GD incident on 2017-01-20 — CA

Operator
Southern California Gas Co
Cause
Pipe, Weld, Or Joint Failure
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities 1 injury
Property damage (nominal)
$40,000
Incident datetime
2017-01-20 15:28
Report number
Location
CA, SAN BERNARDINO
Narrative
On january 20, 2017, at approximately 15:28, socalgas company (scg) was notified of an explosion that occurred at 1748 s. Mountain avenue, unit a, ontario, ca 91762. According to the ontario fire department, an individual went into the garage to smoke a cigarette, and the explosion occurred after he lit a lighter. The individual was transported to arrowhead regional to be treated for his injuries. Scg first responders arrived to the scene and reported gas indications at the msa. Consequently, a step ii leak investigation was conducted successfully. Pressure and lock-up was within tolerance and the meter was hard closed. Underground samples were taken to determine the location of the leak. Leak indications were found at the main to main tie-in, which is approximately 15 ft from the garage where the explosion occurred. After further investigation, the leak was found on a cracked aldyl-a tee fitting at the main to main tie-in. We found a hairline crack approximately 1 1/2 inches long on one of the arms of the 'tee'. The cracked fitting was found underground with other substructures, yet located directly below a concrete electrical box owner by gte. Gte was an old telco company now owned by frontier. The edge of the concrete box, lined up with the location of the crack. The fitting and several feet of pipe were replaced and secured as evidence by the gas company. Updated 3/3/2019 - further investigation showed the identified leak cause was "excessive bending strain". For any further questions, contact khoa le at (626) 893-4536.
Detailed record list
Occurred At
2017-01-20 15:28:00
Year
2017
Report Received Date
2017-02-17 00:00:00
Iyear
2017.0
Report Number
20170020.0
Supplemental Number
31894.0
Report Type
Supplemental Final
Operator Id
Name
Southern California Gas Co
Operator Street Address
555 West Fifth Street
Operator City Name
Los Angeles
Operator State Abbreviation
CA
Operator Postal Code
90013
Local Datetime
2017-01-20 15:28:00
Location Street Address
1748 S Mountain Ave
Location City Name
Ontario
Location County Name
San Bernardino
Location State Abbreviation
CA
Location Postal Code
91762
Location Latitude
Location Longitude
Nrc Rpt Datetime
2017-01-20 17:00:00
Nrc Rpt Num
Commodity Released Type
Natural Gas
Unintentional Release
0.0
Fatality Ind
No
Fatal
0
Injury Ind
Yes
Num Emp Injuries
0
Num Contr Injuries
0
Num Er Injuries
0
Num Worker Injuries
0
Num Gp Injuries
1
Injure
1
Ignite Ind
Yes
Explode Ind
Yes
Num Pub Evacuated
0.0
Incident Identified Datetime
2017-01-20 15:28:00
On Site Datetime
2017-01-20 15:46:00
Federal
No
Location Type
Private Property
Incident Area Type
Underground
Incident Area Subtype
Other
Incident Area Details
Below Concrete Utility Box Located Below
Depth Of Cover
36.0
Crossing
No
Pipe Facility Type
Investor Owned
System Part Involved
Main
Installation Year
1983.0
Pipe Diameter
2.0
Pipe Specification
Unknown
Pipe Manufacturer
Performance Pipe
Material Involved
Plastic
Plastic Type
Polyethylene (Pe)
Wt Plastic Unknown Ind
Unknown
Material Pe Pipe Code
Unknown
Release Type
Leak
Leak Type
Crack
Class Location Type
Class 3 Location
Est Cost Oper Paid
100000.0
Est Cost Prop Damage
40000.0
Est Cost Emergency
200.0
Est Cost Other
0.0
Est Cost Unintentional Release
0.0
Prpty
140200.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
1.0
Accident Psig
45.0
Normal Psig
45.0
Mop Psig
60.0
Accident Pressure
Pressure Did Not Exceed Maop
Scada In Place Ind
No
Accident Identifier
Notification From Public
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Pipe, Weld, Or Joint Failure
Cause Details
Other Pipe, Weld, Or Joint Failure
Pwjf Failure Type
Other Pipe, Weld, Or Joint Failure
Pwjf Failure Details
Cracked Adyla-A
Additional Pipe Bend Ind
Yes
Result Material Ind
Yes
Result Material Subtype
Other
Result Material Details
Excessive Bending Strain
Hydrotest Conducted Ind
Yes
Hydrotest Conducted Year
1983
Hydrotest Pressure
100
Preparer Name
K*** L*
Preparer Title
Pipeline Safety And Compliance Advisor
Preparer Email
K***@s**************.com
Preparer Telephone
626-893-4536
Authorizer Name
K*** L*
Authorizer Title
Pipeline Safety And Compliance Advisor
Authorizer Telephone
626-893-4536
Authorizer Email
K***@s**************.com
Narrative
On january 20, 2017, at approximately 15:28, socalgas company (scg) was notified of an explosion that occurred at 1748 s. Mountain avenue, unit a, ontario, ca 91762. According to the ontario fire department, an individual went into the garage to smoke a cigarette, and the explosion occurred after he lit a lighter. The individual was transported to arrowhead regional to be treated for his injuries. Scg first responders arrived to the scene and reported gas indications at the msa. Consequently, a step ii leak investigation was conducted successfully. Pressure and lock-up was within tolerance and the meter was hard closed. Underground samples were taken to determine the location of the leak. Leak indications were found at the main to main tie-in, which is approximately 15 ft from the garage where the explosion occurred. After further investigation, the leak was found on a cracked aldyl-a tee fitting at the main to main tie-in. We found a hairline crack approximately 1 1/2 inches long on one of the arms of the 'tee'. The cracked fitting was found underground with other substructures, yet located directly below a concrete electrical box owner by gte. Gte was an old telco company now owned by frontier. The edge of the concrete box, lined up with the location of the crack. The fitting and several feet of pipe were replaced and secured as evidence by the gas company. Updated 3/3/2019 - further investigation showed the identified leak cause was "excessive bending strain". For any further questions, contact khoa le at (626) 893-4536.
Occurred At 2017-01-20 15:28:00
Year 2017
Report Received Date 2017-02-17 00:00:00
Iyear 2017.0
Report Number 20170020.0
Supplemental Number 31894.0
Report Type Supplemental Final
Operator Id 18484 PHMSA Enforcement
Name Southern California Gas Co
Operator Street Address 555 West Fifth Street
Operator City Name Los Angeles
Operator State Abbreviation CA
Operator Postal Code 90013
Local Datetime 2017-01-20 15:28:00
Location Street Address 1748 S Mountain Ave
Location City Name Ontario
Location County Name San Bernardino
Location State Abbreviation CA
Location Postal Code 91762
Location Latitude 34.04138 Google Maps OpenStreetMap
Location Longitude -117.67053 Google Maps OpenStreetMap
Nrc Rpt Datetime 2017-01-20 17:00:00
Nrc Rpt Num 1169104 NRC Report How to search
Commodity Released Type Natural Gas
Unintentional Release 0.0
Fatality Ind No
Fatal 0
Injury Ind Yes
Num Emp Injuries 0
Num Contr Injuries 0
Num Er Injuries 0
Num Worker Injuries 0
Num Gp Injuries 1
Injure 1
Ignite Ind Yes
Explode Ind Yes
Num Pub Evacuated 0.0
Incident Identified Datetime 2017-01-20 15:28:00
On Site Datetime 2017-01-20 15:46:00
Federal No
Location Type Private Property
Incident Area Type Underground
Incident Area Subtype Other
Incident Area Details Below Concrete Utility Box Located Below
Depth Of Cover 36.0
Crossing No
Pipe Facility Type Investor Owned
System Part Involved Main
Installation Year 1983.0
Pipe Diameter 2.0
Pipe Specification Unknown
Pipe Manufacturer Performance Pipe
Material Involved Plastic
Plastic Type Polyethylene (Pe)
Wt Plastic Unknown Ind Unknown
Material Pe Pipe Code Unknown
Release Type Leak
Leak Type Crack
Class Location Type Class 3 Location
Est Cost Oper Paid 100000.0
Est Cost Prop Damage 40000.0
Est Cost Emergency 200.0
Est Cost Other 0.0
Est Cost Unintentional Release 0.0
Prpty 140200.0
Commercial Affected 0.0
Industrial Affected 0.0
Residences Affected 1.0
Accident Psig 45.0
Normal Psig 45.0
Mop Psig 60.0
Accident Pressure Pressure Did Not Exceed Maop
Scada In Place Ind No
Accident Identifier Notification From Public
Investigation Status No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Pipe, Weld, Or Joint Failure
Cause Details Other Pipe, Weld, Or Joint Failure
Pwjf Failure Type Other Pipe, Weld, Or Joint Failure
Pwjf Failure Details Cracked Adyla-A
Additional Pipe Bend Ind Yes
Result Material Ind Yes
Result Material Subtype Other
Result Material Details Excessive Bending Strain
Hydrotest Conducted Ind Yes
Hydrotest Conducted Year 1983
Hydrotest Pressure 100
Preparer Name K*** L*
Preparer Title Pipeline Safety And Compliance Advisor
Preparer Email K***@s**************.com
Preparer Telephone 626-893-4536
Authorizer Name K*** L*
Authorizer Title Pipeline Safety And Compliance Advisor
Authorizer Telephone 626-893-4536
Authorizer Email K***@s**************.com
Narrative On january 20, 2017, at approximately 15:28, socalgas company (scg) was notified of an explosion that occurred at 1748 s. Mountain avenue, unit a, ontario, ca 91762. According to the ontario fire department, an individual went into the garage to smoke a cigarette, and the explosion occurred after he lit a lighter. The individual was transported to arrowhead regional to be treated for his injuries. Scg first responders arrived to the scene and reported gas indications at the msa. Consequently, a step ii leak investigation was conducted successfully. Pressure and lock-up was within tolerance and the meter was hard closed. Underground samples were taken to determine the location of the leak. Leak indications were found at the main to main tie-in, which is approximately 15 ft from the garage where the explosion occurred. After further investigation, the leak was found on a cracked aldyl-a tee fitting at the main to main tie-in. We found a hairline crack approximately 1 1/2 inches long on one of the arms of the 'tee'. The cracked fitting was found underground with other substructures, yet located directly below a concrete electrical box owner by gte. Gte was an old telco company now owned by frontier. The edge of the concrete box, lined up with the location of the crack. The fitting and several feet of pipe were replaced and secured as evidence by the gas company. Updated 3/3/2019 - further investigation showed the identified leak cause was "excessive bending strain". For any further questions, contact khoa le at (626) 893-4536.

All rights reserved. Copyright © by ClearPHMSA