HL incident on 2016-08-16 — TX

Operator
Sunoco Pipeline L.p.
Cause
Equipment Failure
Commodity
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$50
Incident datetime
2016-08-16 20:21
Report number
Location
TX
Narrative
On tuesday, 8/16/2016, a high-high alarm condition triggered a facility lockout at hollidaysburg pump station. Event notification was sent to supervision. Field personnel were dispatched to investigate. Leak was discovered at the receiving pig trap closure. Response included isolation of the pig trap and flaring of the remaining product contained in the pig trap. When purged and made safe to open, the pig trap closure assembly was assessed. Investigation determined the pig trap closure o-ring had failed which was the immediate cause of the release. A new o-ring was installed, leak tested and the pipeline was returned to normal operations.
Detailed record list
Report Received Date
2016-09-13 00:00:00
Iyear
2016
Report Number
20160297
Supplemental Number
21843
Report Type
Supplemental Final
Operator Id
Name
Sunoco Pipeline L.p.
Operator Street Address
1300 Main Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2016-08-16 20:21:00
Location Latitude
Location Longitude
Commodity Released Type
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype
Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid)
Unintentional Release Bbls
5
Intentional Release Bbls
2
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Cpm Leak Detection System Or Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Calculations)
Incident Identified Datetime
2016-08-16 20:21:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2016-08-16 20:22:00
Restart Datetime
2016-08-17 00:15:00
On Site Datetime
2016-08-16 20:53:00
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Holl-Hollidaysburg Pump Station
Segment Name
12124-8" Montello To Delmont
Onshore State Abbreviation
Pa
Onshore Postal Code
16635
Onshore City Name
Allegheny Township
Onshore County Name
Blair
Designated Location
Milepost/valve Station
Designated Name
Hollidaysburg
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Scraper/pig Trap
Installation Year
2015
Material Involved
Material Other Than Carbon Steel
Material Details
Viton O-Ring
Release Type
Leak
Leak Type
Seal Or Packing
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
High Pop Ind
Yes
High Pop Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
150
Est Cost Prop Damage
50
Est Cost Emergency
1375
Est Cost Environmental
0
Est Cost Other
12875
Est Cost Other Details
Failure Analysis
Prpty
14450
Accident Psig
1220
Mop Psig
1480
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
A review of the accident determined that there were no control room actions that contributed to the event.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Non-Threaded Connection Failure
Eq Failure Type
Non-Threaded Connection Failure
Other Non Threaded Ind
O-Ring
Eq Additional Other Ind
Yes
Eq Additional Other Details
O-Ring Failure
Preparer Name
T*** G* N*******
Preparer Title
Dot Compliance Manager
Preparer Email
T*********@s**************.com
Preparer Telephone
281-637-6576
Preparer Fax
877-917-0448
Prepared Date
2016-11-15 00:00:00
Authorizer Name
T*** G* N*******
Authorizer Telephone
281-637-6576
Authorizer Title
Dot Compliance Manager
Authorizer Email
T*********@s**************.com
Narrative
On tuesday, 8/16/2016, a high-high alarm condition triggered a facility lockout at hollidaysburg pump station. Event notification was sent to supervision. Field personnel were dispatched to investigate. Leak was discovered at the receiving pig trap closure. Response included isolation of the pig trap and flaring of the remaining product contained in the pig trap. When purged and made safe to open, the pig trap closure assembly was assessed. Investigation determined the pig trap closure o-ring had failed which was the immediate cause of the release. A new o-ring was installed, leak tested and the pipeline was returned to normal operations.
Report Received Date 2016-09-13 00:00:00
Iyear 2016
Report Number 20160297
Supplemental Number 21843
Report Type Supplemental Final
Operator Id 18718 PHMSA Enforcement
Name Sunoco Pipeline L.p.
Operator Street Address 1300 Main Street
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Local Datetime 2016-08-16 20:21:00
Location Latitude 40.456096 Google Maps OpenStreetMap
Location Longitude -78.402961 Google Maps OpenStreetMap
Commodity Released Type Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid)
Unintentional Release Bbls 5
Intentional Release Bbls 2
Recovered Bbls 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Cpm Leak Detection System Or Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Calculations)
Incident Identified Datetime 2016-08-16 20:21:00
System Part Involved Onshore Pump/meter Station Equipment And Piping
On Off Shore Onshore
Shutdown Due Accident Ind Yes
Shutdown Datetime 2016-08-16 20:22:00
Restart Datetime 2016-08-17 00:15:00
On Site Datetime 2016-08-16 20:53:00
Nrc Rpt Num Nrc Notification Not Required NRC Report How to search
Ignite Ind No
Explode Ind No
Num Pub Evacuated 0
Pipe Fac Name Holl-Hollidaysburg Pump Station
Segment Name 12124-8" Montello To Delmont
Onshore State Abbreviation Pa
Onshore Postal Code 16635
Onshore City Name Allegheny Township
Onshore County Name Blair
Designated Location Milepost/valve Station
Designated Name Hollidaysburg
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Interstate
Item Involved Scraper/pig Trap
Installation Year 2015
Material Involved Material Other Than Carbon Steel
Material Details Viton O-Ring
Release Type Leak
Leak Type Seal Or Packing
Wildlife Impact Ind No
Soil Contamination No
Long Term Assessment No
Remediation Ind No
Water Contam Ind No
Could Be Hca Yes
Commodity Reached Hca Yes
High Pop Ind Yes
High Pop Yes No Yes
Est Cost Oper Paid 0
Est Cost Gas Released 150
Est Cost Prop Damage 50
Est Cost Emergency 1375
Est Cost Environmental 0
Est Cost Other 12875
Est Cost Other Details Failure Analysis
Prpty 14450
Accident Psig 1220
Mop Psig 1480
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind Yes
Scada Conf Ind Yes
Cpm In Place Ind Yes
Cpm Operating Ind Yes
Cpm Functional Ind Yes
Cpm Detection Ind No
Cpm Conf Ind No
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details A review of the accident determined that there were no control room actions that contributed to the event.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Equipment Failure
Cause Details Non-Threaded Connection Failure
Eq Failure Type Non-Threaded Connection Failure
Other Non Threaded Ind O-Ring
Eq Additional Other Ind Yes
Eq Additional Other Details O-Ring Failure
Preparer Name T*** G* N*******
Preparer Title Dot Compliance Manager
Preparer Email T*********@s**************.com
Preparer Telephone 281-637-6576
Preparer Fax 877-917-0448
Prepared Date 2016-11-15 00:00:00
Authorizer Name T*** G* N*******
Authorizer Telephone 281-637-6576
Authorizer Title Dot Compliance Manager
Authorizer Email T*********@s**************.com
Narrative On tuesday, 8/16/2016, a high-high alarm condition triggered a facility lockout at hollidaysburg pump station. Event notification was sent to supervision. Field personnel were dispatched to investigate. Leak was discovered at the receiving pig trap closure. Response included isolation of the pig trap and flaring of the remaining product contained in the pig trap. When purged and made safe to open, the pig trap closure assembly was assessed. Investigation determined the pig trap closure o-ring had failed which was the immediate cause of the release. A new o-ring was installed, leak tested and the pipeline was returned to normal operations.

All rights reserved. Copyright © by ClearPHMSA