HL incident on 2017-08-28 — TX

Operator
Dry Trails Midstream Energy, Llc
Cause
Natural Force Damage
Commodity
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$109,592
Incident datetime
2017-08-28 01:04
Report number
Location
TX
Narrative
Texas county, ok emergency dispatcher received call from an unknown source reporting a small fire in a pasture. Fire department was dispatched. Dcp and wtg were also notified. Dcp notified badger first responder at 0045 on august 28, 2017. As a precautionary measure, badger responder notified breitburn plant to shut down pumps at 0045 on august 28, 2017. Leak was verified as being on the dry trails pipeline at 0104, august 28, 2017. Upstream block valve at straight valve set was closed at 0130, august 28, 2017, downstream block valve at midway valve set was closed at 0145, august 28, 2017. In order to provide double block and bleed, hooker valve set was closed at 0900, august 28, 2017. A small fire was allowed to continue to burn off vapors until flares could be installed. 24 hour security and monitoring was initiated. Upon product extraction, line was excavated for observation and repair methodology. Open hole inspection revealed no evidence of corrosion. Coal tar coating was found to be bonded and in very good condition. Recent ili data revealed the nearest anomaly (56 % metal loss) at 1636 feet downstream of the leak. A small pinhole was observed with surrounding coating blown away. The pinhole was surrounded by a half inch diameter pit with very shiny metal flow away from the pit. A very recent extreme source of heat and rapid cooling was determined to be the source. Due to a lightening storm reported in the area at the time of the incident, a lightening strike was considered as the most likely source. A decision was made to replace 13.5 feet of pipe. Metalurgical analysis in progress.
Detailed record list
Report Received Date
2017-09-26 00:00:00
Iyear
2017
Report Number
20170304
Supplemental Number
22697
Report Type
Supplemental Final
Operator Id
Name
Dry Trails Midstream Energy, Llc
Operator Street Address
910 Louisiana Suite 2400
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2017-08-27 23:37:00
Location Latitude
Location Longitude
Commodity Released Type
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype
Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid)
Unintentional Release Bbls
74.2
Intentional Release Bbls
1962
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Notification From Emergency Responder
Incident Identified Datetime
2017-08-28 01:04:00
System Part Involved
Onshore Pipeline, Including Valve Sites
On Off Shore
Onshore
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2017-08-28 00:45:00
Restart Datetime
2017-09-12 10:20:00
On Site Datetime
2017-08-28 01:04:00
Nrc Rpt Datetime
2017-08-28 11:24:00
Nrc Rpt Num
Ignite Ind
Yes
Explode Ind
No
Upstream Valve Type Ind
Manual
Downstream Valve Type Ind
Manual
Num Pub Evacuated
0
Pipe Fac Name
Dry Trails Pipeline
Segment Name
Straight Block Valve To Midway Block Valve
Onshore State Abbreviation
Ok
Onshore Postal Code
73942
Onshore City Name
Not Within A Municipality
Onshore County Name
Texas
Designated Location
Survey Station No.
Designated Name
71575.16 Odo
Federal
No
Location Type
Pipeline Right-Of-Way
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
44
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Pipe
Pipe Type
Pipe Body
Pipe Diameter
4
Pipe Wall Thickness
0.125
Pipe Smys
Unknown
Pipe Specification
Api-5lx-42, 46, 52
Pipe Seam Type
Erw - High Frequency
Pipe Manufacturer
Unknown
Pipe Coating Type
Asphalt
Installation Year
1969
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
Yes
Remediation Ind
Yes
Soil Remed Ind
Yes
Vegetation Remed Ind
Yes
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
2050
Est Cost Gas Released
95373
Est Cost Prop Damage
109592
Est Cost Emergency
10000
Est Cost Environmental
0
Est Cost Other
8800
Est Cost Other Details
Trucking Costs.
Prpty
225815
Accident Psig
265
Mop Psig
968
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
Yes
Exceed Restriction Ind
No
Phmsa Restriction Ind
Not Mandated
Length Segment Isolated
39600
Internal Inspection Ind
Yes
Operation Complications Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Pressure trending revealed a pipeline pressure of 242 psi at 2300, 265 psi at the time of discovery, 270 psi at 0000, and 287 psi at 0100. Pinhole leak resulted in no pressure loss or downward pressure trend to alert the control room of a potential leak. A lightening storm was in the area at the time of discovery and is suspected as the source of failure. That being a lightening strike. An investigation is underway to confirm rca.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Natural Force Damage
Cause Details
Lightning
Natural Force Type
Lightning
Lightning Subtype
Direct Hit
Nf Other Details
,,,
Nf Extreme Weather Ind
Yes
Nf Other Ind
Yes
Nf Extreme Weather Details
Lightening Storm Verified At The Time Of Incident.
Preparer Name
W****** T* K*********
Preparer Title
Badger Compliance Officer
Preparer Email
T**********@b**************.com
Preparer Telephone
3378494230
Prepared Date
2017-09-29 00:00:00
Authorizer Name
D*** M*****
Authorizer Telephone
7139603111
Authorizer Title
Badger Vp Operations
Authorizer Email
D******@b**************.com
Narrative
Texas county, ok emergency dispatcher received call from an unknown source reporting a small fire in a pasture. Fire department was dispatched. Dcp and wtg were also notified. Dcp notified badger first responder at 0045 on august 28, 2017. As a precautionary measure, badger responder notified breitburn plant to shut down pumps at 0045 on august 28, 2017. Leak was verified as being on the dry trails pipeline at 0104, august 28, 2017. Upstream block valve at straight valve set was closed at 0130, august 28, 2017, downstream block valve at midway valve set was closed at 0145, august 28, 2017. In order to provide double block and bleed, hooker valve set was closed at 0900, august 28, 2017. A small fire was allowed to continue to burn off vapors until flares could be installed. 24 hour security and monitoring was initiated. Upon product extraction, line was excavated for observation and repair methodology. Open hole inspection revealed no evidence of corrosion. Coal tar coating was found to be bonded and in very good condition. Recent ili data revealed the nearest anomaly (56 % metal loss) at 1636 feet downstream of the leak. A small pinhole was observed with surrounding coating blown away. The pinhole was surrounded by a half inch diameter pit with very shiny metal flow away from the pit. A very recent extreme source of heat and rapid cooling was determined to be the source. Due to a lightening storm reported in the area at the time of the incident, a lightening strike was considered as the most likely source. A decision was made to replace 13.5 feet of pipe. Metalurgical analysis in progress.
Report Received Date 2017-09-26 00:00:00
Iyear 2017
Report Number 20170304
Supplemental Number 22697
Report Type Supplemental Final
Operator Id 32454 PHMSA Enforcement
Name Dry Trails Midstream Energy, Llc
Operator Street Address 910 Louisiana Suite 2400
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Local Datetime 2017-08-27 23:37:00
Location Latitude 36.855973 Google Maps OpenStreetMap
Location Longitude -101.381356 Google Maps OpenStreetMap
Commodity Released Type Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid)
Unintentional Release Bbls 74.2
Intentional Release Bbls 1962
Recovered Bbls 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Notification From Emergency Responder
Incident Identified Datetime 2017-08-28 01:04:00
System Part Involved Onshore Pipeline, Including Valve Sites
On Off Shore Onshore
Shutdown Due Accident Ind Yes
Shutdown Datetime 2017-08-28 00:45:00
Restart Datetime 2017-09-12 10:20:00
On Site Datetime 2017-08-28 01:04:00
Nrc Rpt Datetime 2017-08-28 11:24:00
Nrc Rpt Num 1188603 NRC Report How to search
Ignite Ind Yes
Explode Ind No
Upstream Valve Type Ind Manual
Downstream Valve Type Ind Manual
Num Pub Evacuated 0
Pipe Fac Name Dry Trails Pipeline
Segment Name Straight Block Valve To Midway Block Valve
Onshore State Abbreviation Ok
Onshore Postal Code 73942
Onshore City Name Not Within A Municipality
Onshore County Name Texas
Designated Location Survey Station No.
Designated Name 71575.16 Odo
Federal No
Location Type Pipeline Right-Of-Way
Incident Area Type Underground
Incident Area Subtype Under Soil
Depth Of Cover 44
Crossing No
Pipe Facility Type Interstate
Item Involved Pipe
Pipe Type Pipe Body
Pipe Diameter 4
Pipe Wall Thickness 0.125
Pipe Smys Unknown
Pipe Specification Api-5lx-42, 46, 52
Pipe Seam Type Erw - High Frequency
Pipe Manufacturer Unknown
Pipe Coating Type Asphalt
Installation Year 1969
Manufactured Year Unknown
Material Involved Carbon Steel
Release Type Leak
Leak Type Pinhole
Wildlife Impact Ind No
Soil Contamination No
Long Term Assessment Yes
Remediation Ind Yes
Soil Remed Ind Yes
Vegetation Remed Ind Yes
Water Contam Ind No
Could Be Hca No
Commodity Reached Hca No
Est Cost Oper Paid 2050
Est Cost Gas Released 95373
Est Cost Prop Damage 109592
Est Cost Emergency 10000
Est Cost Environmental 0
Est Cost Other 8800
Est Cost Other Details Trucking Costs.
Prpty 225815
Accident Psig 265
Mop Psig 968
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind Yes
Exceed Restriction Ind No
Phmsa Restriction Ind Not Mandated
Length Segment Isolated 39600
Internal Inspection Ind Yes
Operation Complications Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Cpm In Place Ind No
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details Pressure trending revealed a pipeline pressure of 242 psi at 2300, 265 psi at the time of discovery, 270 psi at 0000, and 287 psi at 0100. Pinhole leak resulted in no pressure loss or downward pressure trend to alert the control room of a potential leak. A lightening storm was in the area at the time of discovery and is suspected as the source of failure. That being a lightening strike. An investigation is underway to confirm rca.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Natural Force Damage
Cause Details Lightning
Natural Force Type Lightning
Lightning Subtype Direct Hit
Nf Other Details ,,,
Nf Extreme Weather Ind Yes
Nf Other Ind Yes
Nf Extreme Weather Details Lightening Storm Verified At The Time Of Incident.
Preparer Name W****** T* K*********
Preparer Title Badger Compliance Officer
Preparer Email T**********@b**************.com
Preparer Telephone 3378494230
Prepared Date 2017-09-29 00:00:00
Authorizer Name D*** M*****
Authorizer Telephone 7139603111
Authorizer Title Badger Vp Operations
Authorizer Email D******@b**************.com
Narrative Texas county, ok emergency dispatcher received call from an unknown source reporting a small fire in a pasture. Fire department was dispatched. Dcp and wtg were also notified. Dcp notified badger first responder at 0045 on august 28, 2017. As a precautionary measure, badger responder notified breitburn plant to shut down pumps at 0045 on august 28, 2017. Leak was verified as being on the dry trails pipeline at 0104, august 28, 2017. Upstream block valve at straight valve set was closed at 0130, august 28, 2017, downstream block valve at midway valve set was closed at 0145, august 28, 2017. In order to provide double block and bleed, hooker valve set was closed at 0900, august 28, 2017. A small fire was allowed to continue to burn off vapors until flares could be installed. 24 hour security and monitoring was initiated. Upon product extraction, line was excavated for observation and repair methodology. Open hole inspection revealed no evidence of corrosion. Coal tar coating was found to be bonded and in very good condition. Recent ili data revealed the nearest anomaly (56 % metal loss) at 1636 feet downstream of the leak. A small pinhole was observed with surrounding coating blown away. The pinhole was surrounded by a half inch diameter pit with very shiny metal flow away from the pit. A very recent extreme source of heat and rapid cooling was determined to be the source. Due to a lightening storm reported in the area at the time of the incident, a lightening strike was considered as the most likely source. A decision was made to replace 13.5 feet of pipe. Metalurgical analysis in progress.

All rights reserved. Copyright © by ClearPHMSA