Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2018-07-25 — OK
Operator
Oneok Ngl Pipeline, Llc
Cause
Incorrect Operation
Commodity
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$250
Incident datetime
2018-07-25 15:30
Report number
Location
OK
Narrative
On 7/25/2018 oneok personnel changed seals on a pump at oneok's fairfield pump station. Upon completion of changing the seals personnel began to purge the pump cavity to return the pump to service. Purging began through a small ball valve on top of the pump without removing the temporary umbrella shade that had been installed to keep the sun off of the workers while changing the seal. As the purge began the vapors collected under the umbrella and it is believed static electricity ignited the vapors causing a flash fire. The fire immediately extinguished itself and the purge valve was closed. After a safety stand down, the remains of the umbrella were removed and the pump purge was completed. Oneok conducted a cause map investigation into the incident and determined procedures did not cover the use of an umbrella for shade during pump seal changes. In the future when an umbrella is used the umbrella support will be grounded and the umbrella will be removed prior to purging the pump.
Detailed record list
Report Received Date
2018-08-24 00:00:00
Iyear
2018
Report Number
20180256
Supplemental Number
30859
Report Type
Original Final
Operator Id
32109
Name
Oneok Ngl Pipeline, Llc
Operator Street Address
100 West Fifth Street
Operator City Name
Tulsa
Operator State Abbreviation
OK
Operator Postal Code
74103
Local Datetime
2018-07-25 15:30:00
Location Latitude
31.709201
Location Longitude
-96.227467
Commodity Released Type
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype
Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid)
Unintentional Release Bbls
0.02
Intentional Release Bbls
0
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2018-07-25 15:30:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Shutdown Due Accident Ind
No
Shutdown Explain
Pump Was Isolated From Pipeline, Pipeline Continued To Operate.
On Site Datetime
2018-07-25 15:30:00
Nrc Rpt Datetime
2018-07-25 15:42:00
Nrc Rpt Num
1219494
Ignite Ind
Yes
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Oneok Fairfield Pump Station (Site 541)
Segment Name
Oneok Arbuckle Pipeline Index # 10484
Onshore State Abbreviation
Tx
Onshore Postal Code
75840
Onshore City Name
Not Within A Municipality
Onshore County Name
Freestone
Designated Location
Milepost/valve Station
Designated Name
Pump Station
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Pump
Installation Year
2009
Material Involved
Carbon Steel
Release Type
Other
Release Type Details
Flash Fire Occurred While Purging Air From Pump Cavity After Seal Change And Burned Umbrella Shade. Fire Believed To Be Started By Static Electricity.
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
0
Est Cost Prop Damage
250
Est Cost Emergency
0
Est Cost Environmental
0
Est Cost Other
0
Prpty
250
Accident Psig
50
Mop Psig
1440
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Pump was under control of local operating personnel
Employee Drug Test Ind
Yes
Contractor Drug Test Ind
No
Num Employees Tested
2
Num Employees Failed
0
Cause
Incorrect Operation
Cause Details
Other Incorrect Operation
Operation Type
Other Incorrect Operation
Operation Details
Purging Pump Without Moving Shade Umbrella From Over The Purge Vent Which Prevented Hydrocarbon Vapors From Dissipating.
Related Inadequate Proc Ind
Yes
Category Type
Routine Maintenance
Operator Qualification Ind
Yes
Qualified Individuals
Yes, They Were Qualified For The Task(S)
Preparer Name
N*** J****
Preparer Title
Requlatory Compliance Manager
Preparer Email
N*********@o****.com
Preparer Telephone
580-395-6304
Preparer Fax
580-395-2933
Prepared Date
2018-08-24 00:00:00
Authorizer Name
N*** J****
Authorizer Telephone
580-395-6304
Authorizer Title
Regulatory Compliance Manager
Authorizer Email
N*********@o****.com
Narrative
On 7/25/2018 oneok personnel changed seals on a pump at oneok's fairfield pump station. Upon completion of changing the seals personnel began to purge the pump cavity to return the pump to service. Purging began through a small ball valve on top of the pump without removing the temporary umbrella shade that had been installed to keep the sun off of the workers while changing the seal. As the purge began the vapors collected under the umbrella and it is believed static electricity ignited the vapors causing a flash fire. The fire immediately extinguished itself and the purge valve was closed. After a safety stand down, the remains of the umbrella were removed and the pump purge was completed. Oneok conducted a cause map investigation into the incident and determined procedures did not cover the use of an umbrella for shade during pump seal changes. In the future when an umbrella is used the umbrella support will be grounded and the umbrella will be removed prior to purging the pump.
| Report Received Date | 2018-08-24 00:00:00 |
|---|---|
| Iyear | 2018 |
| Report Number | 20180256 |
| Supplemental Number | 30859 |
| Report Type | Original Final |
| Operator Id | 32109 PHMSA Enforcement |
| Name | Oneok Ngl Pipeline, Llc |
| Operator Street Address | 100 West Fifth Street |
| Operator City Name | Tulsa |
| Operator State Abbreviation | OK |
| Operator Postal Code | 74103 |
| Local Datetime | 2018-07-25 15:30:00 |
| Location Latitude | 31.709201 Google Maps OpenStreetMap |
| Location Longitude | -96.227467 Google Maps OpenStreetMap |
| Commodity Released Type | Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions |
| Commodity Subtype | Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid) |
| Unintentional Release Bbls | 0.02 |
| Intentional Release Bbls | 0 |
| Recovered Bbls | 0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Operator Employee |
| Incident Identified Datetime | 2018-07-25 15:30:00 |
| System Part Involved | Onshore Pump/meter Station Equipment And Piping |
| On Off Shore | Onshore |
| Shutdown Due Accident Ind | No |
| Shutdown Explain | Pump Was Isolated From Pipeline, Pipeline Continued To Operate. |
| On Site Datetime | 2018-07-25 15:30:00 |
| Nrc Rpt Datetime | 2018-07-25 15:42:00 |
| Nrc Rpt Num | 1219494 NRC Report How to search |
| Ignite Ind | Yes |
| Explode Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Oneok Fairfield Pump Station (Site 541) |
| Segment Name | Oneok Arbuckle Pipeline Index # 10484 |
| Onshore State Abbreviation | Tx |
| Onshore Postal Code | 75840 |
| Onshore City Name | Not Within A Municipality |
| Onshore County Name | Freestone |
| Designated Location | Milepost/valve Station |
| Designated Name | Pump Station |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
| Crossing | No |
| Pipe Facility Type | Interstate |
| Item Involved | Pump |
| Installation Year | 2009 |
| Material Involved | Carbon Steel |
| Release Type | Other |
| Release Type Details | Flash Fire Occurred While Purging Air From Pump Cavity After Seal Change And Burned Umbrella Shade. Fire Believed To Be Started By Static Electricity. |
| Wildlife Impact Ind | No |
| Soil Contamination | No |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | No |
| Commodity Reached Hca | No |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 0 |
| Est Cost Prop Damage | 250 |
| Est Cost Emergency | 0 |
| Est Cost Environmental | 0 |
| Est Cost Other | 0 |
| Prpty | 250 |
| Accident Psig | 50 |
| Mop Psig | 1440 |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Cpm In Place Ind | Yes |
| Cpm Operating Ind | Yes |
| Cpm Functional Ind | Yes |
| Cpm Detection Ind | No |
| Cpm Conf Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | Pump was under control of local operating personnel |
| Employee Drug Test Ind | Yes |
| Contractor Drug Test Ind | No |
| Num Employees Tested | 2 |
| Num Employees Failed | 0 |
| Cause | Incorrect Operation |
| Cause Details | Other Incorrect Operation |
| Operation Type | Other Incorrect Operation |
| Operation Details | Purging Pump Without Moving Shade Umbrella From Over The Purge Vent Which Prevented Hydrocarbon Vapors From Dissipating. |
| Related Inadequate Proc Ind | Yes |
| Category Type | Routine Maintenance |
| Operator Qualification Ind | Yes |
| Qualified Individuals | Yes, They Were Qualified For The Task(S) |
| Preparer Name | N*** J**** |
| Preparer Title | Requlatory Compliance Manager |
| Preparer Email | N*********@o****.com |
| Preparer Telephone | 580-395-6304 |
| Preparer Fax | 580-395-2933 |
| Prepared Date | 2018-08-24 00:00:00 |
| Authorizer Name | N*** J**** |
| Authorizer Telephone | 580-395-6304 |
| Authorizer Title | Regulatory Compliance Manager |
| Authorizer Email | N*********@o****.com |
| Narrative | On 7/25/2018 oneok personnel changed seals on a pump at oneok's fairfield pump station. Upon completion of changing the seals personnel began to purge the pump cavity to return the pump to service. Purging began through a small ball valve on top of the pump without removing the temporary umbrella shade that had been installed to keep the sun off of the workers while changing the seal. As the purge began the vapors collected under the umbrella and it is believed static electricity ignited the vapors causing a flash fire. The fire immediately extinguished itself and the purge valve was closed. After a safety stand down, the remains of the umbrella were removed and the pump purge was completed. Oneok conducted a cause map investigation into the incident and determined procedures did not cover the use of an umbrella for shade during pump seal changes. In the future when an umbrella is used the umbrella support will be grounded and the umbrella will be removed prior to purging the pump. |