GD incident on 2018-04-17 — KY

Operator
Louisville Gas & Electric Co
Cause
Locating Issue
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$0
Incident datetime
2018-04-17 12:00
Report number
Location
KY, JEFFERSON COUNTY
Narrative
On april 17, 2018, lg&e was notified at 12:04am of third party damage to an 8" steel distribution main at the intersection of hurstbourne lane and taylorsville road (nw corner) in jefferson county, kentucky. The pipeline was damaged by an auger being used by that third party to prepare to pour a foundation for a utility pole (not an lg&e pole). A perimeter was established and gas safely vented until it was shut off at approximately 11:00 am on april 18, 2018. No injuries occurred and no customers lost service.
Detailed record list
Occurred At
2018-04-17 12:00:00
Year
2018
Report Received Date
2018-05-17 00:00:00
Iyear
2018.0
Report Number
20180056.0
Supplemental Number
35992.0
Report Type
Supplemental Final
Operator Id
Name
Louisville Gas & Electric Co
Operator Street Address
820 West Broadway, Po Box 32030
Operator City Name
Louisville
Operator State Abbreviation
KY
Operator Postal Code
40202
Local Datetime
2018-04-17 12:04:00
Time Zone
Eastern
Daylight Savings Ind
No
Location Street Address
Intersection Of Hurstbourne Lane And Taylorsville Road
Location City Name
Louisville
Location County Name
Jefferson County
Location State Abbreviation
KY
Location Postal Code
40214
Location Latitude
Location Longitude
Flow Cont Stopple Fitng Ind
Yes
Nrc Rpt Datetime
2018-04-19 14:39:00
Nrc Rpt Num
Commodity Released Type
Natural Gas
Unintentional Release
1940.0
Intentional Release
0.0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
No
Num Pub Evacuated
0.0
Incident Identified Datetime
2018-04-17 12:00:00
On Site Datetime
2018-04-17 13:06:00
Federal
No
Location Type
Utility Right-Of-Way / Easement
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
108.0
Other Underground Facilities
No
Crossing
No
Pipe Facility Type
Investor Owned
System Part Involved
Main
Installation Year
1962.0
Pipe Diameter
8.0
Pipe Specification
Unknown
Pipe Manufacturer
Unknown
Material Involved
Steel
Steel Seam Type
Other
Steel Seam Type Details
Unknown
Release Type
Mechanical Puncture
Puncture Axial
1.0
Puncture Circum
1.0
Class Location Type
Class 3 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
0.0
Est Cost Emergency
511394.0
Est Cost Other
0.0
Gas Cost In Mcf
3.8332
Est Cost Unintentional Release
7436.0
Est Cost Intentional Release
0.0
Prpty
518830.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
0.0
Num Persons Hosp Not Ovnght
0.0
Num Injured Treated By Emt
0.0
Num Resident Building Affctd
0.0
Num Business Building Affctd
0.0
Accident Psig
55.0
Normal Psig
55.0
Mop Psig
60.0
Mop Cfr Section
192.619(A)(2)
Maop Established Date
1962-09-18 00:00:00
Accident Pressure
Pressure Did Not Exceed Maop
Gas Odorized System Type
Injection Pump
Gas Odorized Lvl Not Msrd Ind
Yes
Scada In Place Ind
No
Accident Identifier
Notification From Emergency Responder
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
There was no control room or scada involvement with the incident or response.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Excavation Damage
Cause Details
Excavation Damage By Third Party
Ex Party Type
Excavation Damage By Third Party
Prior Notification Ind
Yes
One Call System Ind
Yes
State Law Exempt Ind
No
Notify Cga Dirt
No
Public Row Ind
Yes
Public Subtype
State Highway
Excavator Type
State
Excavator Equipment
Auger
Work Performed
Pole
One Call Notified Ind
Yes
One Call Ticket Num
1804171010
Locator Type
Contract Locator
Visible Marks
Yes
Service Interruption
No
Root Cause Category
Locating Issue
Root Cause Type
Facility Not Marked Due To Incomplete Marks At Damage Location
Preparer Name
J** R***
Preparer Title
Director Gas Asset Integrity Mgmt And Compliance
Preparer Email
J*******@l*****.com
Preparer Telephone
502-376-5944
Authorizer Name
J* G****** C******
Authorizer Title
Director Legal Services Associate General Counsel
Authorizer Telephone
502-627-2756
Authorizer Email
G***********@l*****.com
Narrative
On april 17, 2018, lg&e was notified at 12:04am of third party damage to an 8" steel distribution main at the intersection of hurstbourne lane and taylorsville road (nw corner) in jefferson county, kentucky. The pipeline was damaged by an auger being used by that third party to prepare to pour a foundation for a utility pole (not an lg&e pole). A perimeter was established and gas safely vented until it was shut off at approximately 11:00 am on april 18, 2018. No injuries occurred and no customers lost service.
Occurred At 2018-04-17 12:00:00
Year 2018
Report Received Date 2018-05-17 00:00:00
Iyear 2018.0
Report Number 20180056.0
Supplemental Number 35992.0
Report Type Supplemental Final
Operator Id 11824 PHMSA Enforcement
Name Louisville Gas & Electric Co
Operator Street Address 820 West Broadway, Po Box 32030
Operator City Name Louisville
Operator State Abbreviation KY
Operator Postal Code 40202
Local Datetime 2018-04-17 12:04:00
Time Zone Eastern
Daylight Savings Ind No
Location Street Address Intersection Of Hurstbourne Lane And Taylorsville Road
Location City Name Louisville
Location County Name Jefferson County
Location State Abbreviation KY
Location Postal Code 40214
Location Latitude 38.215802 Google Maps OpenStreetMap
Location Longitude -85.5912 Google Maps OpenStreetMap
Flow Cont Stopple Fitng Ind Yes
Nrc Rpt Datetime 2018-04-19 14:39:00
Nrc Rpt Num 1209754 NRC Report How to search
Commodity Released Type Natural Gas
Unintentional Release 1940.0
Intentional Release 0.0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Ignite Ind No
Num Pub Evacuated 0.0
Incident Identified Datetime 2018-04-17 12:00:00
On Site Datetime 2018-04-17 13:06:00
Federal No
Location Type Utility Right-Of-Way / Easement
Incident Area Type Underground
Incident Area Subtype Under Soil
Depth Of Cover 108.0
Other Underground Facilities No
Crossing No
Pipe Facility Type Investor Owned
System Part Involved Main
Installation Year 1962.0
Pipe Diameter 8.0
Pipe Specification Unknown
Pipe Manufacturer Unknown
Material Involved Steel
Steel Seam Type Other
Steel Seam Type Details Unknown
Release Type Mechanical Puncture
Puncture Axial 1.0
Puncture Circum 1.0
Class Location Type Class 3 Location
Est Cost Oper Paid 0.0
Est Cost Prop Damage 0.0
Est Cost Emergency 511394.0
Est Cost Other 0.0
Gas Cost In Mcf 3.8332
Est Cost Unintentional Release 7436.0
Est Cost Intentional Release 0.0
Prpty 518830.0
Commercial Affected 0.0
Industrial Affected 0.0
Residences Affected 0.0
Num Persons Hosp Not Ovnght 0.0
Num Injured Treated By Emt 0.0
Num Resident Building Affctd 0.0
Num Business Building Affctd 0.0
Accident Psig 55.0
Normal Psig 55.0
Mop Psig 60.0
Mop Cfr Section 192.619(A)(2) View CFR 49 §192
Maop Established Date 1962-09-18 00:00:00
Accident Pressure Pressure Did Not Exceed Maop
Gas Odorized System Type Injection Pump
Gas Odorized Lvl Not Msrd Ind Yes
Scada In Place Ind No
Accident Identifier Notification From Emergency Responder
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details There was no control room or scada involvement with the incident or response.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Excavation Damage
Cause Details Excavation Damage By Third Party
Ex Party Type Excavation Damage By Third Party
Prior Notification Ind Yes
One Call System Ind Yes
State Law Exempt Ind No
Notify Cga Dirt No
Public Row Ind Yes
Public Subtype State Highway
Excavator Type State
Excavator Equipment Auger
Work Performed Pole
One Call Notified Ind Yes
One Call Ticket Num 1804171010
Locator Type Contract Locator
Visible Marks Yes
Service Interruption No
Root Cause Category Locating Issue
Root Cause Type Facility Not Marked Due To Incomplete Marks At Damage Location
Preparer Name J** R***
Preparer Title Director Gas Asset Integrity Mgmt And Compliance
Preparer Email J*******@l*****.com
Preparer Telephone 502-376-5944
Authorizer Name J* G****** C******
Authorizer Title Director Legal Services Associate General Counsel
Authorizer Telephone 502-627-2756
Authorizer Email G***********@l*****.com
Narrative On april 17, 2018, lg&e was notified at 12:04am of third party damage to an 8" steel distribution main at the intersection of hurstbourne lane and taylorsville road (nw corner) in jefferson county, kentucky. The pipeline was damaged by an auger being used by that third party to prepare to pour a foundation for a utility pole (not an lg&e pole). A perimeter was established and gas safely vented until it was shut off at approximately 11:00 am on april 18, 2018. No injuries occurred and no customers lost service.