HL incident on 2017-09-23 — OK
Operator
Oneok Ngl Pipeline, Llc
Cause
Equipment Failure
Commodity
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$250
Incident datetime
2017-09-23 03:03
Report number
Location
OK
Narrative
Oneok pipeline control center received a gas detect alarm at the oneok red river pump station at approximately 3:03 am on september 23rd, 2017. The pump station shutdown once the gas detect activated. Pipeline control contacted the local area representative and dispatched him to the site. Upon arrival the oneok employee identified an ice ball on the side of some 1/2" stainless steel tubing used as a seal flush line on the pump. The tubing was isolated and removed and replaced with new tubing. Once the ice ball had thawed it was determined the tubing wall had cracked on the side of a bend. Tubing had been in place since the pump station had been commissioned (2007). All of the stainless steel tubing in the pump station and no other indications of cracks were identified. Once the tubing had been replaces and the gas detection alarms were reset the station was returned to normal operation. Updated 10/20/2017 - corrected hca type to - unsually sensitive area(USA) - ecological
Detailed record list
Report Received Date
2017-10-19 00:00:00
Iyear
2017
Report Number
20170341
Supplemental Number
22747
Report Type
Supplemental Final
Operator Id
32109
Name
Oneok Ngl Pipeline, Llc
Operator Street Address
100 West Fifth Street
Operator City Name
Tulsa
Operator State Abbreviation
OK
Operator Postal Code
74103
Local Datetime
2017-09-23 03:03:00
Location Latitude
33.730409
Location Longitude
-96.443294
Commodity Released Type
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype
Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid)
Unintentional Release Bbls
2.2
Intentional Release Bbls
0
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Cpm Leak Detection System Or Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Calculations)
Incident Identified Datetime
2017-09-23 03:03:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2017-09-23 03:03:00
Restart Datetime
2017-09-23 05:30:00
On Site Datetime
2017-09-23 04:24:00
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Oneok Red River Pump Station
Segment Name
Oneok Red River Pumps Station Site #444
Onshore State Abbreviation
Tx
Onshore Postal Code
75020
Onshore City Name
Not Within A Municipality
Onshore County Name
Grayson
Designated Location
Milepost/valve Station
Designated Name
Pump Station
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Tubing
Installation Year
2007
Material Involved
Material Other Than Carbon Steel
Material Details
Stainless Steel Tubing
Release Type
Leak
Leak Type
Crack
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
Usa Ecological Ind
Yes
Usa Ecological Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
85
Est Cost Prop Damage
250
Est Cost Emergency
250
Est Cost Environmental
0
Est Cost Other
0
Prpty
585
Accident Psig
600
Mop Psig
1800
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
No controller actions had taken place at the station prior to the release.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Defective Or Loose Tubing Or Fitting
Eq Failure Type
Defective Or Loose Tubing Or Fitting
Eq Additional Other Ind
Yes
Eq Additional Other Details
Crack In Section Of 1/2" Stainless Steel Tubing, Located On Side Of Bend.
Preparer Name
N*** J****
Preparer Title
Requlatory Compliance Manager
Preparer Email
N*********@o****.com
Preparer Telephone
580-395-6304
Preparer Fax
580-395-2933
Prepared Date
2017-10-20 00:00:00
Authorizer Name
N*** J****
Authorizer Telephone
580-395-6304
Authorizer Title
Regulatory Compliance Manager
Authorizer Email
N*********@o****.com
Narrative
Oneok pipeline control center received a gas detect alarm at the oneok red river pump station at approximately 3:03 am on september 23rd, 2017. The pump station shutdown once the gas detect activated. Pipeline control contacted the local area representative and dispatched him to the site. Upon arrival the oneok employee identified an ice ball on the side of some 1/2" stainless steel tubing used as a seal flush line on the pump. The tubing was isolated and removed and replaced with new tubing. Once the ice ball had thawed it was determined the tubing wall had cracked on the side of a bend. Tubing had been in place since the pump station had been commissioned (2007). All of the stainless steel tubing in the pump station and no other indications of cracks were identified. Once the tubing had been replaces and the gas detection alarms were reset the station was returned to normal operation. Updated 10/20/2017 - corrected hca type to - unsually sensitive area(USA) - ecological
| Report Received Date | 2017-10-19 00:00:00 |
|---|---|
| Iyear | 2017 |
| Report Number | 20170341 |
| Supplemental Number | 22747 |
| Report Type | Supplemental Final |
| Operator Id | 32109 PHMSA Enforcement |
| Name | Oneok Ngl Pipeline, Llc |
| Operator Street Address | 100 West Fifth Street |
| Operator City Name | Tulsa |
| Operator State Abbreviation | OK |
| Operator Postal Code | 74103 |
| Local Datetime | 2017-09-23 03:03:00 |
| Location Latitude | 33.730409 Google Maps OpenStreetMap |
| Location Longitude | -96.443294 Google Maps OpenStreetMap |
| Commodity Released Type | Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions |
| Commodity Subtype | Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid) |
| Unintentional Release Bbls | 2.2 |
| Intentional Release Bbls | 0 |
| Recovered Bbls | 0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Cpm Leak Detection System Or Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Calculations) |
| Incident Identified Datetime | 2017-09-23 03:03:00 |
| System Part Involved | Onshore Pump/meter Station Equipment And Piping |
| On Off Shore | Onshore |
| Shutdown Due Accident Ind | Yes |
| Shutdown Datetime | 2017-09-23 03:03:00 |
| Restart Datetime | 2017-09-23 05:30:00 |
| On Site Datetime | 2017-09-23 04:24:00 |
| Nrc Rpt Num | Nrc Notification Not Required NRC Report How to search |
| Ignite Ind | No |
| Explode Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Oneok Red River Pump Station |
| Segment Name | Oneok Red River Pumps Station Site #444 |
| Onshore State Abbreviation | Tx |
| Onshore Postal Code | 75020 |
| Onshore City Name | Not Within A Municipality |
| Onshore County Name | Grayson |
| Designated Location | Milepost/valve Station |
| Designated Name | Pump Station |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
| Crossing | No |
| Pipe Facility Type | Interstate |
| Item Involved | Tubing |
| Installation Year | 2007 |
| Material Involved | Material Other Than Carbon Steel |
| Material Details | Stainless Steel Tubing |
| Release Type | Leak |
| Leak Type | Crack |
| Wildlife Impact Ind | No |
| Soil Contamination | No |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | Yes |
| Commodity Reached Hca | Yes |
| Usa Ecological Ind | Yes |
| Usa Ecological Yes No | Yes |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 85 |
| Est Cost Prop Damage | 250 |
| Est Cost Emergency | 250 |
| Est Cost Environmental | 0 |
| Est Cost Other | 0 |
| Prpty | 585 |
| Accident Psig | 600 |
| Mop Psig | 1800 |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | Yes |
| Scada Conf Ind | No |
| Cpm In Place Ind | Yes |
| Cpm Operating Ind | Yes |
| Cpm Functional Ind | Yes |
| Cpm Detection Ind | No |
| Cpm Conf Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | No controller actions had taken place at the station prior to the release. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Equipment Failure |
| Cause Details | Defective Or Loose Tubing Or Fitting |
| Eq Failure Type | Defective Or Loose Tubing Or Fitting |
| Eq Additional Other Ind | Yes |
| Eq Additional Other Details | Crack In Section Of 1/2" Stainless Steel Tubing, Located On Side Of Bend. |
| Preparer Name | N*** J**** |
| Preparer Title | Requlatory Compliance Manager |
| Preparer Email | N*********@o****.com |
| Preparer Telephone | 580-395-6304 |
| Preparer Fax | 580-395-2933 |
| Prepared Date | 2017-10-20 00:00:00 |
| Authorizer Name | N*** J**** |
| Authorizer Telephone | 580-395-6304 |
| Authorizer Title | Regulatory Compliance Manager |
| Authorizer Email | N*********@o****.com |
| Narrative | Oneok pipeline control center received a gas detect alarm at the oneok red river pump station at approximately 3:03 am on september 23rd, 2017. The pump station shutdown once the gas detect activated. Pipeline control contacted the local area representative and dispatched him to the site. Upon arrival the oneok employee identified an ice ball on the side of some 1/2" stainless steel tubing used as a seal flush line on the pump. The tubing was isolated and removed and replaced with new tubing. Once the ice ball had thawed it was determined the tubing wall had cracked on the side of a bend. Tubing had been in place since the pump station had been commissioned (2007). All of the stainless steel tubing in the pump station and no other indications of cracks were identified. Once the tubing had been replaces and the gas detection alarms were reset the station was returned to normal operation. Updated 10/20/2017 - corrected hca type to - unsually sensitive area(USA) - ecological |