HL incident on 2017-04-01 — TX
Operator
Sunoco Pipeline L.p.
Cause
Corrosion Failure
Commodity
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$107,418
Incident datetime
2017-04-01 15:57
Report number
Location
TX
Narrative
On april 1, 2017 at 15:57, a call was received by the sunoco pipeline lp (splp) control center via the company emergency number from a landowner reporting a possible leak along the pipeline row at 5530 morgantown rd, morgantown, pa. Internal notifications were made and splp field personnel were immediately dispatched to the field to investigate. Field personnel arrived onsite at approximately 17:00 and confirmation of the release was made at approximately 17:04. Nrc notification was made at 17:59 (report 1174615) that same day. Required follow up report to nrc was made on april 3, 2017 at 15:46 (report 1174748) updating the volume released to 20bbls and also providing updated coordinates of the release location. The pipeline was shut down and the affected area was isolated via upstream and downstream mainline valves. Product was displaced and the isolated segment was nitrogen purged. Subsequent excavation revealed the source of the leak as an external corrosion pinhole. The affected section of piping was cut out and replaced and the failed section was sent to a 3rd party laboratory for failure analysis. Failure analysis indicated that the leak occurred at the bottom of the pipe at an area of external corrosion coincident with the heat affected zone of a girth weld. The failure analysis confirmed the cause as external corrosion and indicated that microbiologically induced corrosion (mic) may have contributed to the observed external corrosion.
Detailed record list
Report Received Date
2017-04-26 00:00:00
Iyear
2017
Report Number
20170138
Supplemental Number
30259
Report Type
Supplemental Final
Operator Id
18718
Name
Sunoco Pipeline L.p.
Operator Street Address
1300 Main Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2017-04-01 15:57:00
Location Latitude
40.17774
Location Longitude
-75.87633
Commodity Released Type
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype
Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid)
Unintentional Release Bbls
20
Intentional Release Bbls
4.8
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Notification From Public
Incident Identified Datetime
2017-04-01 15:57:00
System Part Involved
Onshore Pipeline, Including Valve Sites
On Off Shore
Onshore
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2017-04-01 18:32:00
Restart Datetime
2017-04-06 20:12:00
On Site Datetime
2017-04-01 17:00:00
Nrc Rpt Datetime
2017-04-01 17:59:00
Nrc Rpt Num
1174615
Ignite Ind
No
Explode Ind
No
Upstream Valve Type Ind
Remotely Controlled
Downstream Valve Type Ind
Manual
Num Pub Evacuated
0
Pipe Fac Name
8" Twin Oaks-Montello
Segment Name
11190 Twin-Mntl-8
Onshore State Abbreviation
Pa
Onshore Postal Code
19543
Onshore City Name
Morgantown
Onshore County Name
Berks
Designated Location
Survey Station No.
Designated Name
2449+12
Federal
No
Location Type
Pipeline Right-Of-Way
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
29
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Weld, Including Heat-Affected Zone
Pipe Diameter
8
Pipe Wall Thickness
0.312
Pipe Smys
35000
Pipe Specification
Grade B
Pipe Seam Type
Seamless
Pipe Manufacturer
National Tube
Pipe Coating Type
None
Weld Subtype
Pipe Girth Weld
Installation Year
1931
Manufactured Year
1931
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
Other Pop Ind
Yes
Other Pop Yes No
Yes
Usa Ecological Ind
Yes
Usa Ecological Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
205
Est Cost Prop Damage
107418
Est Cost Emergency
150239
Est Cost Environmental
0
Est Cost Other
42968
Est Cost Other Details
Metallurgical Analysis
Prpty
300830
Accident Psig
1247
Mop Psig
1480
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Length Segment Isolated
37329
Internal Inspection Ind
Yes
Operation Complications Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
A review of the accident determined that there were no control room actions that contributed to the event.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
External Corrosion
Internal External
External Corrosion
Visual Exam Results
Localized Pitting
Galvanic Corrosion Ind
Yes
Microbiological Corrosion Ind
Yes
Other Corrosion Ind
Yes
Corrosion Type Details
Metallurgical Analysis Indicated That Mic May Have Been A Contributing Factor To The Observed External Corrosion.
Field Exam Basis Ind
Yes
Metallurgical Basis Ind
Yes
Underground Location
Yes
Under Cathodic Protection Ind
Yes
Cathodic Pro Start Year
1964
Shielding Evident
No
Cathodic Survey Type
Yes
Cp Annual Survey Ind
Yes
Close Interval Survey Ind
Yes
Cp Annual Survey Year
2017
Close Interval Survey Year
2017
Prior Damage
No
Collected Data Ind
Yes
Axial Magnetic Flx Lkg Ind
Yes
Geometry Deformation Ind
Yes
Emat Ind
Yes
Axial Recent Year
2017
Geometry Recent Year
2017
Emat Recent Year
2013
Has Hydrtst Conduc Before Ind
Yes
Hydrtst Most Rcnt Year
2014
Hydrtst Most Rcnt Pressure
2072
Direct Asmnt Conducted
No
Non Destructive Exam Ind
No
Preparer Name
T*** G* N*******
Preparer Title
Dot Compliance Sr. Manager
Preparer Email
T*********@s**************.com
Preparer Telephone
281-637-6576
Preparer Fax
877-917-0448
Prepared Date
2018-05-01 00:00:00
Authorizer Name
T*** G* N*******
Authorizer Telephone
281-637-6576
Authorizer Title
Dot Compliance Sr. Manager
Authorizer Email
T*********@s**************.com
Narrative
On april 1, 2017 at 15:57, a call was received by the sunoco pipeline lp (splp) control center via the company emergency number from a landowner reporting a possible leak along the pipeline row at 5530 morgantown rd, morgantown, pa. Internal notifications were made and splp field personnel were immediately dispatched to the field to investigate. Field personnel arrived onsite at approximately 17:00 and confirmation of the release was made at approximately 17:04. Nrc notification was made at 17:59 (report 1174615) that same day. Required follow up report to nrc was made on april 3, 2017 at 15:46 (report 1174748) updating the volume released to 20bbls and also providing updated coordinates of the release location. The pipeline was shut down and the affected area was isolated via upstream and downstream mainline valves. Product was displaced and the isolated segment was nitrogen purged. Subsequent excavation revealed the source of the leak as an external corrosion pinhole. The affected section of piping was cut out and replaced and the failed section was sent to a 3rd party laboratory for failure analysis. Failure analysis indicated that the leak occurred at the bottom of the pipe at an area of external corrosion coincident with the heat affected zone of a girth weld. The failure analysis confirmed the cause as external corrosion and indicated that microbiologically induced corrosion (mic) may have contributed to the observed external corrosion.
| Report Received Date | 2017-04-26 00:00:00 |
|---|---|
| Iyear | 2017 |
| Report Number | 20170138 |
| Supplemental Number | 30259 |
| Report Type | Supplemental Final |
| Operator Id | 18718 PHMSA Enforcement |
| Name | Sunoco Pipeline L.p. |
| Operator Street Address | 1300 Main Street |
| Operator City Name | Houston |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77002 |
| Local Datetime | 2017-04-01 15:57:00 |
| Location Latitude | 40.17774 Google Maps OpenStreetMap |
| Location Longitude | -75.87633 Google Maps OpenStreetMap |
| Commodity Released Type | Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions |
| Commodity Subtype | Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid) |
| Unintentional Release Bbls | 20 |
| Intentional Release Bbls | 4.8 |
| Recovered Bbls | 0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Notification From Public |
| Incident Identified Datetime | 2017-04-01 15:57:00 |
| System Part Involved | Onshore Pipeline, Including Valve Sites |
| On Off Shore | Onshore |
| Shutdown Due Accident Ind | Yes |
| Shutdown Datetime | 2017-04-01 18:32:00 |
| Restart Datetime | 2017-04-06 20:12:00 |
| On Site Datetime | 2017-04-01 17:00:00 |
| Nrc Rpt Datetime | 2017-04-01 17:59:00 |
| Nrc Rpt Num | 1174615 NRC Report How to search |
| Ignite Ind | No |
| Explode Ind | No |
| Upstream Valve Type Ind | Remotely Controlled |
| Downstream Valve Type Ind | Manual |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | 8" Twin Oaks-Montello |
| Segment Name | 11190 Twin-Mntl-8 |
| Onshore State Abbreviation | Pa |
| Onshore Postal Code | 19543 |
| Onshore City Name | Morgantown |
| Onshore County Name | Berks |
| Designated Location | Survey Station No. |
| Designated Name | 2449+12 |
| Federal | No |
| Location Type | Pipeline Right-Of-Way |
| Incident Area Type | Underground |
| Incident Area Subtype | Under Soil |
| Depth Of Cover | 29 |
| Crossing | No |
| Pipe Facility Type | Interstate |
| Item Involved | Weld, Including Heat-Affected Zone |
| Pipe Diameter | 8 |
| Pipe Wall Thickness | 0.312 |
| Pipe Smys | 35000 |
| Pipe Specification | Grade B |
| Pipe Seam Type | Seamless |
| Pipe Manufacturer | National Tube |
| Pipe Coating Type | None |
| Weld Subtype | Pipe Girth Weld |
| Installation Year | 1931 |
| Manufactured Year | 1931 |
| Material Involved | Carbon Steel |
| Release Type | Leak |
| Leak Type | Pinhole |
| Wildlife Impact Ind | No |
| Soil Contamination | No |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | Yes |
| Commodity Reached Hca | Yes |
| Other Pop Ind | Yes |
| Other Pop Yes No | Yes |
| Usa Ecological Ind | Yes |
| Usa Ecological Yes No | Yes |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 205 |
| Est Cost Prop Damage | 107418 |
| Est Cost Emergency | 150239 |
| Est Cost Environmental | 0 |
| Est Cost Other | 42968 |
| Est Cost Other Details | Metallurgical Analysis |
| Prpty | 300830 |
| Accident Psig | 1247 |
| Mop Psig | 1480 |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Length Segment Isolated | 37329 |
| Internal Inspection Ind | Yes |
| Operation Complications Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Cpm In Place Ind | Yes |
| Cpm Operating Ind | Yes |
| Cpm Functional Ind | Yes |
| Cpm Detection Ind | No |
| Cpm Conf Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | A review of the accident determined that there were no control room actions that contributed to the event. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Corrosion Failure |
| Cause Details | External Corrosion |
| Internal External | External Corrosion |
| Visual Exam Results | Localized Pitting |
| Galvanic Corrosion Ind | Yes |
| Microbiological Corrosion Ind | Yes |
| Other Corrosion Ind | Yes |
| Corrosion Type Details | Metallurgical Analysis Indicated That Mic May Have Been A Contributing Factor To The Observed External Corrosion. |
| Field Exam Basis Ind | Yes |
| Metallurgical Basis Ind | Yes |
| Underground Location | Yes |
| Under Cathodic Protection Ind | Yes |
| Cathodic Pro Start Year | 1964 |
| Shielding Evident | No |
| Cathodic Survey Type | Yes |
| Cp Annual Survey Ind | Yes |
| Close Interval Survey Ind | Yes |
| Cp Annual Survey Year | 2017 |
| Close Interval Survey Year | 2017 |
| Prior Damage | No |
| Collected Data Ind | Yes |
| Axial Magnetic Flx Lkg Ind | Yes |
| Geometry Deformation Ind | Yes |
| Emat Ind | Yes |
| Axial Recent Year | 2017 |
| Geometry Recent Year | 2017 |
| Emat Recent Year | 2013 |
| Has Hydrtst Conduc Before Ind | Yes |
| Hydrtst Most Rcnt Year | 2014 |
| Hydrtst Most Rcnt Pressure | 2072 |
| Direct Asmnt Conducted | No |
| Non Destructive Exam Ind | No |
| Preparer Name | T*** G* N******* |
| Preparer Title | Dot Compliance Sr. Manager |
| Preparer Email | T*********@s**************.com |
| Preparer Telephone | 281-637-6576 |
| Preparer Fax | 877-917-0448 |
| Prepared Date | 2018-05-01 00:00:00 |
| Authorizer Name | T*** G* N******* |
| Authorizer Telephone | 281-637-6576 |
| Authorizer Title | Dot Compliance Sr. Manager |
| Authorizer Email | T*********@s**************.com |
| Narrative | On april 1, 2017 at 15:57, a call was received by the sunoco pipeline lp (splp) control center via the company emergency number from a landowner reporting a possible leak along the pipeline row at 5530 morgantown rd, morgantown, pa. Internal notifications were made and splp field personnel were immediately dispatched to the field to investigate. Field personnel arrived onsite at approximately 17:00 and confirmation of the release was made at approximately 17:04. Nrc notification was made at 17:59 (report 1174615) that same day. Required follow up report to nrc was made on april 3, 2017 at 15:46 (report 1174748) updating the volume released to 20bbls and also providing updated coordinates of the release location. The pipeline was shut down and the affected area was isolated via upstream and downstream mainline valves. Product was displaced and the isolated segment was nitrogen purged. Subsequent excavation revealed the source of the leak as an external corrosion pinhole. The affected section of piping was cut out and replaced and the failed section was sent to a 3rd party laboratory for failure analysis. Failure analysis indicated that the leak occurred at the bottom of the pipe at an area of external corrosion coincident with the heat affected zone of a girth weld. The failure analysis confirmed the cause as external corrosion and indicated that microbiologically induced corrosion (mic) may have contributed to the observed external corrosion. |