HL incident on 2018-10-01 — TX

Operator
Rose Rock Midstream L.p.
Cause
Corrosion Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$36,103
Incident datetime
2018-10-01 06:00
Report number
Location
TX
Narrative
On the morning of 10/1/18 at approximately 6:00am, rose rock measurement tech arrived at the hudson station and noticed there was standing crude oil north of the mainline pd pumps. The measurement tech made notifications to his supervisor who then contacted the control center to shut down the station. The control center verified that the station had been down since 23:05 on 9/30/18. The measurement tech then closed the valve at tank 413 and locked out all the inbound truck lacts. Our repair contractor arrived and excavated and exposed the 12" suction line to the mainline pd pumps where the leak originated. On 10/1/18 a temporary clamp was installed to stop the leak and on 10/2/18 approximately 54" of pipe was cut out and replaced. Upon removal of the pipe it was determined that internal corrosion was the cause of the leak. The impacted soil was excavated and transported to an onsite land farm for treatment per kdhe approval.
Detailed record list
Report Received Date
2018-10-30 00:00:00
Iyear
2018
Report Number
20180332
Supplemental Number
31329
Report Type
Supplemental Final
Operator Id
Name
Rose Rock Midstream L.p.
Operator Street Address
1300 Main Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2018-10-01 06:00:00
Location Latitude
Location Longitude
Commodity Released Type
Crude Oil
Unintentional Release Bbls
2
Recovered Bbls
2
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2018-10-01 06:00:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Shutdown Due Accident Ind
No
Shutdown Explain
Pipeline Was Already Shut Down At The Time Of The Accident.
On Site Datetime
2018-10-01 06:00:00
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Hudson Station
Segment Name
Tank/station Piping
Onshore State Abbreviation
Ks
Onshore Postal Code
67545
Onshore City Name
Not Within A Municipality
Onshore County Name
Stafford
Designated Location
Milepost/valve Station
Designated Name
Within Statio
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
48
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Weld, Including Heat-Affected Zone
Pipe Diameter
12
Pipe Wall Thickness
0.375
Pipe Smys
42000
Pipe Specification
Api 5l
Pipe Seam Type
Seamless
Pipe Manufacturer
Pangang Group Chendu Iron And Steel Co
Pipe Coating Type
Fusion Bonded Epoxy(Fbe)
Weld Subtype
Pipe Girth Weld
Installation Year
2012
Manufactured Year
2004
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Other
Leak Type Other
Internal Corros. Leak In Weld
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
Yes
Soil Remed Ind
Yes
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
140
Est Cost Prop Damage
36103
Est Cost Emergency
1000
Est Cost Environmental
6447
Est Cost Other
0
Prpty
43690
Accident Psig
3
Mop Psig
285
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
< 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Corrosion leak
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
Internal Corrosion
Internal External
Internal Corrosion
Int Visual Exam Results
Localized Pitting
Int Microbiological Ind
Yes
Int Field Exam Basis Ind
Yes
Int Low Point Pipe Loc Ind
Yes
Corrosion Inhibitors
Yes
Corrosion Lining
No
Cleaning Dewatering
Not Applicable - Not Mainline Pipe
Corrosion Coupons
Yes
Collected Data Ind
No
Has Hydrtst Conduc Before Ind
No
Direct Asmnt Conducted
No
Non Destructive Exam Ind
No
Preparer Name
D**** Y****
Preparer Title
District Manager
Preparer Email
D******@s***********.com
Preparer Telephone
620-268-6004
Prepared Date
2018-12-14 00:00:00
Authorizer Name
L*** V******
Authorizer Telephone
918-524-8109
Authorizer Title
Dot Compliance Manager
Authorizer Email
L*******@s***********.com
Narrative
On the morning of 10/1/18 at approximately 6:00am, rose rock measurement tech arrived at the hudson station and noticed there was standing crude oil north of the mainline pd pumps. The measurement tech made notifications to his supervisor who then contacted the control center to shut down the station. The control center verified that the station had been down since 23:05 on 9/30/18. The measurement tech then closed the valve at tank 413 and locked out all the inbound truck lacts. Our repair contractor arrived and excavated and exposed the 12" suction line to the mainline pd pumps where the leak originated. On 10/1/18 a temporary clamp was installed to stop the leak and on 10/2/18 approximately 54" of pipe was cut out and replaced. Upon removal of the pipe it was determined that internal corrosion was the cause of the leak. The impacted soil was excavated and transported to an onsite land farm for treatment per kdhe approval.
Report Received Date 2018-10-30 00:00:00
Iyear 2018
Report Number 20180332
Supplemental Number 31329
Report Type Supplemental Final
Operator Id 31476 PHMSA Enforcement
Name Rose Rock Midstream L.p.
Operator Street Address 1300 Main Street
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Local Datetime 2018-10-01 06:00:00
Location Latitude 38.09369 Google Maps OpenStreetMap
Location Longitude -98.581894 Google Maps OpenStreetMap
Commodity Released Type Crude Oil
Unintentional Release Bbls 2
Recovered Bbls 2
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
Incident Identified Datetime 2018-10-01 06:00:00
System Part Involved Onshore Pump/meter Station Equipment And Piping
On Off Shore Onshore
Shutdown Due Accident Ind No
Shutdown Explain Pipeline Was Already Shut Down At The Time Of The Accident.
On Site Datetime 2018-10-01 06:00:00
Nrc Rpt Num Nrc Notification Not Required NRC Report How to search
Ignite Ind No
Explode Ind No
Num Pub Evacuated 0
Pipe Fac Name Hudson Station
Segment Name Tank/station Piping
Onshore State Abbreviation Ks
Onshore Postal Code 67545
Onshore City Name Not Within A Municipality
Onshore County Name Stafford
Designated Location Milepost/valve Station
Designated Name Within Statio
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Underground
Incident Area Subtype Under Soil
Depth Of Cover 48
Crossing No
Pipe Facility Type Interstate
Item Involved Weld, Including Heat-Affected Zone
Pipe Diameter 12
Pipe Wall Thickness 0.375
Pipe Smys 42000
Pipe Specification Api 5l
Pipe Seam Type Seamless
Pipe Manufacturer Pangang Group Chendu Iron And Steel Co
Pipe Coating Type Fusion Bonded Epoxy(Fbe)
Weld Subtype Pipe Girth Weld
Installation Year 2012
Manufactured Year 2004
Material Involved Carbon Steel
Release Type Leak
Leak Type Other
Leak Type Other Internal Corros. Leak In Weld
Wildlife Impact Ind No
Soil Contamination Yes
Long Term Assessment No
Remediation Ind Yes
Soil Remed Ind Yes
Water Contam Ind No
Could Be Hca No
Commodity Reached Hca No
Est Cost Oper Paid 0
Est Cost Gas Released 140
Est Cost Prop Damage 36103
Est Cost Emergency 1000
Est Cost Environmental 6447
Est Cost Other 0
Prpty 43690
Accident Psig 3
Mop Psig 285
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function < 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Cpm In Place Ind Yes
Cpm Operating Ind Yes
Cpm Functional Ind Yes
Cpm Detection Ind No
Cpm Conf Ind No
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details Corrosion leak
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Corrosion Failure
Cause Details Internal Corrosion
Internal External Internal Corrosion
Int Visual Exam Results Localized Pitting
Int Microbiological Ind Yes
Int Field Exam Basis Ind Yes
Int Low Point Pipe Loc Ind Yes
Corrosion Inhibitors Yes
Corrosion Lining No
Cleaning Dewatering Not Applicable - Not Mainline Pipe
Corrosion Coupons Yes
Collected Data Ind No
Has Hydrtst Conduc Before Ind No
Direct Asmnt Conducted No
Non Destructive Exam Ind No
Preparer Name D**** Y****
Preparer Title District Manager
Preparer Email D******@s***********.com
Preparer Telephone 620-268-6004
Prepared Date 2018-12-14 00:00:00
Authorizer Name L*** V******
Authorizer Telephone 918-524-8109
Authorizer Title Dot Compliance Manager
Authorizer Email L*******@s***********.com
Narrative On the morning of 10/1/18 at approximately 6:00am, rose rock measurement tech arrived at the hudson station and noticed there was standing crude oil north of the mainline pd pumps. The measurement tech made notifications to his supervisor who then contacted the control center to shut down the station. The control center verified that the station had been down since 23:05 on 9/30/18. The measurement tech then closed the valve at tank 413 and locked out all the inbound truck lacts. Our repair contractor arrived and excavated and exposed the 12" suction line to the mainline pd pumps where the leak originated. On 10/1/18 a temporary clamp was installed to stop the leak and on 10/2/18 approximately 54" of pipe was cut out and replaced. Upon removal of the pipe it was determined that internal corrosion was the cause of the leak. The impacted soil was excavated and transported to an onsite land farm for treatment per kdhe approval.