GD incident on 2017-09-30 — MI
Operator
Consumers Energy Co
Cause
Equipment Failure
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$0
Incident datetime
2017-09-30 07:32
Report number
Location
MI, CLINTON
Narrative
At 07:32 am on september 30, 2017 consumers energy gas control received a high-high alarm on the outlet pressure at lansing city gate, airport rd, located at 13698 s. Airport rd, lansing mi (clinton county). This alarm is set to 400 psi, which is the maop of outlet of the facility. The highest pressure recorded was 500 psig, however that is the upper limit of the transducer so pressure may have been higher than 500 psig. Consumers energy personnel arrived onside at approximately 08:15. It was found that with the release of natural gas through the relief valve, an oil-like substance was also released. This substance affected 3 homes and a farmers field nearby. Lab analysis has determined this substance was comprised of mid-range and heavy hydrocarbons. The facility was operating properly on the secondary run when personnel arrived within normal operating pressures. The regulator failure was caused by an influx of hydrocarbons affecting the function of the regulators. Consumers energy crew rebuilt the primary and secondary run regulators and pilots at the city gate and re-tested the relief valve. Additional personnel completed leak survey and found no leaks. Personnel also checked surrounding regulator stations and all were found to be operating correctly. All work was completed by 19:15 on september 30, 2017. Consumers energy has been working with a third-party contractor for environmental cleanup. The deq was notified at 13:00 on september 30, 2017. Environmental cleanup has been completed. After lab analysis and investigation, the cause/source of the hydrocarbons is believed to be a result of free liquids from storage fields, and liquids not recovered in pigging operations. Consumers energy has provided these sources and affiliated action plans to the mpsc.
Detailed record list
Occurred At
2017-09-30 07:32:00
Year
2017
Report Received Date
2017-10-30 00:00:00
Iyear
2017.0
Report Number
20170096.0
Supplemental Number
16726.0
Report Type
Supplemental Final
Operator Id
2748
Name
Consumers Energy Co
Operator Street Address
One Energy Plaza
Operator City Name
Jackson
Operator State Abbreviation
MI
Operator Postal Code
49201
Local Datetime
2017-09-30 07:32:00
Location Street Address
13698 S. Airport Rd
Location City Name
Lansing
Location County Name
Clinton
Location State Abbreviation
MI
Location Postal Code
48906
Location Latitude
42.8178
Location Longitude
-84.6056
Nrc Rpt Datetime
2017-10-01 10:07:00
Nrc Rpt Num
1191994
Commodity Released Type
Natural Gas
Unintentional Release
422.0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
6.0
Incident Identified Datetime
2017-09-30 07:32:00
On Site Datetime
2017-09-30 08:15:00
Federal
No
Location Type
Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance (E.g. Value Or Regulator Station, Outdoor Meter Set)
Crossing
No
Pipe Facility Type
Privately Owned
System Part Involved
District Regulator/metering Station
Installation Year
2015.0
Material Involved
Steel
Steel Seam Type
Other
Steel Seam Type Details
Unknown
Release Type
Other
Release Type Details
Relief Valve Caused By Overpressure
Class Location Type
Class 3 Location
Est Cost Oper Paid
120000.0
Est Cost Prop Damage
0.0
Est Cost Emergency
3800.0
Est Cost Other
0.0
Est Cost Unintentional Release
1215.0
Prpty
125015.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
0.0
Accident Psig
500.0
Normal Psig
393.0
Mop Psig
400.0
Accident Pressure
Pressure Exceeded The Applicable Allowance In 192.201
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Accident Identifier
Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Controllers performed as expected and reported alarms immediately upon receipt
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Malfunction Of Control/relief Equipment
Eq Failure Type
Malfunction Of Control/relief Equipment
Pressure Regulator Ind
Yes
Preparer Name
K**** M******
Preparer Title
G Engineer Ii
Preparer Email
K************@c********.com
Preparer Telephone
9892954218
Authorizer Name
J**** P****
Authorizer Title
Senior Engineering Technical Analyst Lead
Authorizer Telephone
9897915749
Authorizer Email
J**********@c********.com
Narrative
At 07:32 am on september 30, 2017 consumers energy gas control received a high-high alarm on the outlet pressure at lansing city gate, airport rd, located at 13698 s. Airport rd, lansing mi (clinton county). This alarm is set to 400 psi, which is the maop of outlet of the facility. The highest pressure recorded was 500 psig, however that is the upper limit of the transducer so pressure may have been higher than 500 psig. Consumers energy personnel arrived onside at approximately 08:15. It was found that with the release of natural gas through the relief valve, an oil-like substance was also released. This substance affected 3 homes and a farmers field nearby. Lab analysis has determined this substance was comprised of mid-range and heavy hydrocarbons. The facility was operating properly on the secondary run when personnel arrived within normal operating pressures. The regulator failure was caused by an influx of hydrocarbons affecting the function of the regulators. Consumers energy crew rebuilt the primary and secondary run regulators and pilots at the city gate and re-tested the relief valve. Additional personnel completed leak survey and found no leaks. Personnel also checked surrounding regulator stations and all were found to be operating correctly. All work was completed by 19:15 on september 30, 2017. Consumers energy has been working with a third-party contractor for environmental cleanup. The deq was notified at 13:00 on september 30, 2017. Environmental cleanup has been completed. After lab analysis and investigation, the cause/source of the hydrocarbons is believed to be a result of free liquids from storage fields, and liquids not recovered in pigging operations. Consumers energy has provided these sources and affiliated action plans to the mpsc.
| Occurred At | 2017-09-30 07:32:00 |
|---|---|
| Year | 2017 |
| Report Received Date | 2017-10-30 00:00:00 |
| Iyear | 2017.0 |
| Report Number | 20170096.0 |
| Supplemental Number | 16726.0 |
| Report Type | Supplemental Final |
| Operator Id | 2748 PHMSA Enforcement |
| Name | Consumers Energy Co |
| Operator Street Address | One Energy Plaza |
| Operator City Name | Jackson |
| Operator State Abbreviation | MI |
| Operator Postal Code | 49201 |
| Local Datetime | 2017-09-30 07:32:00 |
| Location Street Address | 13698 S. Airport Rd |
| Location City Name | Lansing |
| Location County Name | Clinton |
| Location State Abbreviation | MI |
| Location Postal Code | 48906 |
| Location Latitude | 42.8178 Google Maps OpenStreetMap |
| Location Longitude | -84.6056 Google Maps OpenStreetMap |
| Nrc Rpt Datetime | 2017-10-01 10:07:00 |
| Nrc Rpt Num | 1191994 NRC Report How to search |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 422.0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Ignite Ind | No |
| Explode Ind | No |
| Num Pub Evacuated | 6.0 |
| Incident Identified Datetime | 2017-09-30 07:32:00 |
| On Site Datetime | 2017-09-30 08:15:00 |
| Federal | No |
| Location Type | Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance (E.g. Value Or Regulator Station, Outdoor Meter Set) |
| Crossing | No |
| Pipe Facility Type | Privately Owned |
| System Part Involved | District Regulator/metering Station |
| Installation Year | 2015.0 |
| Material Involved | Steel |
| Steel Seam Type | Other |
| Steel Seam Type Details | Unknown |
| Release Type | Other |
| Release Type Details | Relief Valve Caused By Overpressure |
| Class Location Type | Class 3 Location |
| Est Cost Oper Paid | 120000.0 |
| Est Cost Prop Damage | 0.0 |
| Est Cost Emergency | 3800.0 |
| Est Cost Other | 0.0 |
| Est Cost Unintentional Release | 1215.0 |
| Prpty | 125015.0 |
| Commercial Affected | 0.0 |
| Industrial Affected | 0.0 |
| Residences Affected | 0.0 |
| Accident Psig | 500.0 |
| Normal Psig | 393.0 |
| Mop Psig | 400.0 |
| Accident Pressure | Pressure Exceeded The Applicable Allowance In 192.201 |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | Yes |
| Scada Conf Ind | Yes |
| Accident Identifier | Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations) |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | Controllers performed as expected and reported alarms immediately upon receipt |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Equipment Failure |
| Cause Details | Malfunction Of Control/relief Equipment |
| Eq Failure Type | Malfunction Of Control/relief Equipment |
| Pressure Regulator Ind | Yes |
| Preparer Name | K**** M****** |
| Preparer Title | G Engineer Ii |
| Preparer Email | K************@c********.com |
| Preparer Telephone | 9892954218 |
| Authorizer Name | J**** P**** |
| Authorizer Title | Senior Engineering Technical Analyst Lead |
| Authorizer Telephone | 9897915749 |
| Authorizer Email | J**********@c********.com |
| Narrative | At 07:32 am on september 30, 2017 consumers energy gas control received a high-high alarm on the outlet pressure at lansing city gate, airport rd, located at 13698 s. Airport rd, lansing mi (clinton county). This alarm is set to 400 psi, which is the maop of outlet of the facility. The highest pressure recorded was 500 psig, however that is the upper limit of the transducer so pressure may have been higher than 500 psig. Consumers energy personnel arrived onside at approximately 08:15. It was found that with the release of natural gas through the relief valve, an oil-like substance was also released. This substance affected 3 homes and a farmers field nearby. Lab analysis has determined this substance was comprised of mid-range and heavy hydrocarbons. The facility was operating properly on the secondary run when personnel arrived within normal operating pressures. The regulator failure was caused by an influx of hydrocarbons affecting the function of the regulators. Consumers energy crew rebuilt the primary and secondary run regulators and pilots at the city gate and re-tested the relief valve. Additional personnel completed leak survey and found no leaks. Personnel also checked surrounding regulator stations and all were found to be operating correctly. All work was completed by 19:15 on september 30, 2017. Consumers energy has been working with a third-party contractor for environmental cleanup. The deq was notified at 13:00 on september 30, 2017. Environmental cleanup has been completed. After lab analysis and investigation, the cause/source of the hydrocarbons is believed to be a result of free liquids from storage fields, and liquids not recovered in pigging operations. Consumers energy has provided these sources and affiliated action plans to the mpsc. |