HL incident on 2017-04-06 — TX

Operator
Kinder Morgan Liquid Terminals, Llc
Cause
Material Failure Of Pipe Or Weld
Commodity
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$120,000
Incident datetime
2017-04-06 11:15
Report number
Location
TX
Narrative
Staining found around tank 293 where previous long term remediation was occurring lead to investigation of tank. Km made the decision to evaluate tank soil sample which still only indicated historical contamination. As a precaution tank was taken out of service where tank floor was scanned and vacuum tested. The vacuum test revealed a pinhole in a corner weld between the tank floor and the shell. Repairs are on going. Tank API 653 inspection is complete and will be brought back into service in q2 2018. Predicted final cost is $125,000 but if cost is to exceed a supplemental report will be submitted.
Detailed record list
Report Received Date
2017-08-04 00:00:00
Iyear
2017
Report Number
20170236
Supplemental Number
23100
Report Type
Supplemental Final
Operator Id
Name
Kinder Morgan Liquid Terminals, Llc
Operator Street Address
1001 Louisiana St, Suite 1000
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2017-04-06 11:15:00
Location Latitude
Location Longitude
Commodity Released Type
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype
Gasoline (Non-Ethanol)
Unintentional Release Bbls
1
Recovered Bbls
1
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2017-04-06 11:15:00
System Part Involved
Onshore Breakout Tank Or Storage Vessel, Including Attached Appurtenances
On Off Shore
Onshore
Shutdown Due Accident Ind
No
Shutdown Explain
Leak Not Verified Until Tank Oos Inspection
On Site Datetime
2017-04-06 11:15:00
Nrc Rpt Datetime
2017-04-06 11:32:00
Nrc Rpt Num
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Kinder Morgan Wood River Terminal
Segment Name
Tank 293
Onshore State Abbreviation
Il
Onshore Postal Code
62048
Onshore City Name
Hartford
Onshore County Name
Madison
Designated Location
Milepost/valve Station
Designated Name
0
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Tank, Including Attached Appurtenances
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Weld, Including Heat-Affected Zone
Weld Subtype
Other
Weld Details
Corner Weld On Tank Floor And Shell
Tank Type
Atmospheric
Installation Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
Yes
Soil Remed Ind
Yes
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
Commercially Nav Ind
Yes
Commercially Nav Yes No
Yes
High Pop Ind
Yes
High Pop Yes No
Yes
Other Pop Ind
Yes
Other Pop Yes No
Yes
Usa Drinking Ind
Yes
Usa Drinking Yes No
Yes
Usa Ecological Ind
Yes
Usa Ecological Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
0
Est Cost Prop Damage
120000
Est Cost Emergency
0
Est Cost Environmental
5000
Est Cost Other
0
Prpty
125000
Accident Psig
49
Mop Psig
285
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
No
Cpm In Place Ind
No
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the accident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Material Failure Of Pipe Or Weld
Cause Details
Design-, Construction-, Installation-, Or Fabrication-Related
Field Exam Ind
Yes
Failure Type
Design-, Construction-, Installation-, Or Fabrication-Related
Other Factor
Yes
Other Factor Details
Porosity
Pwf Additional Other Ind
Yes
Collected Data Ind
Yes
Other Tool Tech Ind
Yes
Other Tool
Floor Scan And Vacuum Box
Other Recent Year
2017
Has Hydrtst Conduc Before Ind
Yes
Hydrtst Most Rcnt Year
-1
Hydrtst Most Rcnt Pressure
-1
Direct Asmnt Conducted
No
Non Destructive Exam Ind
No
Preparer Name
D******* S*******
Preparer Title
Director Of Compliance Codes And Standards
Preparer Email
D****************@k***********.com
Preparer Telephone
7134206496
Preparer Fax
3039843048
Prepared Date
2018-02-05 00:00:00
Authorizer Name
D******* S*******
Authorizer Telephone
7134206496
Authorizer Title
Director Of Compliance Codes And Standards
Authorizer Email
D****************@k***********.com
Narrative
Staining found around tank 293 where previous long term remediation was occurring lead to investigation of tank. Km made the decision to evaluate tank soil sample which still only indicated historical contamination. As a precaution tank was taken out of service where tank floor was scanned and vacuum tested. The vacuum test revealed a pinhole in a corner weld between the tank floor and the shell. Repairs are on going. Tank API 653 inspection is complete and will be brought back into service in q2 2018. Predicted final cost is $125,000 but if cost is to exceed a supplemental report will be submitted.
Report Received Date 2017-08-04 00:00:00
Iyear 2017
Report Number 20170236
Supplemental Number 23100
Report Type Supplemental Final
Operator Id 26041 PHMSA Enforcement
Name Kinder Morgan Liquid Terminals, Llc
Operator Street Address 1001 Louisiana St, Suite 1000
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Local Datetime 2017-04-06 11:15:00
Location Latitude 38.844011 Google Maps OpenStreetMap
Location Longitude -90.085648 Google Maps OpenStreetMap
Commodity Released Type Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype Gasoline (Non-Ethanol)
Unintentional Release Bbls 1
Recovered Bbls 1
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
Incident Identified Datetime 2017-04-06 11:15:00
System Part Involved Onshore Breakout Tank Or Storage Vessel, Including Attached Appurtenances
On Off Shore Onshore
Shutdown Due Accident Ind No
Shutdown Explain Leak Not Verified Until Tank Oos Inspection
On Site Datetime 2017-04-06 11:15:00
Nrc Rpt Datetime 2017-04-06 11:32:00
Nrc Rpt Num 1175000 NRC Report How to search
Ignite Ind No
Explode Ind No
Num Pub Evacuated 0
Pipe Fac Name Kinder Morgan Wood River Terminal
Segment Name Tank 293
Onshore State Abbreviation Il
Onshore Postal Code 62048
Onshore City Name Hartford
Onshore County Name Madison
Designated Location Milepost/valve Station
Designated Name 0
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Tank, Including Attached Appurtenances
Crossing No
Pipe Facility Type Interstate
Item Involved Weld, Including Heat-Affected Zone
Weld Subtype Other
Weld Details Corner Weld On Tank Floor And Shell
Tank Type Atmospheric
Installation Year Unknown
Material Involved Carbon Steel
Release Type Leak
Leak Type Pinhole
Wildlife Impact Ind No
Soil Contamination Yes
Long Term Assessment No
Remediation Ind Yes
Soil Remed Ind Yes
Water Contam Ind No
Could Be Hca Yes
Commodity Reached Hca Yes
Commercially Nav Ind Yes
Commercially Nav Yes No Yes
High Pop Ind Yes
High Pop Yes No Yes
Other Pop Ind Yes
Other Pop Yes No Yes
Usa Drinking Ind Yes
Usa Drinking Yes No Yes
Usa Ecological Ind Yes
Usa Ecological Yes No Yes
Est Cost Oper Paid 0
Est Cost Gas Released 0
Est Cost Prop Damage 120000
Est Cost Emergency 0
Est Cost Environmental 5000
Est Cost Other 0
Prpty 125000
Accident Psig 49
Mop Psig 285
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind No
Cpm In Place Ind No
Investigation Status No, the facility was not monitored by a controller(s) at the time of the accident
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Material Failure Of Pipe Or Weld
Cause Details Design-, Construction-, Installation-, Or Fabrication-Related
Field Exam Ind Yes
Failure Type Design-, Construction-, Installation-, Or Fabrication-Related
Other Factor Yes
Other Factor Details Porosity
Pwf Additional Other Ind Yes
Collected Data Ind Yes
Other Tool Tech Ind Yes
Other Tool Floor Scan And Vacuum Box
Other Recent Year 2017
Has Hydrtst Conduc Before Ind Yes
Hydrtst Most Rcnt Year -1
Hydrtst Most Rcnt Pressure -1
Direct Asmnt Conducted No
Non Destructive Exam Ind No
Preparer Name D******* S*******
Preparer Title Director Of Compliance Codes And Standards
Preparer Email D****************@k***********.com
Preparer Telephone 7134206496
Preparer Fax 3039843048
Prepared Date 2018-02-05 00:00:00
Authorizer Name D******* S*******
Authorizer Telephone 7134206496
Authorizer Title Director Of Compliance Codes And Standards
Authorizer Email D****************@k***********.com
Narrative Staining found around tank 293 where previous long term remediation was occurring lead to investigation of tank. Km made the decision to evaluate tank soil sample which still only indicated historical contamination. As a precaution tank was taken out of service where tank floor was scanned and vacuum tested. The vacuum test revealed a pinhole in a corner weld between the tank floor and the shell. Repairs are on going. Tank API 653 inspection is complete and will be brought back into service in q2 2018. Predicted final cost is $125,000 but if cost is to exceed a supplemental report will be submitted.

All rights reserved. Copyright © by ClearPHMSA