GD incident on 2019-02-16 — UT

Operator
Dominion Energy Utah/wyoming/idaho
Cause
Other Outside Force Damage
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$300
Incident datetime
2019-02-16 19:58
Report number
Location
UT, SALT LAKE COUNTY
Narrative
On february 16, 2019 dominion energy utah (deu) was notified of a house fire at 9740 bypass road, alta, utah. Deu sent a technician to the site. Upon arrival the technician was unable to access the gas meter due to excessive amounts of snow (about 12' of snow from ground level). Later, deu dispatch received an updated call from the fire department stating that a natural gas explosion may have occurred. Additional resources were sent to assist with securing the service line to the property. Company reported the incident upon discovery and suspected natural gas involvement. After the fire was contained, deu crews excavated the natural gas meter and found it was damaged. The gas service line to the unit was secured at 02:30 on february 17, 2019. A viewing of the meter and riser evidence was conducted with the involved parties and the state of utah pipeline safety on april 23, 2019. Based on information from the event investigation, deu believes that snow load, along with a snow slide from the roof of the building damaged the natural gas meter causing a leak. Leaking gas accumulated and ignited from an undetermined ignition source. This is substantiated through investigation and documented in the unified fire investigation report.
Detailed record list
Occurred At
2019-02-16 19:58:00
Year
2019
Report Received Date
2019-03-18 00:00:00
Iyear
2019.0
Report Number
20190028.0
Supplemental Number
32427.0
Report Type
Supplemental Final
Operator Id
Name
Dominion Energy Utah/wyoming/idaho
Operator Street Address
333 South State Street P.o. Box 45360
Operator City Name
Salt Lake City
Operator State Abbreviation
UT
Operator Postal Code
84111
Local Datetime
2019-02-16 16:00:00
Location Street Address
9740 Bypass Road
Location City Name
Alta
Location County Name
Salt Lake County
Location State Abbreviation
UT
Location Postal Code
84092
Location Latitude
Location Longitude
Nrc Rpt Datetime
2019-02-16 20:24:00
Nrc Rpt Num
Commodity Released Type
Natural Gas
Unintentional Release
11.32
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
Yes
Explode Ind
Yes
Num Pub Evacuated
3.0
Incident Identified Datetime
2019-02-16 19:58:00
On Site Datetime
2019-02-16 16:21:00
Federal
No
Location Type
Private Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance (E.g. Value Or Regulator Station, Outdoor Meter Set)
Crossing
No
Pipe Facility Type
Investor Owned
System Part Involved
Outside Meter/regulator Set
Installation Year
2016.0
Material Involved
Steel
Steel Seam Type
Other
Steel Seam Type Details
Unknown
Release Type
Leak
Leak Type
Crack
Class Location Type
Class 3 Location
Est Cost Oper Paid
650000.0
Est Cost Prop Damage
300.0
Est Cost Emergency
9400.0
Est Cost Other
0.0
Est Cost Unintentional Release
50.0
Prpty
659750.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
3.0
Accident Psig
45.0
Normal Psig
45.0
Mop Psig
60.0
Accident Pressure
Pressure Did Not Exceed Maop
Scada In Place Ind
No
Accident Identifier
Notification From Emergency Responder
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Other Outside Force Damage
Cause Details
Other Outside Force Damage
Outside Force Type
Other Outside Force Damage
Osf Other Details
Accumulated Snow And Snow Slide Onto The Natural Gas Meter.
Preparer Name
L***** S*****
Preparer Title
Engineer-Pipeline Compliance
Preparer Email
L**************@d*************.com
Preparer Telephone
8013243746
Authorizer Name
R*** H***
Authorizer Title
Manager- Gas Operations
Authorizer Telephone
8013243374
Authorizer Email
R********@d*************.com
Narrative
On february 16, 2019 dominion energy utah (deu) was notified of a house fire at 9740 bypass road, alta, utah. Deu sent a technician to the site. Upon arrival the technician was unable to access the gas meter due to excessive amounts of snow (about 12' of snow from ground level). Later, deu dispatch received an updated call from the fire department stating that a natural gas explosion may have occurred. Additional resources were sent to assist with securing the service line to the property. Company reported the incident upon discovery and suspected natural gas involvement. After the fire was contained, deu crews excavated the natural gas meter and found it was damaged. The gas service line to the unit was secured at 02:30 on february 17, 2019. A viewing of the meter and riser evidence was conducted with the involved parties and the state of utah pipeline safety on april 23, 2019. Based on information from the event investigation, deu believes that snow load, along with a snow slide from the roof of the building damaged the natural gas meter causing a leak. Leaking gas accumulated and ignited from an undetermined ignition source. This is substantiated through investigation and documented in the unified fire investigation report.
Occurred At 2019-02-16 19:58:00
Year 2019
Report Received Date 2019-03-18 00:00:00
Iyear 2019.0
Report Number 20190028.0
Supplemental Number 32427.0
Report Type Supplemental Final
Operator Id 12876 PHMSA Enforcement
Name Dominion Energy Utah/wyoming/idaho
Operator Street Address 333 South State Street P.o. Box 45360
Operator City Name Salt Lake City
Operator State Abbreviation UT
Operator Postal Code 84111
Local Datetime 2019-02-16 16:00:00
Location Street Address 9740 Bypass Road
Location City Name Alta
Location County Name Salt Lake County
Location State Abbreviation UT
Location Postal Code 84092
Location Latitude 40.586376 Google Maps OpenStreetMap
Location Longitude -111.648972 Google Maps OpenStreetMap
Nrc Rpt Datetime 2019-02-16 20:24:00
Nrc Rpt Num 1237885 NRC Report How to search
Commodity Released Type Natural Gas
Unintentional Release 11.32
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Ignite Ind Yes
Explode Ind Yes
Num Pub Evacuated 3.0
Incident Identified Datetime 2019-02-16 19:58:00
On Site Datetime 2019-02-16 16:21:00
Federal No
Location Type Private Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance (E.g. Value Or Regulator Station, Outdoor Meter Set)
Crossing No
Pipe Facility Type Investor Owned
System Part Involved Outside Meter/regulator Set
Installation Year 2016.0
Material Involved Steel
Steel Seam Type Other
Steel Seam Type Details Unknown
Release Type Leak
Leak Type Crack
Class Location Type Class 3 Location
Est Cost Oper Paid 650000.0
Est Cost Prop Damage 300.0
Est Cost Emergency 9400.0
Est Cost Other 0.0
Est Cost Unintentional Release 50.0
Prpty 659750.0
Commercial Affected 0.0
Industrial Affected 0.0
Residences Affected 3.0
Accident Psig 45.0
Normal Psig 45.0
Mop Psig 60.0
Accident Pressure Pressure Did Not Exceed Maop
Scada In Place Ind No
Accident Identifier Notification From Emergency Responder
Investigation Status No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Other Outside Force Damage
Cause Details Other Outside Force Damage
Outside Force Type Other Outside Force Damage
Osf Other Details Accumulated Snow And Snow Slide Onto The Natural Gas Meter.
Preparer Name L***** S*****
Preparer Title Engineer-Pipeline Compliance
Preparer Email L**************@d*************.com
Preparer Telephone 8013243746
Authorizer Name R*** H***
Authorizer Title Manager- Gas Operations
Authorizer Telephone 8013243374
Authorizer Email R********@d*************.com
Narrative On february 16, 2019 dominion energy utah (deu) was notified of a house fire at 9740 bypass road, alta, utah. Deu sent a technician to the site. Upon arrival the technician was unable to access the gas meter due to excessive amounts of snow (about 12' of snow from ground level). Later, deu dispatch received an updated call from the fire department stating that a natural gas explosion may have occurred. Additional resources were sent to assist with securing the service line to the property. Company reported the incident upon discovery and suspected natural gas involvement. After the fire was contained, deu crews excavated the natural gas meter and found it was damaged. The gas service line to the unit was secured at 02:30 on february 17, 2019. A viewing of the meter and riser evidence was conducted with the involved parties and the state of utah pipeline safety on april 23, 2019. Based on information from the event investigation, deu believes that snow load, along with a snow slide from the roof of the building damaged the natural gas meter causing a leak. Leaking gas accumulated and ignited from an undetermined ignition source. This is substantiated through investigation and documented in the unified fire investigation report.