GTG incident on 2018-11-16 — TX

Operator
Columbia Gas Transmission, Llc
Cause
Equipment Failure
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$525,715
Incident datetime
2018-11-16 02:16
Report number
Location
TX
Narrative
All times recorded were in eastern standard time on 11/15/18 at 23:54, transcanada's gas control (gc) center (columbia gas transmission opid 2616) was notified by west virginia wyoming county 911 of a gas release and fire at cairo hollow in the town of bud, wv. Company personnel was dispatched by local operations at that time. At 00:36 on 11/16/18, gc received a low-pressure alarm of 0 at measuring station (ms) 804927 corrine delivery point (dp) at the end of line ka-14. Company personnel arrived onsite at 01:45 on 11/16/2018 and confirmed a fire at corrine regulator station (rs) 807629 located at pipelines ka to ka-14. Company personnel closed the valve to pipeline ka-14 at 02:45 on 11/16/2018 isolating rs-807629 and pipeline ka-14. Company personnel contacted mountaineer gas company (local distribution operator) to isolate the feed at ms-804927 corrine dp to prevent backfeed into pipeline ka-14. Preliminary investigation identified a failed 2" ansi-600 flanged connection that was missing part of the garlock gasket. The missing gasket aligns with heat maps of the facility to indicate the fire damage is sourced from this flange. Ignition source for the leak at the inlet flange to the regulation could be the in-direct fired heater onsite. Temporary service will be restored using a 2" skid mounted regulation skid and 2" connection to and from below ground piping to pipeline ka-14. Permanent installation of facility will commence in 2019 with expected in service of march 29, 2019. The initial nrc report no. 1230533 reported on november 16, 2016 @ 02:32 and the 48-hr update nrc report no. 1230594 was reported on november 16, 2018 @ 14:23. An apparent gasket failure occurred in top works of the pressure regulator at corrine regulator station (rs) 807629. Repairs were completed on june 10, 2019.
Detailed record list
Report Received Date
2018-12-14 00:00:00
Iyear
2018
Report Number
20180130
Supplemental Number
32377
Report Type
Supplemental Final
Operator Id
Name
Columbia Gas Transmission, Llc
Operator Street Address
700 Louisiana St. Suite 700
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2018-11-16 02:16:00
Location Latitude
Location Longitude
Nrc Rpt Num
Nrc Rpt Datetime
2018-11-16 02:32:00
Commodity Released Type
Natural Gas
Unintentional Release
3920
Intentional Release
3.64
Accompanying Liquid
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2018-11-16 02:45:00
Restart Datetime
2019-06-10 09:00:00
Ignite Ind
Yes
Explode Ind
No
Num Pub Evacuated
0
Incident Identified Datetime
2018-11-16 02:16:00
On Site Datetime
2018-11-16 01:45:00
On Off Shore
Onshore
Onshore State Abbreviation
Wv
Onshore Postal Code
25826
Onshore City Name
Corrine
Onshore County Name
Wyoming
Designated Location
Survey Station No.
Designated Name
Rs-807629
Pipe Fac Name
Line Ka To Ka-14
Segment Name
Line Ka-14
Federal
No
Location Type
Pipeline Right-Of-Way
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
System Part Involved
Onshore Regulator/metering Station Equipment And Piping
Item Involved
Flange Assembly
Installation Year
1999
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Connection Failure
Class Location Type
Class 1 Location
Could Be Hca
No
Pir Radius
49
Heat Damage Ind
No
Non Heat Damage Ind
No
Hca Fatalities Ind
No
Est Cost Oper Paid
0
Est Cost Unintentional Release
11564
Est Cost Intentional Release
11
Est Cost Prop Damage
525715
Est Cost Emergency
2200
Est Cost Other
0
Est Cost Other Details
Temporary Repairs, Equipment Will Be Removed When Permanent Repairs Are Complete
Prpty
539490
Accident Psig
560
Mop Psig
1000
Mop Cfr Section
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Pipeline Function
Transmission System
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Accident Identifier
Notification From Emergency Responder
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
The controller was notified operating personnel about the pressure alarm and made operations aware there was a call already from wyoming 911.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Non-Threaded Connection Failure
Eq Failure Type
Non-Threaded Connection Failure
Other Non Threaded Ind
Gasket
Eq Additional Other Ind
Yes
Eq Additional Other Details
Age And Conditions Of Soft Goods
Preparer Name
M*** N*****
Preparer Title
Compliance Specialist Us Regulatory Compliance
Preparer Email
M**********@t**********.com
Preparer Telephone
304-722-8475
Preparer Fax
304-722-8420
Authorizer Name
G***** H*****
Authorizer Title
Manager East Us Regulatory Compliance
Authorizer Telephone
304-357-3728
Authorizer Email
G************@t**********.com
Narrative
A**********************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************@ 02:32 and the 48-hr update nrc report no. 1230594 was reported on november 16, 2018 @ 14:23. An apparent gasket failure occurred in top works of the pressure regulator at corrine regulator station (rs) 807629. ***************************************.
Report Received Date 2018-12-14 00:00:00
Iyear 2018
Report Number 20180130
Supplemental Number 32377
Report Type Supplemental Final
Operator Id 2616 PHMSA Enforcement
Name Columbia Gas Transmission, Llc
Operator Street Address 700 Louisiana St. Suite 700
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Local Datetime 2018-11-16 02:16:00
Location Latitude 37.55587 Google Maps OpenStreetMap
Location Longitude -81.36975 Google Maps OpenStreetMap
Nrc Rpt Num 1230533 NRC Report How to search
Nrc Rpt Datetime 2018-11-16 02:32:00
Commodity Released Type Natural Gas
Unintentional Release 3920
Intentional Release 3.64
Accompanying Liquid 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Shutdown Due Accident Ind Yes
Shutdown Datetime 2018-11-16 02:45:00
Restart Datetime 2019-06-10 09:00:00
Ignite Ind Yes
Explode Ind No
Num Pub Evacuated 0
Incident Identified Datetime 2018-11-16 02:16:00
On Site Datetime 2018-11-16 01:45:00
On Off Shore Onshore
Onshore State Abbreviation Wv
Onshore Postal Code 25826
Onshore City Name Corrine
Onshore County Name Wyoming
Designated Location Survey Station No.
Designated Name Rs-807629
Pipe Fac Name Line Ka To Ka-14
Segment Name Line Ka-14
Federal No
Location Type Pipeline Right-Of-Way
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Interstate
System Part Involved Onshore Regulator/metering Station Equipment And Piping
Item Involved Flange Assembly
Installation Year 1999
Material Involved Carbon Steel
Release Type Leak
Leak Type Connection Failure
Class Location Type Class 1 Location
Could Be Hca No
Pir Radius 49
Heat Damage Ind No
Non Heat Damage Ind No
Hca Fatalities Ind No
Est Cost Oper Paid 0
Est Cost Unintentional Release 11564
Est Cost Intentional Release 11
Est Cost Prop Damage 525715
Est Cost Emergency 2200
Est Cost Other 0
Est Cost Other Details Temporary Repairs, Equipment Will Be Removed When Permanent Repairs Are Complete
Prpty 539490
Accident Psig 560
Mop Psig 1000
Mop Cfr Section 192.619(C) View CFR 49 §192
Accident Pressure Pressure Did Not Exceed Maop
Pressure Restriction Ind No
Pipeline Function Transmission System
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind Yes
Scada Conf Ind Yes
Accident Identifier Notification From Emergency Responder
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details The controller was notified operating personnel about the pressure alarm and made operations aware there was a call already from wyoming 911.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Equipment Failure
Cause Details Non-Threaded Connection Failure
Eq Failure Type Non-Threaded Connection Failure
Other Non Threaded Ind Gasket
Eq Additional Other Ind Yes
Eq Additional Other Details Age And Conditions Of Soft Goods
Preparer Name M*** N*****
Preparer Title Compliance Specialist Us Regulatory Compliance
Preparer Email M**********@t**********.com
Preparer Telephone 304-722-8475
Preparer Fax 304-722-8420
Authorizer Name G***** H*****
Authorizer Title Manager East Us Regulatory Compliance
Authorizer Telephone 304-357-3728
Authorizer Email G************@t**********.com
Narrative A**********************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************@ 02:32 and the 48-hr update nrc report no. 1230594 was reported on november 16, 2018 @ 14:23. An apparent gasket failure occurred in top works of the pressure regulator at corrine regulator station (rs) 807629. ***************************************.

All rights reserved. Copyright © by ClearPHMSA