
| Visible Marks | Yes |
| Service Interruption | Yes |
| Service Interruption Hours | 22.0 |
| Root Cause Category | Excavation Issue |
| Root Cause Type | Improper Excavation Practice Not Listed Above |
| Preparer Name | J*** T***** |
| Preparer Title | Senior Engineer |
| Preparer Email | J******@u**.com |
| Preparer Telephone | 717 675 4606 |
| Authorizer Name | K**** A** B***** |
| Authorizer Title | Vp Engineering And Operations Support |
| Authorizer Telephone | 6107963601 |
| Authorizer Email | K******@u**.com |
| Narrative | On april 4, 2019 3rd party contractor was performing excavation using horizontal directional drilling (hdd) methods along the 200 block of west chocolate avenue. In the process of hdd work, the 3rd party contractor failed to expose a properly marked ugi facility in the public right of way, that happened to be in the bore path. The drill subsequently pierced our main which was part of a distribution network in a commercial area. This event is being reported as an incident due to the cost of this repair exceeding the $50,000 reporting threshold. Please note ugi updated the nrc on april 5, 2019 at approximately 16:16 with gas lost calculations and the amount of individuals evacuated. The updated nrc number is 1241967. |
External Resources
PHMSA pipeline safety insights.
Product
Features
Company
All rights reserved. Copyright © by ClearPHMSA