Narrative
Tank 906 at lockport terminal was taken out of service for API 653 inspection. During the inspection, a through-wall corrosion pit was discovered. An approximate 12'x 12' square hole was cut in the tank bottom, and samples were taken from the soil/water between the tank bottom and underlying clay liner. Based upon sampling results, the estimated release volume is approximately 25 gallons. Remnants of abrasive material, or other contaminants, found under the coating affected its adhesion, which could have hastened the delamination and premature failure. 06/04/2018 - updated cost estimates, updated volume based on soil sampling results. 5/3/19 - updated part g, #7 by selecting water drop out, updated #8 by selecting metallurgical analysis, and updated the narrative with failure mechanism information.
Detailed record list
Report Received Date
2017-11-22 00:00:00
Iyear
2017
Report Number
20170387
Supplemental Number
32087
Report Type
Supplemental Final
Operator Id
Name
Exxonmobil Oil Corporation-Terminals
Operator Street Address
22777 Springwoods Village Parkway Emhc/e3.5a.598
Operator City Name
Spring
Operator State Abbreviation
TX
Operator Postal Code
77389
Local Datetime
2017-10-25 12:00:00
Location Latitude
Location Longitude
Commodity Released Type
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype
Diesel, Fuel Oil, Kerosene, Jet Fuel
Unintentional Release Bbls
0.6
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Contractor Working For The Operator
Incident Identified Datetime
2017-10-25 12:00:00
System Part Involved
Onshore Breakout Tank Or Storage Vessel, Including Attached Appurtenances
On Off Shore
Onshore
Shutdown Due Accident Ind
No
Shutdown Explain
Release Was Discovered During An Out Of Service Inspection Of Lockport Tk 906
On Site Datetime
2017-10-25 12:00:00
Nrc Rpt Datetime
2017-11-22 14:10:00
Nrc Rpt Num
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Lockport Terminal
Segment Name
Lockport Terminal
Onshore State Abbreviation
Il
Onshore Postal Code
60441
Onshore City Name
Lockport
Onshore County Name
Will
Designated Location
Survey Station No.
Designated Name
Lockport Term
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Tank, Including Attached Appurtenances
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Tank/vessel
Tank Vessel Subtype
Single Bottom System
Tank Type
Atmospheric
Api Std Out Of Service Year
1997
Api Std In Service Year
2016
Installation Year
1972
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
Yes
Soil Remed Ind
Yes
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
High Pop Ind
Yes
High Pop Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
75
Est Cost Prop Damage
5000
Est Cost Emergency
0
Est Cost Environmental
0
Est Cost Other
43000
Est Cost Other Details
Soil Sampling Underneath The Tank.
Prpty
48075
Accident Psig
0
Mop Psig
0
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
No
Cpm In Place Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Release was discovered during an out of service inspection of tank 906
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
Internal Corrosion
Internal External
Internal Corrosion
Int Visual Exam Results
Localized Pitting
Int Water Acid Ind
Yes
Int Field Exam Basis Ind
Yes
Int Metallurgical Basis Ind
Yes
Int Other Loc Ind
Yes
Corrosion Location Details
Tank Floor
Corrosion Inhibitors
No
Corrosion Lining
Yes
Cleaning Dewatering
Not Applicable - Not Mainline Pipe
Corrosion Coupons
Not Applicable - Not Mainline Pipe
Preparer Name
J** M*********
Preparer Title
Pipeline Safety Advisor
Preparer Email
J*****************@e*********.com
Preparer Telephone
8326246121
Prepared Date
2019-05-06 00:00:00
Authorizer Name
C******* B* H********
Authorizer Telephone
8326247920
Authorizer Title
She Manager
Authorizer Email
C*******************@e*********.com
Narrative
Tank 906 at lockport terminal was taken out of service for API 653 inspection. During the inspection, a through-wall corrosion pit was discovered. An approximate 12'x 12' square hole was cut in the tank bottom, and samples were taken from the soil/water between the tank bottom and underlying clay liner. Based upon sampling results, the estimated release volume is approximately 25 gallons. Remnants of abrasive material, or other contaminants, found under the coating affected its adhesion, which could have hastened the delamination and premature failure. 06/04/2018 - updated cost estimates, updated volume based on soil sampling results. 5/3/19 - updated part g, #7 by selecting water drop out, updated #8 by selecting metallurgical analysis, and updated the narrative with failure mechanism information.
Report Received Date 2017-11-22 00:00:00
Iyear 2017
Report Number 20170387
Supplemental Number 32087
Report Type Supplemental Final
Operator Id 32009 PHMSA Enforcement
Name Exxonmobil Oil Corporation-Terminals
Operator Street Address 22777 Springwoods Village Parkway Emhc/e3.5a.598
Operator City Name Spring
Operator State Abbreviation TX
Operator Postal Code 77389
Local Datetime 2017-10-25 12:00:00
Location Latitude 41.64924 Google Maps OpenStreetMap
Location Longitude -88.04449 Google Maps OpenStreetMap
Commodity Released Type Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype Diesel, Fuel Oil, Kerosene, Jet Fuel
Unintentional Release Bbls 0.6
Recovered Bbls 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Contractor Working For The Operator
Incident Identified Datetime 2017-10-25 12:00:00
System Part Involved Onshore Breakout Tank Or Storage Vessel, Including Attached Appurtenances
On Off Shore Onshore
Shutdown Due Accident Ind No
Shutdown Explain Release Was Discovered During An Out Of Service Inspection Of Lockport Tk 906
On Site Datetime 2017-10-25 12:00:00
Nrc Rpt Datetime 2017-11-22 14:10:00
Nrc Rpt Num 1197931 NRC Report How to search
Ignite Ind No
Explode Ind No
Num Pub Evacuated 0
Pipe Fac Name Lockport Terminal
Segment Name Lockport Terminal
Onshore State Abbreviation Il
Onshore Postal Code 60441
Onshore City Name Lockport
Onshore County Name Will
Designated Location Survey Station No.
Designated Name Lockport Term
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Tank, Including Attached Appurtenances
Crossing No
Pipe Facility Type Interstate
Item Involved Tank/vessel
Tank Vessel Subtype Single Bottom System
Tank Type Atmospheric
Api Std Out Of Service Year 1997
Api Std In Service Year 2016
Installation Year 1972
Material Involved Carbon Steel
Release Type Leak
Leak Type Pinhole
Wildlife Impact Ind No
Soil Contamination Yes
Long Term Assessment No
Remediation Ind Yes
Soil Remed Ind Yes
Water Contam Ind No
Could Be Hca Yes
Commodity Reached Hca Yes
High Pop Ind Yes
High Pop Yes No Yes
Est Cost Oper Paid 0
Est Cost Gas Released 75
Est Cost Prop Damage 5000
Est Cost Emergency 0
Est Cost Environmental 0
Est Cost Other 43000
Est Cost Other Details Soil Sampling Underneath The Tank.
Prpty 48075
Accident Psig 0
Mop Psig 0
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind No
Cpm In Place Ind No
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details Release was discovered during an out of service inspection of tank 906
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Corrosion Failure
Cause Details Internal Corrosion
Internal External Internal Corrosion
Int Visual Exam Results Localized Pitting
Int Water Acid Ind Yes
Int Field Exam Basis Ind Yes
Int Metallurgical Basis Ind Yes
Int Other Loc Ind Yes
Corrosion Location Details Tank Floor
Corrosion Inhibitors No
Corrosion Lining Yes
Cleaning Dewatering Not Applicable - Not Mainline Pipe
Corrosion Coupons Not Applicable - Not Mainline Pipe
Preparer Name J** M*********
Preparer Title Pipeline Safety Advisor
Preparer Email J*****************@e*********.com
Preparer Telephone 8326246121
Prepared Date 2019-05-06 00:00:00
Authorizer Name C******* B* H********
Authorizer Telephone 8326247920
Authorizer Title She Manager
Authorizer Email C*******************@e*********.com
Narrative Tank 906 at lockport terminal was taken out of service for API 653 inspection. During the inspection, a through-wall corrosion pit was discovered. An approximate 12'x 12' square hole was cut in the tank bottom, and samples were taken from the soil/water between the tank bottom and underlying clay liner. Based upon sampling results, the estimated release volume is approximately 25 gallons. Remnants of abrasive material, or other contaminants, found under the coating affected its adhesion, which could have hastened the delamination and premature failure. 06/04/2018 - updated cost estimates, updated volume based on soil sampling results. 5/3/19 - updated part g, #7 by selecting water drop out, updated #8 by selecting metallurgical analysis, and updated the narrative with failure mechanism information.