Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2016-10-26 — KS
Operator
Jayhawk Pipeline Llc
Cause
Equipment Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$300
Incident datetime
2016-10-26 10:01
Report number
Location
KS
Narrative
At approximately 10:00 a.M. On october 16th, 2016 a local jayhawk pipeline employee arrived on-site to perform normal operating duties and noticed crude oil on the ground in the area of the pump, resulting from packing failure. Local personnel activated the esd (shutting down the pumps and lact unit) and initiated the emergency response. The release was isolated to the immediate vicinity of the pump and the product did not overspray to other areas. Response personnel used a tank truck unit to recover free standing crude oil and jayhawk pipeline personnel placed the 1.2 cubic yards of contaminated soil on the local remediation plot. This pump was permanently removed from service on october 27, 2016 and replaced with a screw style pd pump.
Detailed record list
Report Received Date
2016-12-02 00:00:00
Iyear
2016
Report Number
20160403
Supplemental Number
22140
Report Type
Supplemental Final
Operator Id
9175
Name
Jayhawk Pipeline Llc
Operator Street Address
2000 S. Main
Operator City Name
Mcpherson
Operator State Abbreviation
KS
Operator Postal Code
67460
Local Datetime
2016-10-26 10:01:00
Location Latitude
38.62313
Location Longitude
-98.533921
Commodity Released Type
Crude Oil
Unintentional Release Bbls
1.2
Recovered Bbls
1.2
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2016-10-26 10:01:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2016-10-26 10:01:00
Restart Datetime
2016-10-27 09:11:00
On Site Datetime
2016-10-26 10:01:00
Nrc Rpt Datetime
2016-10-26 10:41:00
Nrc Rpt Num
1162558
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Frees Station
Onshore State Abbreviation
Ks
Onshore Postal Code
67525
Onshore City Name
Clafin
Onshore County Name
Barton
Designated Location
Milepost/valve Station
Designated Name
Frees Station
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Pump
Installation Year
1995
Material Involved
Material Other Than Carbon Steel
Material Details
Pump Packing Failure
Release Type
Leak
Leak Type
Seal Or Packing
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
50
Est Cost Prop Damage
300
Est Cost Emergency
2000
Est Cost Environmental
1200
Est Cost Other
500
Est Cost Other Details
Disposal Of Contaminated Soil
Prpty
4050
Accident Psig
256
Mop Psig
1328
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
< 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Equipment packing failure was cause and was small enough quantity that it did not trigger scada/cpm alarm thresholds for controller actions to have played any role in incident.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Pump Or Pump-Related Equipment
Eq Failure Type
Pump Or Pump-Related Equipment
Other Pump Ind
Seal/packing Failure
Eq Additional Other Ind
Yes
Eq Additional Other Details
No Other Contributing Factors
Preparer Name
M******* S*****
Preparer Title
Manager Dot Compliance
Preparer Email
M**************@c*****.com
Preparer Telephone
4068619284
Preparer Fax
4066285393
Prepared Date
2017-03-02 00:00:00
Authorizer Name
R****** S* P*******
Authorizer Telephone
6202419240
Authorizer Title
V.p. Pipelines And Terminals
Authorizer Email
R***************@c*****.com
Narrative
At approximately 10:00 a.M. On october 16th, 2016 a local jayhawk pipeline employee arrived on-site to perform normal operating duties and noticed crude oil on the ground in the area of the pump, resulting from packing failure. Local personnel activated the esd (shutting down the pumps and lact unit) and initiated the emergency response. The release was isolated to the immediate vicinity of the pump and the product did not overspray to other areas. Response personnel used a tank truck unit to recover free standing crude oil and jayhawk pipeline personnel placed the 1.2 cubic yards of contaminated soil on the local remediation plot. This pump was permanently removed from service on october 27, 2016 and replaced with a screw style pd pump.
| Report Received Date | 2016-12-02 00:00:00 |
|---|---|
| Iyear | 2016 |
| Report Number | 20160403 |
| Supplemental Number | 22140 |
| Report Type | Supplemental Final |
| Operator Id | 9175 PHMSA Enforcement |
| Name | Jayhawk Pipeline Llc |
| Operator Street Address | 2000 S. Main |
| Operator City Name | Mcpherson |
| Operator State Abbreviation | KS |
| Operator Postal Code | 67460 |
| Local Datetime | 2016-10-26 10:01:00 |
| Location Latitude | 38.62313 Google Maps OpenStreetMap |
| Location Longitude | -98.533921 Google Maps OpenStreetMap |
| Commodity Released Type | Crude Oil |
| Unintentional Release Bbls | 1.2 |
| Recovered Bbls | 1.2 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Operator Employee |
| Incident Identified Datetime | 2016-10-26 10:01:00 |
| System Part Involved | Onshore Pump/meter Station Equipment And Piping |
| On Off Shore | Onshore |
| Shutdown Due Accident Ind | Yes |
| Shutdown Datetime | 2016-10-26 10:01:00 |
| Restart Datetime | 2016-10-27 09:11:00 |
| On Site Datetime | 2016-10-26 10:01:00 |
| Nrc Rpt Datetime | 2016-10-26 10:41:00 |
| Nrc Rpt Num | 1162558 NRC Report How to search |
| Ignite Ind | No |
| Explode Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Frees Station |
| Onshore State Abbreviation | Ks |
| Onshore Postal Code | 67525 |
| Onshore City Name | Clafin |
| Onshore County Name | Barton |
| Designated Location | Milepost/valve Station |
| Designated Name | Frees Station |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
| Crossing | No |
| Pipe Facility Type | Interstate |
| Item Involved | Pump |
| Installation Year | 1995 |
| Material Involved | Material Other Than Carbon Steel |
| Material Details | Pump Packing Failure |
| Release Type | Leak |
| Leak Type | Seal Or Packing |
| Wildlife Impact Ind | No |
| Soil Contamination | Yes |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | No |
| Commodity Reached Hca | No |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 50 |
| Est Cost Prop Damage | 300 |
| Est Cost Emergency | 2000 |
| Est Cost Environmental | 1200 |
| Est Cost Other | 500 |
| Est Cost Other Details | Disposal Of Contaminated Soil |
| Prpty | 4050 |
| Accident Psig | 256 |
| Mop Psig | 1328 |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | < 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Cpm In Place Ind | Yes |
| Cpm Operating Ind | Yes |
| Cpm Functional Ind | Yes |
| Cpm Detection Ind | No |
| Cpm Conf Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | Equipment packing failure was cause and was small enough quantity that it did not trigger scada/cpm alarm thresholds for controller actions to have played any role in incident. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Equipment Failure |
| Cause Details | Pump Or Pump-Related Equipment |
| Eq Failure Type | Pump Or Pump-Related Equipment |
| Other Pump Ind | Seal/packing Failure |
| Eq Additional Other Ind | Yes |
| Eq Additional Other Details | No Other Contributing Factors |
| Preparer Name | M******* S***** |
| Preparer Title | Manager Dot Compliance |
| Preparer Email | M**************@c*****.com |
| Preparer Telephone | 4068619284 |
| Preparer Fax | 4066285393 |
| Prepared Date | 2017-03-02 00:00:00 |
| Authorizer Name | R****** S* P******* |
| Authorizer Telephone | 6202419240 |
| Authorizer Title | V.p. Pipelines And Terminals |
| Authorizer Email | R***************@c*****.com |
| Narrative | At approximately 10:00 a.M. On october 16th, 2016 a local jayhawk pipeline employee arrived on-site to perform normal operating duties and noticed crude oil on the ground in the area of the pump, resulting from packing failure. Local personnel activated the esd (shutting down the pumps and lact unit) and initiated the emergency response. The release was isolated to the immediate vicinity of the pump and the product did not overspray to other areas. Response personnel used a tank truck unit to recover free standing crude oil and jayhawk pipeline personnel placed the 1.2 cubic yards of contaminated soil on the local remediation plot. This pump was permanently removed from service on october 27, 2016 and replaced with a screw style pd pump. |