Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2017-05-02 — TX
Operator
Enterprise Crude Pipeline Llc
Cause
Corrosion Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$53,300
Incident datetime
2017-05-02 03:15
Report number
Location
TX
Narrative
On 05/02/2017 at approximately 03:15 local operating personnel noticed crude oil accumulated on top of the soil near the c15 meter skid. All incoming lines were immediately shut down and isolated until the source could be determined. Hydro-excavation began which identified the source to be a pinhole at the 6 o'clock position on a section of piping associated with the c15 meter skid. At approximately 11:00 on 05/02 a plidco clamp was installed and the meter skid was placed back into service. The permanent repair will be made at a later time. At approximately 0415 it was determined that the clean-up and repair cost would exceed $50,000 and the nrc call was immediately placed. The 48 hour nrc update was made at approximately 09:15 resulting in report number 1177234. Update 07/24/17: the piping has been replaced and the report is now final.
Detailed record list
Report Received Date
2017-05-25 00:00:00
Iyear
2017
Report Number
20170173
Supplemental Number
22651
Report Type
Supplemental Final
Operator Id
30829
Name
Enterprise Crude Pipeline Llc
Operator Street Address
1100 Louisiana Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2017-05-02 03:15:00
Location Latitude
32.016096
Location Longitude
-102.015804
Commodity Released Type
Crude Oil
Unintentional Release Bbls
50
Recovered Bbls
50
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2017-05-02 03:15:00
System Part Involved
Onshore Terminal/tank Farm Equipment And Piping
On Off Shore
Onshore
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2017-05-02 03:15:00
Restart Datetime
2017-05-02 11:40:00
On Site Datetime
2017-05-02 03:15:00
Nrc Rpt Datetime
2017-05-02 04:27:00
Nrc Rpt Num
1177201
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Midland Station
Segment Name
C15 Meter Bank Piping
Onshore State Abbreviation
Tx
Onshore Postal Code
79706
Onshore City Name
Midland
Onshore County Name
Midland
Designated Location
Milepost/valve Station
Designated Name
Midland Sta.
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
36
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Pipe
Pipe Type
Pipe Body
Pipe Diameter
6
Pipe Wall Thickness
0.25
Pipe Smys
24000
Pipe Specification
5l
Pipe Seam Type
Erw - High Frequency
Pipe Manufacturer
Unknown
Pipe Coating Type
Fusion Bonded Epoxy(Fbe)
Installation Year
1980
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
2250
Est Cost Prop Damage
53300
Est Cost Emergency
12000
Est Cost Environmental
0
Est Cost Other
0
Prpty
67550
Accident Psig
130
Mop Psig
275
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Controller nor control room were a contributing factor
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
Internal Corrosion
Internal External
Internal Corrosion
Int Visual Exam Results
Localized Pitting
Int Microbiological Ind
Yes
Int Field Exam Basis Ind
Yes
Int Low Point Pipe Loc Ind
Yes
Corrosion Inhibitors
Yes
Corrosion Lining
No
Cleaning Dewatering
No
Corrosion Coupons
Not Applicable - Not Mainline Pipe
Collected Data Ind
No
Has Hydrtst Conduc Before Ind
No
Direct Asmnt Conducted
No
Non Destructive Exam Ind
No
Preparer Name
C**** A******
Preparer Title
Pipeline Compliance
Preparer Email
C*******@e****.com
Preparer Telephone
713-381-6426
Prepared Date
2017-09-20 00:00:00
Authorizer Name
C**** A******
Authorizer Telephone
713-381-6426
Authorizer Email
C*******@e****.com
Narrative
On 05/02/2017 at approximately 03:15 local operating personnel noticed crude oil accumulated on top of the soil near the c15 meter skid. All incoming lines were immediately shut down and isolated until the source could be determined. Hydro-excavation began which identified the source to be a pinhole at the 6 o'clock position on a section of piping associated with the c15 meter skid. At approximately 11:00 on 05/02 a plidco clamp was installed and the meter skid was placed back into service. The permanent repair will be made at a later time. At approximately 0415 it was determined that the clean-up and repair cost would exceed $50,000 and the nrc call was immediately placed. The 48 hour nrc update was made at approximately 09:15 resulting in report number 1177234. Update 07/24/17: the piping has been replaced and the report is now final.
| Report Received Date | 2017-05-25 00:00:00 |
|---|---|
| Iyear | 2017 |
| Report Number | 20170173 |
| Supplemental Number | 22651 |
| Report Type | Supplemental Final |
| Operator Id | 30829 PHMSA Enforcement |
| Name | Enterprise Crude Pipeline Llc |
| Operator Street Address | 1100 Louisiana Street |
| Operator City Name | Houston |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77002 |
| Local Datetime | 2017-05-02 03:15:00 |
| Location Latitude | 32.016096 Google Maps OpenStreetMap |
| Location Longitude | -102.015804 Google Maps OpenStreetMap |
| Commodity Released Type | Crude Oil |
| Unintentional Release Bbls | 50 |
| Recovered Bbls | 50 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Operator Employee |
| Incident Identified Datetime | 2017-05-02 03:15:00 |
| System Part Involved | Onshore Terminal/tank Farm Equipment And Piping |
| On Off Shore | Onshore |
| Shutdown Due Accident Ind | Yes |
| Shutdown Datetime | 2017-05-02 03:15:00 |
| Restart Datetime | 2017-05-02 11:40:00 |
| On Site Datetime | 2017-05-02 03:15:00 |
| Nrc Rpt Datetime | 2017-05-02 04:27:00 |
| Nrc Rpt Num | 1177201 NRC Report How to search |
| Ignite Ind | No |
| Explode Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Midland Station |
| Segment Name | C15 Meter Bank Piping |
| Onshore State Abbreviation | Tx |
| Onshore Postal Code | 79706 |
| Onshore City Name | Midland |
| Onshore County Name | Midland |
| Designated Location | Milepost/valve Station |
| Designated Name | Midland Sta. |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Underground |
| Incident Area Subtype | Under Soil |
| Depth Of Cover | 36 |
| Crossing | No |
| Pipe Facility Type | Interstate |
| Item Involved | Pipe |
| Pipe Type | Pipe Body |
| Pipe Diameter | 6 |
| Pipe Wall Thickness | 0.25 |
| Pipe Smys | 24000 |
| Pipe Specification | 5l |
| Pipe Seam Type | Erw - High Frequency |
| Pipe Manufacturer | Unknown |
| Pipe Coating Type | Fusion Bonded Epoxy(Fbe) |
| Installation Year | 1980 |
| Manufactured Year | Unknown |
| Material Involved | Carbon Steel |
| Release Type | Leak |
| Leak Type | Pinhole |
| Wildlife Impact Ind | No |
| Soil Contamination | Yes |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | No |
| Commodity Reached Hca | No |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 2250 |
| Est Cost Prop Damage | 53300 |
| Est Cost Emergency | 12000 |
| Est Cost Environmental | 0 |
| Est Cost Other | 0 |
| Prpty | 67550 |
| Accident Psig | 130 |
| Mop Psig | 275 |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Cpm In Place Ind | Yes |
| Cpm Operating Ind | Yes |
| Cpm Functional Ind | Yes |
| Cpm Detection Ind | No |
| Cpm Conf Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | Controller nor control room were a contributing factor |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Corrosion Failure |
| Cause Details | Internal Corrosion |
| Internal External | Internal Corrosion |
| Int Visual Exam Results | Localized Pitting |
| Int Microbiological Ind | Yes |
| Int Field Exam Basis Ind | Yes |
| Int Low Point Pipe Loc Ind | Yes |
| Corrosion Inhibitors | Yes |
| Corrosion Lining | No |
| Cleaning Dewatering | No |
| Corrosion Coupons | Not Applicable - Not Mainline Pipe |
| Collected Data Ind | No |
| Has Hydrtst Conduc Before Ind | No |
| Direct Asmnt Conducted | No |
| Non Destructive Exam Ind | No |
| Preparer Name | C**** A****** |
| Preparer Title | Pipeline Compliance |
| Preparer Email | C*******@e****.com |
| Preparer Telephone | 713-381-6426 |
| Prepared Date | 2017-09-20 00:00:00 |
| Authorizer Name | C**** A****** |
| Authorizer Telephone | 713-381-6426 |
| Authorizer Email | C*******@e****.com |
| Narrative | On 05/02/2017 at approximately 03:15 local operating personnel noticed crude oil accumulated on top of the soil near the c15 meter skid. All incoming lines were immediately shut down and isolated until the source could be determined. Hydro-excavation began which identified the source to be a pinhole at the 6 o'clock position on a section of piping associated with the c15 meter skid. At approximately 11:00 on 05/02 a plidco clamp was installed and the meter skid was placed back into service. The permanent repair will be made at a later time. At approximately 0415 it was determined that the clean-up and repair cost would exceed $50,000 and the nrc call was immediately placed. The 48 hour nrc update was made at approximately 09:15 resulting in report number 1177234. Update 07/24/17: the piping has been replaced and the report is now final. |
External Resources