GD incident on 2019-04-02 — NJ

Operator
New Jersey Natural Gas Co
Cause
Excavation Issue
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$91,658
Incident datetime
2019-04-02 11:32
Report number
Location
NJ, OCEAN
Narrative
On april 2, 2019, njng responded to an odor called in by ocean county sherriff's office at 11:32 a.M. Upon arrival at 2313 route 547, manchester at 11:40 a.M., gas-in-air percentages were confirmed within the vicinity of an excavator installing a new gas main. Further investigation confirmed the excavator damaged a gas facility while horizontal directionally drilling the new gas main. Njng confirmed the excavator damaged the 12-inch steel main located under the roadway while reaming which created a dent and small mechanical puncture in the pipeline. The excavator had a valid one call ticket and the 12-inch steel main was properly located. Njng closed valves to shut down gas flow to the damaged facility. The damaged section was blown down and replaced on april 3, 2019. There were no injuries or fatalities and the escaping natural gas did not ignite or explode as a result of this damage. This was a reportable incident as the operator emergency response and repair costs exceeded $50,000.
Detailed record list
Occurred At
2019-04-02 11:32:00
Year
2019
Report Received Date
2019-04-26 00:00:00
Iyear
2019.0
Report Number
20190040.0
Supplemental Number
32523.0
Report Type
Supplemental Final
Operator Id
Name
New Jersey Natural Gas Co
Operator Street Address
1415 Wyckoff Road
Operator City Name
Wall
Operator State Abbreviation
NJ
Operator Postal Code
07719
Local Datetime
2019-04-02 11:32:00
Location Street Address
2313 Route 547
Location City Name
Manchester
Location County Name
Ocean
Location State Abbreviation
NJ
Location Postal Code
08759
Location Latitude
Location Longitude
Nrc Rpt Datetime
2019-04-03 13:52:00
Nrc Rpt Num
Commodity Released Type
Natural Gas
Unintentional Release
12.8
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
4.0
Incident Identified Datetime
2019-04-02 11:32:00
On Site Datetime
2019-04-02 11:40:00
Federal
No
Location Type
Public Property
Incident Area Type
Underground
Incident Area Subtype
Under Pavement
Depth Of Cover
61.0
Crossing
No
Pipe Facility Type
Investor Owned
System Part Involved
Main
Installation Year
1988.0
Pipe Diameter
12.0
Pipe Specification
Api 5l
Pipe Manufacturer
Unknown
Material Involved
Steel
Steel Seam Type
Other
Steel Seam Type Details
Unknown
Wt Steel
0.25
Release Type
Mechanical Puncture
Puncture Axial
0.1
Puncture Circum
0.1
Class Location Type
Class 3 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
91658.0
Est Cost Emergency
38452.0
Est Cost Other
0.0
Est Cost Unintentional Release
123.0
Prpty
130233.0
Commercial Affected
2.0
Industrial Affected
0.0
Residences Affected
0.0
Accident Psig
52.0
Normal Psig
52.0
Mop Psig
60.0
Accident Pressure
Pressure Did Not Exceed Maop
Scada In Place Ind
No
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Contractor Working For The Operator
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Excavation Damage
Cause Details
Excavation Damage By Operator's Contractor (Second Party)
Ex Party Type
Excavation Damage By Operator's Contractor (Second Party)
Notify Cga Dirt
No
Public Row Ind
Yes
Public Subtype
County Road
Excavator Type
Contractor
Excavator Equipment
Directional Drilling
Work Performed
Natural Gas
One Call Notified Ind
Yes
One Call Ticket Num
190601126
Locator Type
Contract Locator
Visible Marks
Yes
Service Interruption
Yes
Service Interruption Hours
9.0
Root Cause Category
Excavation Issue
Root Cause Type
Excavator Failed To Maintain Clearance After Verifying Marks
Preparer Name
M***** K***
Preparer Title
Director - System Enhancement
Preparer Email
M*****@n***.com
Preparer Telephone
732-919-8035
Preparer Fax
732-919-0936
Authorizer Name
M***** K***
Authorizer Title
Director - System Enhancement
Authorizer Telephone
732-919-8035
Authorizer Email
M*****@n***.com
Narrative
On april 2, 2019, njng responded to an odor called in by ocean county sherriff's office at 11:32 a.M. Upon arrival at 2313 route 547, manchester at 11:40 a.M., gas-in-air percentages were confirmed within the vicinity of an excavator installing a new gas main. Further investigation confirmed the excavator damaged a gas facility while horizontal directionally drilling the new gas main. Njng confirmed the excavator damaged the 12-inch steel main located under the roadway while reaming which created a dent and small mechanical puncture in the pipeline. The excavator had a valid one call ticket and the 12-inch steel main was properly located. Njng closed valves to shut down gas flow to the damaged facility. The damaged section was blown down and replaced on april 3, 2019. There were no injuries or fatalities and the escaping natural gas did not ignite or explode as a result of this damage. This was a reportable incident as the operator emergency response and repair costs exceeded $50,000.
Occurred At 2019-04-02 11:32:00
Year 2019
Report Received Date 2019-04-26 00:00:00
Iyear 2019.0
Report Number 20190040.0
Supplemental Number 32523.0
Report Type Supplemental Final
Operator Id 13299 PHMSA Enforcement
Name New Jersey Natural Gas Co
Operator Street Address 1415 Wyckoff Road
Operator City Name Wall
Operator State Abbreviation NJ
Operator Postal Code 07719
Local Datetime 2019-04-02 11:32:00
Location Street Address 2313 Route 547
Location City Name Manchester
Location County Name Ocean
Location State Abbreviation NJ
Location Postal Code 08759
Location Latitude 40.0162101 Google Maps OpenStreetMap
Location Longitude -74.3101675 Google Maps OpenStreetMap
Nrc Rpt Datetime 2019-04-03 13:52:00
Nrc Rpt Num 1241762 NRC Report How to search
Commodity Released Type Natural Gas
Unintentional Release 12.8
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Ignite Ind No
Explode Ind No
Num Pub Evacuated 4.0
Incident Identified Datetime 2019-04-02 11:32:00
On Site Datetime 2019-04-02 11:40:00
Federal No
Location Type Public Property
Incident Area Type Underground
Incident Area Subtype Under Pavement
Depth Of Cover 61.0
Crossing No
Pipe Facility Type Investor Owned
System Part Involved Main
Installation Year 1988.0
Pipe Diameter 12.0
Pipe Specification Api 5l
Pipe Manufacturer Unknown
Material Involved Steel
Steel Seam Type Other
Steel Seam Type Details Unknown
Wt Steel 0.25
Release Type Mechanical Puncture
Puncture Axial 0.1
Puncture Circum 0.1
Class Location Type Class 3 Location
Est Cost Oper Paid 0.0
Est Cost Prop Damage 91658.0
Est Cost Emergency 38452.0
Est Cost Other 0.0
Est Cost Unintentional Release 123.0
Prpty 130233.0
Commercial Affected 2.0
Industrial Affected 0.0
Residences Affected 0.0
Accident Psig 52.0
Normal Psig 52.0
Mop Psig 60.0
Accident Pressure Pressure Did Not Exceed Maop
Scada In Place Ind No
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Contractor Working For The Operator
Investigation Status No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Excavation Damage
Cause Details Excavation Damage By Operator's Contractor (Second Party)
Ex Party Type Excavation Damage By Operator's Contractor (Second Party)
Notify Cga Dirt No
Public Row Ind Yes
Public Subtype County Road
Excavator Type Contractor
Excavator Equipment Directional Drilling
Work Performed Natural Gas
One Call Notified Ind Yes
One Call Ticket Num 190601126
Locator Type Contract Locator
Visible Marks Yes
Service Interruption Yes
Service Interruption Hours 9.0
Root Cause Category Excavation Issue
Root Cause Type Excavator Failed To Maintain Clearance After Verifying Marks
Preparer Name M***** K***
Preparer Title Director - System Enhancement
Preparer Email M*****@n***.com
Preparer Telephone 732-919-8035
Preparer Fax 732-919-0936
Authorizer Name M***** K***
Authorizer Title Director - System Enhancement
Authorizer Telephone 732-919-8035
Authorizer Email M*****@n***.com
Narrative On april 2, 2019, njng responded to an odor called in by ocean county sherriff's office at 11:32 a.M. Upon arrival at 2313 route 547, manchester at 11:40 a.M., gas-in-air percentages were confirmed within the vicinity of an excavator installing a new gas main. Further investigation confirmed the excavator damaged a gas facility while horizontal directionally drilling the new gas main. Njng confirmed the excavator damaged the 12-inch steel main located under the roadway while reaming which created a dent and small mechanical puncture in the pipeline. The excavator had a valid one call ticket and the 12-inch steel main was properly located. Njng closed valves to shut down gas flow to the damaged facility. The damaged section was blown down and replaced on april 3, 2019. There were no injuries or fatalities and the escaping natural gas did not ignite or explode as a result of this damage. This was a reportable incident as the operator emergency response and repair costs exceeded $50,000.