HL incident on 2018-11-30 — TX

Operator
West Coast Terminal Pipeline (Wctp)
Cause
Equipment Failure
Commodity
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$84,000
Incident datetime
2018-11-30 12:00
Report number
Location
TX
Narrative
At approximately 1200 on 11/30/18 during a facility inspection, a stain was discovered at the edge of gasoline tank 80002, originally estimated to be 1.7 gallons. The stained soil was cleaned up. At 1530, continued investigation found elevated lel readings in the soil at the edge of the tank. Threatened release notifications (ca oes and nrc among them) were made and further response and investigative measures (emptying tank, gas-free, testing) were employed. On 12/11/18, a small crack in the weld of the tank's water draw sump was discovered. Telephonic release notifications were made (cal oes #18-8154 @1237 and nrc #1232664 @ 1242 as the estimated property damage exceeded the $50,000 threshold. No further gasoline was released. This type of drain-dry tank allows flexing of the tank bottom at the drain dry sump location. Recent heavy rains caused soil compaction in this area allowing added stress on the floor plate welds causing a crack, approximately 1/8 in diameter and 3-ft long. Note: part a, #6 there were three nrc notifications made. The first (#1231759) notified of a threatened release, the second (#1232664) confirming the probability that the $50,000 reporting threshold would be exceeded and the third (#1232845) was the PHMSA-required 48 hour follow-up notification. Note: part a, #14 while this tank was taken out of service, pipeline and other facility operations were not affected.
Detailed record list
Report Received Date
2018-12-26 00:00:00
Iyear
2018
Report Number
20180408
Supplemental Number
31401
Report Type
Original Final
Operator Id
Name
West Coast Terminal Pipeline (Wctp)
Operator Street Address
1001 Louisiana St., Suite 1000
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2018-11-30 15:30:00
Location Latitude
Location Longitude
Commodity Released Type
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype
Gasoline (Non-Ethanol)
Unintentional Release Bbls
0.1
Recovered Bbls
0.1
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2018-11-30 12:00:00
System Part Involved
Onshore Breakout Tank Or Storage Vessel, Including Attached Appurtenances
On Off Shore
Onshore
Shutdown Due Accident Ind
No
Shutdown Explain
While This Tank Was Taken Out Of Service, Pipeline And Other Facility Operations
On Site Datetime
2018-11-30 12:00:00
Nrc Rpt Datetime
2018-12-11 12:42:00
Nrc Rpt Num
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Carson Terminal
Segment Name
Carson Terminal
Onshore State Abbreviation
Ca
Onshore Postal Code
90810
Onshore City Name
Carson
Onshore County Name
Los Angeles
Designated Location
Milepost/valve Station
Designated Name
Carson Termin
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Tank, Including Attached Appurtenances
Crossing
No
Pipe Facility Type
Intrastate
Item Involved
Tank/vessel
Tank Vessel Subtype
Single Bottom System
Tank Type
Atmospheric
Installation Year
1990
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Crack
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
High Pop Ind
Yes
High Pop Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
3
Est Cost Prop Damage
84000
Est Cost Emergency
2751
Est Cost Environmental
0
Est Cost Other
0
Prpty
86754
Accident Psig
2.85
Mop Psig
14.5
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
No
Cpm In Place Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
The tank is independent of the scada system, not controlled by the field control room.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Other Equipment Failure
Eq Failure Type
Other Equipment Failure
Failure Details
Recent Heavy Rains Caused Soil Compaction In This Area Allowing Added Stress On The Floor Plate Welds Causing A Crack, Approximately 1/8 In Diameter And 3-Ft Long.
Additional Support Ind
Yes
Preparer Name
S**** M*******
Preparer Title
Mgr Ccs - Pacific
Preparer Email
S*************@k***********.com
Preparer Telephone
909-873-5146
Preparer Fax
303-984-3620
Prepared Date
2018-12-26 00:00:00
Authorizer Name
E***** A* F***
Authorizer Telephone
713-369-9454
Authorizer Title
Director Ccs
Authorizer Email
B********@k***********.com
Narrative
A************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************@1237 and nrc #1232664 @ 1242 as the estimated property damage exceeded the $50,000 threshold. No further gasoline was released. This type of drain-dry tank allows flexing of the tank bottom at the drain dry sump location. Recent heavy rains caused soil compaction in this area allowing added stress on the floor plate welds causing a crack, approximately 1/8 in diameter and 3-ft long. Note: part a, #6 there were three nrc notifications made. The first (#1231759) notified of a threatened release, the second (#1232664) confirming the probability that the $50,000 reporting threshold would be exceeded and the third (#1232845) was the PHMSA-required 48 hour follow-up notification. ***********************************************************************************************************************.
Report Received Date 2018-12-26 00:00:00
Iyear 2018
Report Number 20180408
Supplemental Number 31401
Report Type Original Final
Operator Id 32688 PHMSA Enforcement
Name West Coast Terminal Pipeline (Wctp)
Operator Street Address 1001 Louisiana St., Suite 1000
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Local Datetime 2018-11-30 15:30:00
Location Latitude 33.801639 Google Maps OpenStreetMap
Location Longitude -118.23209 Google Maps OpenStreetMap
Commodity Released Type Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype Gasoline (Non-Ethanol)
Unintentional Release Bbls 0.1
Recovered Bbls 0.1
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
Incident Identified Datetime 2018-11-30 12:00:00
System Part Involved Onshore Breakout Tank Or Storage Vessel, Including Attached Appurtenances
On Off Shore Onshore
Shutdown Due Accident Ind No
Shutdown Explain While This Tank Was Taken Out Of Service, Pipeline And Other Facility Operations
On Site Datetime 2018-11-30 12:00:00
Nrc Rpt Datetime 2018-12-11 12:42:00
Nrc Rpt Num 1232664 NRC Report How to search
Ignite Ind No
Explode Ind No
Num Pub Evacuated 0
Pipe Fac Name Carson Terminal
Segment Name Carson Terminal
Onshore State Abbreviation Ca
Onshore Postal Code 90810
Onshore City Name Carson
Onshore County Name Los Angeles
Designated Location Milepost/valve Station
Designated Name Carson Termin
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Tank, Including Attached Appurtenances
Crossing No
Pipe Facility Type Intrastate
Item Involved Tank/vessel
Tank Vessel Subtype Single Bottom System
Tank Type Atmospheric
Installation Year 1990
Material Involved Carbon Steel
Release Type Leak
Leak Type Crack
Wildlife Impact Ind No
Soil Contamination Yes
Long Term Assessment No
Remediation Ind No
Water Contam Ind No
Could Be Hca Yes
Commodity Reached Hca Yes
High Pop Ind Yes
High Pop Yes No Yes
Est Cost Oper Paid 0
Est Cost Gas Released 3
Est Cost Prop Damage 84000
Est Cost Emergency 2751
Est Cost Environmental 0
Est Cost Other 0
Prpty 86754
Accident Psig 2.85
Mop Psig 14.5
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind No
Cpm In Place Ind No
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details The tank is independent of the scada system, not controlled by the field control room.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Equipment Failure
Cause Details Other Equipment Failure
Eq Failure Type Other Equipment Failure
Failure Details Recent Heavy Rains Caused Soil Compaction In This Area Allowing Added Stress On The Floor Plate Welds Causing A Crack, Approximately 1/8 In Diameter And 3-Ft Long.
Additional Support Ind Yes
Preparer Name S**** M*******
Preparer Title Mgr Ccs - Pacific
Preparer Email S*************@k***********.com
Preparer Telephone 909-873-5146
Preparer Fax 303-984-3620
Prepared Date 2018-12-26 00:00:00
Authorizer Name E***** A* F***
Authorizer Telephone 713-369-9454
Authorizer Title Director Ccs
Authorizer Email B********@k***********.com
Narrative A************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************@1237 and nrc #1232664 @ 1242 as the estimated property damage exceeded the $50,000 threshold. No further gasoline was released. This type of drain-dry tank allows flexing of the tank bottom at the drain dry sump location. Recent heavy rains caused soil compaction in this area allowing added stress on the floor plate welds causing a crack, approximately 1/8 in diameter and 3-ft long. Note: part a, #6 there were three nrc notifications made. The first (#1231759) notified of a threatened release, the second (#1232664) confirming the probability that the $50,000 reporting threshold would be exceeded and the third (#1232845) was the PHMSA-required 48 hour follow-up notification. ***********************************************************************************************************************.

All rights reserved. Copyright © by ClearPHMSA