HL incident on 2017-12-02 — TX
Operator
Dcp Midstream
Cause
Equipment Failure
Commodity
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$200
Incident datetime
2017-12-02 11:55
Report number
Location
TX
Narrative
At 11:55 am on 12/2/2017, dcp midstream's houston control center (hcc) received a call from the neighboring targa plant control room. The operator at the targa plant stated that he saw a product vapor cloud blowing inside of the dcp facility at the mont belvieu station, on their cameras. A hcc controller notified an ngl tech of the situation who then proceeded on site to investigate. Around 12:19 pm the ngl tech which arrived onsite, notified hcc that everything was under control and the leak which occurred on a sampler speed loop motor was blocked in and completely isolated. Dcp determined that due to excessive vibration of the pump, the tubing broke off. The pump will now be bolted onto the concrete slab to alleviate any excessive vibration. Additionally, dcp is now engaged in conducting a site study to determine the most effective place to locate its leak detection equipment and for adding any additional equipment.
Detailed record list
Report Received Date
2017-12-20 00:00:00
Iyear
2017
Report Number
20170423
Supplemental Number
22982
Report Type
Supplemental Final
Operator Id
31130
Name
Dcp Midstream
Operator Street Address
2331 Citywest Blvd. Hq-08-S812-02
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77042
Local Datetime
2017-12-02 11:55:00
Location Latitude
29.827428
Location Longitude
-94.940951
Commodity Released Type
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype
Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid)
Unintentional Release Bbls
3.05
Intentional Release Bbls
0
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Other
Accident Details
Controller Stationed At A Neighboring Facility Made Notification To Dcp
Incident Identified Datetime
2017-12-02 11:55:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Shutdown Due Accident Ind
No
Shutdown Explain
Equipment Was Isolated
On Site Datetime
2017-12-02 12:05:00
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Mont Belvieu Station
Segment Name
Sahi-1
Onshore State Abbreviation
Tx
Onshore Postal Code
77521
Onshore City Name
Baytown
Onshore County Name
Harris
Designated Location
Survey Station No.
Designated Name
A09007d
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Intrastate
Item Involved
Tubing
Installation Year
2013
Material Involved
Material Other Than Carbon Steel
Material Details
Stainless Steel Tubing
Release Type
Leak
Leak Type
Other
Leak Type Other
Tubing Broke In Half
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
Other Pop Ind
Yes
Other Pop Yes No
Yes
Usa Drinking Ind
Yes
Usa Drinking Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
85
Est Cost Prop Damage
200
Est Cost Emergency
0
Est Cost Environmental
0
Est Cost Other
0
Prpty
285
Accident Psig
978
Mop Psig
1440
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
An investigation into a controller's actions or any control room issues was unwarranted since the underlying cause of the event was not directly related to either of the aforementioned.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Defective Or Loose Tubing Or Fitting
Eq Failure Type
Defective Or Loose Tubing Or Fitting
Additional Vibration Ind
Yes
Preparer Name
K*** F*****
Preparer Title
Ngl Pipeline Compliance And Integrity Specialist
Preparer Email
K*******@d***********.com
Preparer Telephone
7137353719
Prepared Date
2017-12-20 00:00:00
Authorizer Name
J*** P*******
Authorizer Telephone
405-605-3859
Authorizer Title
Manager Pipeline Compliance
Authorizer Email
J*********@d***********.com
Narrative
At 11:55 am on 12/2/2017, dcp midstream's houston control center (hcc) received a call from the neighboring targa plant control room. The operator at the targa plant stated that he saw a product vapor cloud blowing inside of the dcp facility at the mont belvieu station, on their cameras. A hcc controller notified an ngl tech of the situation who then proceeded on site to investigate. Around 12:19 pm the ngl tech which arrived onsite, notified hcc that everything was under control and the leak which occurred on a sampler speed loop motor was blocked in and completely isolated. Dcp determined that due to excessive vibration of the pump, the tubing broke off. The pump will now be bolted onto the concrete slab to alleviate any excessive vibration. Additionally, dcp is now engaged in conducting a site study to determine the most effective place to locate its leak detection equipment and for adding any additional equipment.
| Report Received Date | 2017-12-20 00:00:00 |
|---|---|
| Iyear | 2017 |
| Report Number | 20170423 |
| Supplemental Number | 22982 |
| Report Type | Supplemental Final |
| Operator Id | 31130 PHMSA Enforcement |
| Name | Dcp Midstream |
| Operator Street Address | 2331 Citywest Blvd. Hq-08-S812-02 |
| Operator City Name | Houston |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77042 |
| Local Datetime | 2017-12-02 11:55:00 |
| Location Latitude | 29.827428 Google Maps OpenStreetMap |
| Location Longitude | -94.940951 Google Maps OpenStreetMap |
| Commodity Released Type | Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions |
| Commodity Subtype | Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid) |
| Unintentional Release Bbls | 3.05 |
| Intentional Release Bbls | 0 |
| Recovered Bbls | 0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Other |
| Accident Details | Controller Stationed At A Neighboring Facility Made Notification To Dcp |
| Incident Identified Datetime | 2017-12-02 11:55:00 |
| System Part Involved | Onshore Pump/meter Station Equipment And Piping |
| On Off Shore | Onshore |
| Shutdown Due Accident Ind | No |
| Shutdown Explain | Equipment Was Isolated |
| On Site Datetime | 2017-12-02 12:05:00 |
| Nrc Rpt Num | Nrc Notification Not Required NRC Report How to search |
| Ignite Ind | No |
| Explode Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Mont Belvieu Station |
| Segment Name | Sahi-1 |
| Onshore State Abbreviation | Tx |
| Onshore Postal Code | 77521 |
| Onshore City Name | Baytown |
| Onshore County Name | Harris |
| Designated Location | Survey Station No. |
| Designated Name | A09007d |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
| Crossing | No |
| Pipe Facility Type | Intrastate |
| Item Involved | Tubing |
| Installation Year | 2013 |
| Material Involved | Material Other Than Carbon Steel |
| Material Details | Stainless Steel Tubing |
| Release Type | Leak |
| Leak Type | Other |
| Leak Type Other | Tubing Broke In Half |
| Wildlife Impact Ind | No |
| Soil Contamination | No |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | Yes |
| Commodity Reached Hca | Yes |
| Other Pop Ind | Yes |
| Other Pop Yes No | Yes |
| Usa Drinking Ind | Yes |
| Usa Drinking Yes No | Yes |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 85 |
| Est Cost Prop Damage | 200 |
| Est Cost Emergency | 0 |
| Est Cost Environmental | 0 |
| Est Cost Other | 0 |
| Prpty | 285 |
| Accident Psig | 978 |
| Mop Psig | 1440 |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Cpm In Place Ind | Yes |
| Cpm Operating Ind | Yes |
| Cpm Functional Ind | Yes |
| Cpm Detection Ind | No |
| Cpm Conf Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | An investigation into a controller's actions or any control room issues was unwarranted since the underlying cause of the event was not directly related to either of the aforementioned. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Equipment Failure |
| Cause Details | Defective Or Loose Tubing Or Fitting |
| Eq Failure Type | Defective Or Loose Tubing Or Fitting |
| Additional Vibration Ind | Yes |
| Preparer Name | K*** F***** |
| Preparer Title | Ngl Pipeline Compliance And Integrity Specialist |
| Preparer Email | K*******@d***********.com |
| Preparer Telephone | 7137353719 |
| Prepared Date | 2017-12-20 00:00:00 |
| Authorizer Name | J*** P******* |
| Authorizer Telephone | 405-605-3859 |
| Authorizer Title | Manager Pipeline Compliance |
| Authorizer Email | J*********@d***********.com |
| Narrative | At 11:55 am on 12/2/2017, dcp midstream's houston control center (hcc) received a call from the neighboring targa plant control room. The operator at the targa plant stated that he saw a product vapor cloud blowing inside of the dcp facility at the mont belvieu station, on their cameras. A hcc controller notified an ngl tech of the situation who then proceeded on site to investigate. Around 12:19 pm the ngl tech which arrived onsite, notified hcc that everything was under control and the leak which occurred on a sampler speed loop motor was blocked in and completely isolated. Dcp determined that due to excessive vibration of the pump, the tubing broke off. The pump will now be bolted onto the concrete slab to alleviate any excessive vibration. Additionally, dcp is now engaged in conducting a site study to determine the most effective place to locate its leak detection equipment and for adding any additional equipment. |