Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2017-10-25 — TX
Operator
Exxonmobil Oil Corporation-Terminals
Cause
Corrosion Failure
Commodity
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$5,000
Incident datetime
2017-10-25 12:00
Report number
Location
TX
Narrative
Tank 906 at lockport terminal was taken out of service for API 653 inspection. During the inspection, a through-wall corrosion pit was discovered. An approximate 12'x 12' square hole was cut in the tank bottom, and samples were taken from the soil/water between the tank bottom and underlying clay liner. Based upon sampling results, the estimated release volume is approximately 25 gallons. Remnants of abrasive material, or other contaminants, found under the coating affected its adhesion, which could have hastened the delamination and premature failure. 06/04/2018 - updated cost estimates, updated volume based on soil sampling results. 5/3/19 - updated part g, #7 by selecting water drop out, updated #8 by selecting metallurgical analysis, and updated the narrative with failure mechanism information.
Detailed record list
Report Received Date
2017-11-22 00:00:00
Iyear
2017
Report Number
20170387
Supplemental Number
32087
Report Type
Supplemental Final
Operator Id
32009
Name
Exxonmobil Oil Corporation-Terminals
Operator Street Address
22777 Springwoods Village Parkway Emhc/e3.5a.598
Operator City Name
Spring
Operator State Abbreviation
TX
Operator Postal Code
77389
Local Datetime
2017-10-25 12:00:00
Location Latitude
41.64924
Location Longitude
-88.04449
Commodity Released Type
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype
Diesel, Fuel Oil, Kerosene, Jet Fuel
Unintentional Release Bbls
0.6
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Contractor Working For The Operator
Incident Identified Datetime
2017-10-25 12:00:00
System Part Involved
Onshore Breakout Tank Or Storage Vessel, Including Attached Appurtenances
On Off Shore
Onshore
Shutdown Due Accident Ind
No
Shutdown Explain
Release Was Discovered During An Out Of Service Inspection Of Lockport Tk 906
On Site Datetime
2017-10-25 12:00:00
Nrc Rpt Datetime
2017-11-22 14:10:00
Nrc Rpt Num
1197931
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Lockport Terminal
Segment Name
Lockport Terminal
Onshore State Abbreviation
Il
Onshore Postal Code
60441
Onshore City Name
Lockport
Onshore County Name
Will
Designated Location
Survey Station No.
Designated Name
Lockport Term
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Tank, Including Attached Appurtenances
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Tank/vessel
Tank Vessel Subtype
Single Bottom System
Tank Type
Atmospheric
Api Std Out Of Service Year
1997
Api Std In Service Year
2016
Installation Year
1972
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
Yes
Soil Remed Ind
Yes
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
High Pop Ind
Yes
High Pop Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
75
Est Cost Prop Damage
5000
Est Cost Emergency
0
Est Cost Environmental
0
Est Cost Other
43000
Est Cost Other Details
Soil Sampling Underneath The Tank.
Prpty
48075
Accident Psig
0
Mop Psig
0
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
No
Cpm In Place Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Release was discovered during an out of service inspection of tank 906
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
Internal Corrosion
Internal External
Internal Corrosion
Int Visual Exam Results
Localized Pitting
Int Water Acid Ind
Yes
Int Field Exam Basis Ind
Yes
Int Metallurgical Basis Ind
Yes
Int Other Loc Ind
Yes
Corrosion Location Details
Tank Floor
Corrosion Inhibitors
No
Corrosion Lining
Yes
Cleaning Dewatering
Not Applicable - Not Mainline Pipe
Corrosion Coupons
Not Applicable - Not Mainline Pipe
Preparer Name
J** M*********
Preparer Title
Pipeline Safety Advisor
Preparer Email
J*****************@e*********.com
Preparer Telephone
8326246121
Prepared Date
2019-05-06 00:00:00
Authorizer Name
C******* B* H********
Authorizer Telephone
8326247920
Authorizer Title
She Manager
Authorizer Email
C*******************@e*********.com
Narrative
Tank 906 at lockport terminal was taken out of service for API 653 inspection. During the inspection, a through-wall corrosion pit was discovered. An approximate 12'x 12' square hole was cut in the tank bottom, and samples were taken from the soil/water between the tank bottom and underlying clay liner. Based upon sampling results, the estimated release volume is approximately 25 gallons. Remnants of abrasive material, or other contaminants, found under the coating affected its adhesion, which could have hastened the delamination and premature failure. 06/04/2018 - updated cost estimates, updated volume based on soil sampling results. 5/3/19 - updated part g, #7 by selecting water drop out, updated #8 by selecting metallurgical analysis, and updated the narrative with failure mechanism information.
| Report Received Date | 2017-11-22 00:00:00 |
|---|---|
| Iyear | 2017 |
| Report Number | 20170387 |
| Supplemental Number | 32087 |
| Report Type | Supplemental Final |
| Operator Id | 32009 PHMSA Enforcement |
| Name | Exxonmobil Oil Corporation-Terminals |
| Operator Street Address | 22777 Springwoods Village Parkway Emhc/e3.5a.598 |
| Operator City Name | Spring |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77389 |
| Local Datetime | 2017-10-25 12:00:00 |
| Location Latitude | 41.64924 Google Maps OpenStreetMap |
| Location Longitude | -88.04449 Google Maps OpenStreetMap |
| Commodity Released Type | Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions |
| Commodity Subtype | Diesel, Fuel Oil, Kerosene, Jet Fuel |
| Unintentional Release Bbls | 0.6 |
| Recovered Bbls | 0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Contractor Working For The Operator |
| Incident Identified Datetime | 2017-10-25 12:00:00 |
| System Part Involved | Onshore Breakout Tank Or Storage Vessel, Including Attached Appurtenances |
| On Off Shore | Onshore |
| Shutdown Due Accident Ind | No |
| Shutdown Explain | Release Was Discovered During An Out Of Service Inspection Of Lockport Tk 906 |
| On Site Datetime | 2017-10-25 12:00:00 |
| Nrc Rpt Datetime | 2017-11-22 14:10:00 |
| Nrc Rpt Num | 1197931 NRC Report How to search |
| Ignite Ind | No |
| Explode Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Lockport Terminal |
| Segment Name | Lockport Terminal |
| Onshore State Abbreviation | Il |
| Onshore Postal Code | 60441 |
| Onshore City Name | Lockport |
| Onshore County Name | Will |
| Designated Location | Survey Station No. |
| Designated Name | Lockport Term |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Tank, Including Attached Appurtenances |
| Crossing | No |
| Pipe Facility Type | Interstate |
| Item Involved | Tank/vessel |
| Tank Vessel Subtype | Single Bottom System |
| Tank Type | Atmospheric |
| Api Std Out Of Service Year | 1997 |
| Api Std In Service Year | 2016 |
| Installation Year | 1972 |
| Material Involved | Carbon Steel |
| Release Type | Leak |
| Leak Type | Pinhole |
| Wildlife Impact Ind | No |
| Soil Contamination | Yes |
| Long Term Assessment | No |
| Remediation Ind | Yes |
| Soil Remed Ind | Yes |
| Water Contam Ind | No |
| Could Be Hca | Yes |
| Commodity Reached Hca | Yes |
| High Pop Ind | Yes |
| High Pop Yes No | Yes |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 75 |
| Est Cost Prop Damage | 5000 |
| Est Cost Emergency | 0 |
| Est Cost Environmental | 0 |
| Est Cost Other | 43000 |
| Est Cost Other Details | Soil Sampling Underneath The Tank. |
| Prpty | 48075 |
| Accident Psig | 0 |
| Mop Psig | 0 |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | No |
| Cpm In Place Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | Release was discovered during an out of service inspection of tank 906 |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Corrosion Failure |
| Cause Details | Internal Corrosion |
| Internal External | Internal Corrosion |
| Int Visual Exam Results | Localized Pitting |
| Int Water Acid Ind | Yes |
| Int Field Exam Basis Ind | Yes |
| Int Metallurgical Basis Ind | Yes |
| Int Other Loc Ind | Yes |
| Corrosion Location Details | Tank Floor |
| Corrosion Inhibitors | No |
| Corrosion Lining | Yes |
| Cleaning Dewatering | Not Applicable - Not Mainline Pipe |
| Corrosion Coupons | Not Applicable - Not Mainline Pipe |
| Preparer Name | J** M********* |
| Preparer Title | Pipeline Safety Advisor |
| Preparer Email | J*****************@e*********.com |
| Preparer Telephone | 8326246121 |
| Prepared Date | 2019-05-06 00:00:00 |
| Authorizer Name | C******* B* H******** |
| Authorizer Telephone | 8326247920 |
| Authorizer Title | She Manager |
| Authorizer Email | C*******************@e*********.com |
| Narrative | Tank 906 at lockport terminal was taken out of service for API 653 inspection. During the inspection, a through-wall corrosion pit was discovered. An approximate 12'x 12' square hole was cut in the tank bottom, and samples were taken from the soil/water between the tank bottom and underlying clay liner. Based upon sampling results, the estimated release volume is approximately 25 gallons. Remnants of abrasive material, or other contaminants, found under the coating affected its adhesion, which could have hastened the delamination and premature failure. 06/04/2018 - updated cost estimates, updated volume based on soil sampling results. 5/3/19 - updated part g, #7 by selecting water drop out, updated #8 by selecting metallurgical analysis, and updated the narrative with failure mechanism information. |