Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2018-06-07 — OK
Operator
Magellan Pipeline Company, Lp
Cause
Incorrect Operation
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$500
Incident datetime
2018-06-07 09:00
Report number
Location
OK
Narrative
During morning facility inspection, operator observed product on the concrete containment floor originating from the bottom of the flange in the transfer manifold area. The line was not running at the time. Clean up activities were commenced by using diapers and solvents. Further investigation identified a thermal psv on the line segment was isolated. Due to the psv being isolated, it is believed the line became pressurized due to thermal pressure and likely exceeded mop, resulting in the release at the flange. The flange gasket and bolts were replaced and the transfer manifold visually inspected. A safety meeting was conducted and duties of daily facility and equipment inspections were re-enforced along with a review of the psv inspection procedure
Detailed record list
Report Received Date
2018-06-29 00:00:00
Iyear
2018
Report Number
20180187
Supplemental Number
30575
Report Type
Original Final
Operator Id
22610
Name
Magellan Pipeline Company, Lp
Operator Street Address
100 West 5th Street
Operator City Name
Tulsa
Operator State Abbreviation
OK
Operator Postal Code
74103
Local Datetime
2018-06-07 09:00:00
Location Latitude
40.200501
Location Longitude
-104.608058
Commodity Released Type
Crude Oil
Unintentional Release Bbls
0.36
Recovered Bbls
0.36
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2018-06-07 09:00:00
System Part Involved
Onshore Terminal/tank Farm Equipment And Piping
On Off Shore
Onshore
Shutdown Due Accident Ind
No
Shutdown Explain
Affected Section Of Piping Was Idle At The Time
On Site Datetime
2018-06-07 09:00:00
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Platteville
Segment Name
Sta. No. 880
Onshore State Abbreviation
Co
Onshore Postal Code
80642
Onshore City Name
Not Within A Municipality
Onshore County Name
Weld
Designated Location
Milepost/valve Station
Designated Name
0
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Flange Assembly
Installation Year
2016
Material Involved
Material Other Than Carbon Steel
Material Details
Gasket
Release Type
Leak
Leak Type
Connection Failure
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
25
Est Cost Prop Damage
500
Est Cost Emergency
0
Est Cost Environmental
0
Est Cost Other
0
Prpty
525
Accident Psig
303
Mop Psig
275
Accident Pressure
Pressure Exceeded 110% Of Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Scada/cpm does not monitor facility piping for transfers between tanks.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Incorrect Operation
Cause Details
Pipeline Or Equipment Overpressured
Operation Type
Pipeline Or Equipment Overpressured
Related Failure Follow Ind
Yes
Category Type
Routine Maintenance
Operator Qualification Ind
Yes
Qualified Individuals
Yes, They Were Qualified For The Task(S)
Preparer Name
S****** L******
Preparer Title
Ai Analyst
Preparer Email
S**************@m*********.com
Preparer Telephone
918-574-7327
Preparer Fax
918574-7636
Prepared Date
2018-06-29 00:00:00
Authorizer Name
M*** M******
Authorizer Telephone
918-574-7073
Authorizer Title
Mgr Integrity Mgmt And Regulatory Comp
Authorizer Email
Mark Materna
Narrative
During morning facility inspection, operator observed product on the concrete containment floor originating from the bottom of the flange in the transfer manifold area. The line was not running at the time. Clean up activities were commenced by using diapers and solvents. Further investigation identified a thermal psv on the line segment was isolated. Due to the psv being isolated, it is believed the line became pressurized due to thermal pressure and likely exceeded mop, resulting in the release at the flange. The flange gasket and bolts were replaced and the transfer manifold visually inspected. A safety meeting was conducted and duties of daily facility and equipment inspections were re-enforced along with a review of the psv inspection procedure
| Report Received Date | 2018-06-29 00:00:00 |
|---|---|
| Iyear | 2018 |
| Report Number | 20180187 |
| Supplemental Number | 30575 |
| Report Type | Original Final |
| Operator Id | 22610 PHMSA Enforcement |
| Name | Magellan Pipeline Company, Lp |
| Operator Street Address | 100 West 5th Street |
| Operator City Name | Tulsa |
| Operator State Abbreviation | OK |
| Operator Postal Code | 74103 |
| Local Datetime | 2018-06-07 09:00:00 |
| Location Latitude | 40.200501 Google Maps OpenStreetMap |
| Location Longitude | -104.608058 Google Maps OpenStreetMap |
| Commodity Released Type | Crude Oil |
| Unintentional Release Bbls | 0.36 |
| Recovered Bbls | 0.36 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Operator Employee |
| Incident Identified Datetime | 2018-06-07 09:00:00 |
| System Part Involved | Onshore Terminal/tank Farm Equipment And Piping |
| On Off Shore | Onshore |
| Shutdown Due Accident Ind | No |
| Shutdown Explain | Affected Section Of Piping Was Idle At The Time |
| On Site Datetime | 2018-06-07 09:00:00 |
| Nrc Rpt Num | Nrc Notification Not Required NRC Report How to search |
| Ignite Ind | No |
| Explode Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Platteville |
| Segment Name | Sta. No. 880 |
| Onshore State Abbreviation | Co |
| Onshore Postal Code | 80642 |
| Onshore City Name | Not Within A Municipality |
| Onshore County Name | Weld |
| Designated Location | Milepost/valve Station |
| Designated Name | 0 |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
| Crossing | No |
| Pipe Facility Type | Interstate |
| Item Involved | Flange Assembly |
| Installation Year | 2016 |
| Material Involved | Material Other Than Carbon Steel |
| Material Details | Gasket |
| Release Type | Leak |
| Leak Type | Connection Failure |
| Wildlife Impact Ind | No |
| Soil Contamination | No |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | No |
| Commodity Reached Hca | No |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 25 |
| Est Cost Prop Damage | 500 |
| Est Cost Emergency | 0 |
| Est Cost Environmental | 0 |
| Est Cost Other | 0 |
| Prpty | 525 |
| Accident Psig | 303 |
| Mop Psig | 275 |
| Accident Pressure | Pressure Exceeded 110% Of Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Cpm In Place Ind | Yes |
| Cpm Operating Ind | Yes |
| Cpm Functional Ind | Yes |
| Cpm Detection Ind | No |
| Cpm Conf Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | Scada/cpm does not monitor facility piping for transfers between tanks. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Incorrect Operation |
| Cause Details | Pipeline Or Equipment Overpressured |
| Operation Type | Pipeline Or Equipment Overpressured |
| Related Failure Follow Ind | Yes |
| Category Type | Routine Maintenance |
| Operator Qualification Ind | Yes |
| Qualified Individuals | Yes, They Were Qualified For The Task(S) |
| Preparer Name | S****** L****** |
| Preparer Title | Ai Analyst |
| Preparer Email | S**************@m*********.com |
| Preparer Telephone | 918-574-7327 |
| Preparer Fax | 918574-7636 |
| Prepared Date | 2018-06-29 00:00:00 |
| Authorizer Name | M*** M****** |
| Authorizer Telephone | 918-574-7073 |
| Authorizer Title | Mgr Integrity Mgmt And Regulatory Comp |
| Authorizer Email | Mark Materna |
| Narrative | During morning facility inspection, operator observed product on the concrete containment floor originating from the bottom of the flange in the transfer manifold area. The line was not running at the time. Clean up activities were commenced by using diapers and solvents. Further investigation identified a thermal psv on the line segment was isolated. Due to the psv being isolated, it is believed the line became pressurized due to thermal pressure and likely exceeded mop, resulting in the release at the flange. The flange gasket and bolts were replaced and the transfer manifold visually inspected. A safety meeting was conducted and duties of daily facility and equipment inspections were re-enforced along with a review of the psv inspection procedure |