Incident details
Operator, cause, commodity and consequences with raw source fields.
GD incident on 2018-07-22 — CA
Operator
Pacific Gas & Electric Co
Cause
Equipment Failure
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$50,000
Incident datetime
2018-07-22 08:31
Report number
Location
CA, PLACER
Narrative
On july 22, 2018 at 0831 hours, pg&e was notified of a service line rupture at a parking lot at 9100 foothills blvd in roseville. The actual service line that ruptured was 8000 foothills blvd. Pg&e's gas service representative arrived on-site at 0853 hours. Pg&e's crew stopped the flow of gas by shutting in the station at 1033 hours. The area was uncovered and determined that the 4" plastic service had ruptured from a potential maop exceedance. There was no pressure monitoring/recording on this line, therefore the exact pressure reached at the time of the rupture is unknown. The cause of the overpressure event was a malfunction of the control equipment. One customer's gas service was impacted. The customer's gas service was restored using compressed natural gas (cng) portable tanks on 7/23/18 at 0700 hours. The ruptured service pipe is planned to be deactivated, and a new service is to be installed from an existing distribution main. Construction is pending. There were no injuries, fatalities or ignition associated with this incident. Fire department was reported on-site. This incident was reported to the cpuc due to a maop exceedance event, which was determined on 7/22/18 at 1748 hours. On 7/24/18 at 1120 hours, it was determined that repair costs would exceed $50k. On 7/24/18 at 1134 hours, this incident was reported to the DOT due to the $50k criteria. Gas equipment affected
Detailed record list
Occurred At
2018-07-22 08:31:00
Year
2018
Report Received Date
2018-08-22 00:00:00
Iyear
2018.0
Report Number
20180077.0
Supplemental Number
31458.0
Report Type
Supplemental Final
Operator Id
15007
Name
Pacific Gas & Electric Co
Operator Street Address
6121 Bollinger Canyon Rd.
Operator City Name
San Ramon
Operator State Abbreviation
CA
Operator Postal Code
94583
Local Datetime
2018-07-22 08:31:00
Location Street Address
8000 Foothills Blvd
Location City Name
Roseville
Location County Name
Placer
Location State Abbreviation
CA
Location Postal Code
95747
Location Latitude
38.785644
Location Longitude
-121.318716
Nrc Rpt Datetime
2018-07-24 11:34:00
Nrc Rpt Num
1219376
Commodity Released Type
Natural Gas
Unintentional Release
837.0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0.0
Incident Identified Datetime
2018-07-22 08:31:00
On Site Datetime
2018-07-22 08:53:00
Federal
No
Location Type
Private Property
Incident Area Type
Underground
Incident Area Subtype
Under Pavement
Depth Of Cover
36.0
Crossing
No
Pipe Facility Type
Investor Owned
System Part Involved
Service
Installation Year
1998.0
Pipe Diameter
4.0
Pipe Specification
Astm D2513
Pipe Manufacturer
Uponor
Material Involved
Plastic
Plastic Type
Polyethylene (Pe)
Plastic Sdr
13.5
Material Pe Pipe Code
2406
Release Type
Rupture
Rupture Orient
Longitudinal
Rupture Length
4
Rupture Width
12
Class Location Type
Class 3 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
50000.0
Est Cost Emergency
0.0
Est Cost Other
0.0
Est Cost Other Details
Costs For This Event Are Still Being Evaluated, But Are Estimated To Be >$50k
Est Cost Unintentional Release
2500.0
Prpty
52500.0
Commercial Affected
1.0
Industrial Affected
0.0
Residences Affected
0.0
Accident Psig
480.0
Normal Psig
45.0
Mop Psig
60.0
Accident Pressure
Pressure Exceeded The Applicable Allowance In 192.201
Scada In Place Ind
No
Accident Identifier
Notification From Public
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Malfunction Of Control/relief Equipment
Eq Failure Type
Malfunction Of Control/relief Equipment
Pressure Regulator Ind
Yes
Preparer Name
E*** B******
Preparer Title
Regulatory Compliance
Preparer Email
E***@p**.com
Preparer Telephone
925-357-7889
Authorizer Name
S**** R*******
Authorizer Title
Regulatory Compliance Manager
Authorizer Telephone
925-328-5776
Authorizer Email
G***@p**.com
Narrative
On july 22, 2018 at 0831 hours, pg&e was notified of a service line rupture at a parking lot at 9100 foothills blvd in roseville. The actual service line that ruptured was 8000 foothills blvd. Pg&e's gas service representative arrived on-site at 0853 hours. Pg&e's crew stopped the flow of gas by shutting in the station at 1033 hours. The area was uncovered and determined that the 4" plastic service had ruptured from a potential maop exceedance. There was no pressure monitoring/recording on this line, therefore the exact pressure reached at the time of the rupture is unknown. The cause of the overpressure event was a malfunction of the control equipment. One customer's gas service was impacted. The customer's gas service was restored using compressed natural gas (cng) portable tanks on 7/23/18 at 0700 hours. The ruptured service pipe is planned to be deactivated, and a new service is to be installed from an existing distribution main. Construction is pending. There were no injuries, fatalities or ignition associated with this incident. Fire department was reported on-site. This incident was reported to the cpuc due to a maop exceedance event, which was determined on 7/22/18 at 1748 hours. On 7/24/18 at 1120 hours, it was determined that repair costs would exceed $50k. On 7/24/18 at 1134 hours, this incident was reported to the DOT due to the $50k criteria. Gas equipment affected
| Occurred At | 2018-07-22 08:31:00 |
|---|---|
| Year | 2018 |
| Report Received Date | 2018-08-22 00:00:00 |
| Iyear | 2018.0 |
| Report Number | 20180077.0 |
| Supplemental Number | 31458.0 |
| Report Type | Supplemental Final |
| Operator Id | 15007 PHMSA Enforcement |
| Name | Pacific Gas & Electric Co |
| Operator Street Address | 6121 Bollinger Canyon Rd. |
| Operator City Name | San Ramon |
| Operator State Abbreviation | CA |
| Operator Postal Code | 94583 |
| Local Datetime | 2018-07-22 08:31:00 |
| Location Street Address | 8000 Foothills Blvd |
| Location City Name | Roseville |
| Location County Name | Placer |
| Location State Abbreviation | CA |
| Location Postal Code | 95747 |
| Location Latitude | 38.785644 Google Maps OpenStreetMap |
| Location Longitude | -121.318716 Google Maps OpenStreetMap |
| Nrc Rpt Datetime | 2018-07-24 11:34:00 |
| Nrc Rpt Num | 1219376 NRC Report How to search |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 837.0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Ignite Ind | No |
| Explode Ind | No |
| Num Pub Evacuated | 0.0 |
| Incident Identified Datetime | 2018-07-22 08:31:00 |
| On Site Datetime | 2018-07-22 08:53:00 |
| Federal | No |
| Location Type | Private Property |
| Incident Area Type | Underground |
| Incident Area Subtype | Under Pavement |
| Depth Of Cover | 36.0 |
| Crossing | No |
| Pipe Facility Type | Investor Owned |
| System Part Involved | Service |
| Installation Year | 1998.0 |
| Pipe Diameter | 4.0 |
| Pipe Specification | Astm D2513 |
| Pipe Manufacturer | Uponor |
| Material Involved | Plastic |
| Plastic Type | Polyethylene (Pe) |
| Plastic Sdr | 13.5 |
| Material Pe Pipe Code | 2406 |
| Release Type | Rupture |
| Rupture Orient | Longitudinal |
| Rupture Length | 4 |
| Rupture Width | 12 |
| Class Location Type | Class 3 Location |
| Est Cost Oper Paid | 0.0 |
| Est Cost Prop Damage | 50000.0 |
| Est Cost Emergency | 0.0 |
| Est Cost Other | 0.0 |
| Est Cost Other Details | Costs For This Event Are Still Being Evaluated, But Are Estimated To Be >$50k |
| Est Cost Unintentional Release | 2500.0 |
| Prpty | 52500.0 |
| Commercial Affected | 1.0 |
| Industrial Affected | 0.0 |
| Residences Affected | 0.0 |
| Accident Psig | 480.0 |
| Normal Psig | 45.0 |
| Mop Psig | 60.0 |
| Accident Pressure | Pressure Exceeded The Applicable Allowance In 192.201 |
| Scada In Place Ind | No |
| Accident Identifier | Notification From Public |
| Investigation Status | No, the facility was not monitored by a controller(s) at the time of the incident |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Equipment Failure |
| Cause Details | Malfunction Of Control/relief Equipment |
| Eq Failure Type | Malfunction Of Control/relief Equipment |
| Pressure Regulator Ind | Yes |
| Preparer Name | E*** B****** |
| Preparer Title | Regulatory Compliance |
| Preparer Email | E***@p**.com |
| Preparer Telephone | 925-357-7889 |
| Authorizer Name | S**** R******* |
| Authorizer Title | Regulatory Compliance Manager |
| Authorizer Telephone | 925-328-5776 |
| Authorizer Email | G***@p**.com |
| Narrative | On july 22, 2018 at 0831 hours, pg&e was notified of a service line rupture at a parking lot at 9100 foothills blvd in roseville. The actual service line that ruptured was 8000 foothills blvd. Pg&e's gas service representative arrived on-site at 0853 hours. Pg&e's crew stopped the flow of gas by shutting in the station at 1033 hours. The area was uncovered and determined that the 4" plastic service had ruptured from a potential maop exceedance. There was no pressure monitoring/recording on this line, therefore the exact pressure reached at the time of the rupture is unknown. The cause of the overpressure event was a malfunction of the control equipment. One customer's gas service was impacted. The customer's gas service was restored using compressed natural gas (cng) portable tanks on 7/23/18 at 0700 hours. The ruptured service pipe is planned to be deactivated, and a new service is to be installed from an existing distribution main. Construction is pending. There were no injuries, fatalities or ignition associated with this incident. Fire department was reported on-site. This incident was reported to the cpuc due to a maop exceedance event, which was determined on 7/22/18 at 1748 hours. On 7/24/18 at 1120 hours, it was determined that repair costs would exceed $50k. On 7/24/18 at 1134 hours, this incident was reported to the DOT due to the $50k criteria. Gas equipment affected |