Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2017-06-05 — TX
Operator
Enbridge Energy, Limited Partnership
Cause
Incorrect Operation
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$2,599
Incident datetime
2017-06-05 09:00
Report number
Location
TX
Narrative
On june 5, 2017 at 9:00 am local time, two terminal maintainers, while working near the 151 meter manifold at the clearbrook minnesota terminal, discovered oil under the 151 meter manifold on the concrete slab. The oil had migrated from beneath the manifold into the trough system and adjoining sump adjacent to the 151 meter skid. All the oil was contained within the building on the concrete slab and trough system. The oil leaked from the body bleed valve on the prover valve, 151-v-222, which was found to be in the incorrect full open position. It is unknown when the body bleed valve was changed from the closed to open position. The volume out was approximately 32 gallons. The oil has been cleaned up and the valve returned to the closed position. Further investigation revealed that caps were not present on the prover valve block and bleed piping at the time of the release. It has been confirmed on all three metering facilities at the clearbrook minnesota terminal that there are caps on the block and bleed piping for the prover valves. There was no contaminated soil associated with this incident.
Detailed record list
Report Received Date
2017-06-29 00:00:00
Iyear
2017
Report Number
20170205
Supplemental Number
22449
Report Type
Original Final
Operator Id
11169
Name
Enbridge Energy, Limited Partnership
Operator Street Address
915 N Eldridge Parkway, Suite 1100
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77079
Local Datetime
2017-06-05 09:00:00
Location Latitude
47.688752
Location Longitude
-95.412136
Commodity Released Type
Crude Oil
Unintentional Release Bbls
0.76
Recovered Bbls
0.76
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2017-06-05 09:00:00
System Part Involved
Onshore Terminal/tank Farm Equipment And Piping
On Off Shore
Onshore
Shutdown Due Accident Ind
No
Shutdown Explain
No Flow Through The System At The Time Release Was Discovered
On Site Datetime
2017-06-05 09:00:00
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Clearbrook Terminal
Segment Name
151 Meter Manifold
Onshore State Abbreviation
Mn
Onshore Postal Code
56634
Onshore City Name
Clearbrook
Onshore County Name
Clearwater
Designated Location
Milepost/valve Station
Designated Name
909
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Inside A Building
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Valve
Valve Type
Auxiliary Or Other Valve
Installation Year
1992
Material Involved
Carbon Steel
Release Type
Other
Release Type Details
Body Bleed Valve Left In Wrong Position
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
Other Pop Ind
Yes
Other Pop Yes No
Yes
Usa Drinking Ind
Yes
Usa Drinking Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
0
Est Cost Prop Damage
2599
Est Cost Emergency
113
Est Cost Environmental
0
Est Cost Other
0
Prpty
2712
Accident Psig
44
Mop Psig
745
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Pipeline was not operatiang at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Incorrect Operation
Cause Details
Valve Left Or Placed In Wrong Position, But Not Resulting In A Tank, Vessel, Or Sump/separator Overflow Or Facility Overpressure
Operation Type
Valve Left Or Placed In Wrong Position, But Not Resulting In A Tank, Vessel, Or Sump/separator Overflow Or Facility Overpressure
Related Failure Follow Ind
Yes
Category Type
Routine Maintenance
Operator Qualification Ind
Yes
Qualified Individuals
Yes, They Were Qualified For The Task(S)
Preparer Name
S**** S****
Preparer Title
Compliance Analyst
Preparer Email
S**********@e*******.com
Preparer Telephone
715-395-3620
Preparer Fax
715-398-4802
Prepared Date
2017-06-29 00:00:00
Authorizer Name
R** C*******
Authorizer Telephone
715-395-3619
Authorizer Title
Supervisor Us Pipeline Compliance
Authorizer Email
R***********@e*******.com
Narrative
On june 5, 2017 at 9:00 am local time, two terminal maintainers, while working near the 151 meter manifold at the clearbrook minnesota terminal, discovered oil under the 151 meter manifold on the concrete slab. The oil had migrated from beneath the manifold into the trough system and adjoining sump adjacent to the 151 meter skid. All the oil was contained within the building on the concrete slab and trough system. The oil leaked from the body bleed valve on the prover valve, 151-v-222, which was found to be in the incorrect full open position. It is unknown when the body bleed valve was changed from the closed to open position. The volume out was approximately 32 gallons. The oil has been cleaned up and the valve returned to the closed position. Further investigation revealed that caps were not present on the prover valve block and bleed piping at the time of the release. It has been confirmed on all three metering facilities at the clearbrook minnesota terminal that there are caps on the block and bleed piping for the prover valves. There was no contaminated soil associated with this incident.
| Report Received Date | 2017-06-29 00:00:00 |
|---|---|
| Iyear | 2017 |
| Report Number | 20170205 |
| Supplemental Number | 22449 |
| Report Type | Original Final |
| Operator Id | 11169 PHMSA Enforcement |
| Name | Enbridge Energy, Limited Partnership |
| Operator Street Address | 915 N Eldridge Parkway, Suite 1100 |
| Operator City Name | Houston |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77079 |
| Local Datetime | 2017-06-05 09:00:00 |
| Location Latitude | 47.688752 Google Maps OpenStreetMap |
| Location Longitude | -95.412136 Google Maps OpenStreetMap |
| Commodity Released Type | Crude Oil |
| Unintentional Release Bbls | 0.76 |
| Recovered Bbls | 0.76 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Operator Employee |
| Incident Identified Datetime | 2017-06-05 09:00:00 |
| System Part Involved | Onshore Terminal/tank Farm Equipment And Piping |
| On Off Shore | Onshore |
| Shutdown Due Accident Ind | No |
| Shutdown Explain | No Flow Through The System At The Time Release Was Discovered |
| On Site Datetime | 2017-06-05 09:00:00 |
| Nrc Rpt Num | Nrc Notification Not Required NRC Report How to search |
| Ignite Ind | No |
| Explode Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Clearbrook Terminal |
| Segment Name | 151 Meter Manifold |
| Onshore State Abbreviation | Mn |
| Onshore Postal Code | 56634 |
| Onshore City Name | Clearbrook |
| Onshore County Name | Clearwater |
| Designated Location | Milepost/valve Station |
| Designated Name | 909 |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Inside A Building |
| Crossing | No |
| Pipe Facility Type | Interstate |
| Item Involved | Valve |
| Valve Type | Auxiliary Or Other Valve |
| Installation Year | 1992 |
| Material Involved | Carbon Steel |
| Release Type | Other |
| Release Type Details | Body Bleed Valve Left In Wrong Position |
| Wildlife Impact Ind | No |
| Soil Contamination | No |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | Yes |
| Commodity Reached Hca | Yes |
| Other Pop Ind | Yes |
| Other Pop Yes No | Yes |
| Usa Drinking Ind | Yes |
| Usa Drinking Yes No | Yes |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 0 |
| Est Cost Prop Damage | 2599 |
| Est Cost Emergency | 113 |
| Est Cost Environmental | 0 |
| Est Cost Other | 0 |
| Prpty | 2712 |
| Accident Psig | 44 |
| Mop Psig | 745 |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Cpm In Place Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | Pipeline was not operatiang at the time of the incident |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Incorrect Operation |
| Cause Details | Valve Left Or Placed In Wrong Position, But Not Resulting In A Tank, Vessel, Or Sump/separator Overflow Or Facility Overpressure |
| Operation Type | Valve Left Or Placed In Wrong Position, But Not Resulting In A Tank, Vessel, Or Sump/separator Overflow Or Facility Overpressure |
| Related Failure Follow Ind | Yes |
| Category Type | Routine Maintenance |
| Operator Qualification Ind | Yes |
| Qualified Individuals | Yes, They Were Qualified For The Task(S) |
| Preparer Name | S**** S**** |
| Preparer Title | Compliance Analyst |
| Preparer Email | S**********@e*******.com |
| Preparer Telephone | 715-395-3620 |
| Preparer Fax | 715-398-4802 |
| Prepared Date | 2017-06-29 00:00:00 |
| Authorizer Name | R** C******* |
| Authorizer Telephone | 715-395-3619 |
| Authorizer Title | Supervisor Us Pipeline Compliance |
| Authorizer Email | R***********@e*******.com |
| Narrative | On june 5, 2017 at 9:00 am local time, two terminal maintainers, while working near the 151 meter manifold at the clearbrook minnesota terminal, discovered oil under the 151 meter manifold on the concrete slab. The oil had migrated from beneath the manifold into the trough system and adjoining sump adjacent to the 151 meter skid. All the oil was contained within the building on the concrete slab and trough system. The oil leaked from the body bleed valve on the prover valve, 151-v-222, which was found to be in the incorrect full open position. It is unknown when the body bleed valve was changed from the closed to open position. The volume out was approximately 32 gallons. The oil has been cleaned up and the valve returned to the closed position. Further investigation revealed that caps were not present on the prover valve block and bleed piping at the time of the release. It has been confirmed on all three metering facilities at the clearbrook minnesota terminal that there are caps on the block and bleed piping for the prover valves. There was no contaminated soil associated with this incident. |