GD incident on 2016-10-19 — OR

Operator
Northwest Natural Gas Co
Cause
Notification Issue
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities 1 injury
Property damage (nominal)
$35,000
Incident datetime
2016-10-19 08:51
Report number
Location
OR, MULTNOMAH
Narrative
At approximately 8:51am on october 19, 2016 nw natural received notification of damage to a 1" service line at nw 23rd avenue and glisan street in portland. The service was damaged by loy clark during the course of their excavation for a third party. The natural gas ignited at 9:38am resulting in the loss of a structure at 500/510 nw 23rd avenue. A nw natural first responder arrived on site at 9:10am. Gas was controlled at 9:52am by closing a 2-inch valve located at the intersection of nw 22nd avenue and nw glisan street. Gas service was interrupted to 126 customers. All costs reported in part d are preliminary estimates and will be updated on supplemental reports. Historical perspective: on july 12th 2016, a locate request (ticket 16173103) for installing electric primary and service was called in by loy clark and, was accurately marked by locating inc. For the area where loy clark was excavating on october 19th, 2016. Marks from this ticket were still visible and accurate. On september 12th, 2016, a locate request for replacing telephone and cable tv mainline was called in by loy clark. The locate description for this request was close to, but did not cover, the area where loy clark was excavating on october 19th, 2016. Locate ticket number 16229204. On october 19th, 2016, during the course of excavation on part of the sidewalk on nw glisan within the area covered by the july 12th, 2016 locate, an employee with loy clark pipeline hit the gas service to 500 nw 23rd with a back hoe causing the service line to be pulled out of and separated from the fitting of the dresser valve. The operator did not employ hand tools or other non-invasive methods to determine the exact location of the underground service. Loy clark reported they were performing communication work on october 19th, 2016. The loy clark employees were digging outside of the locate area that had been called in by loy clark for communications work (locate ticket number 16229204).
Detailed record list
Occurred At
2016-10-19 08:51:00
Year
2016
Report Received Date
2016-11-18 00:00:00
Iyear
2016.0
Report Number
20160118.0
Supplemental Number
16728.0
Report Type
Supplemental Final
Operator Id
Name
Northwest Natural Gas Co
Operator Street Address
250 Sw Taylor St
Operator City Name
Portland
Operator State Abbreviation
OR
Operator Postal Code
97204
Local Datetime
2016-10-19 09:38:00
Location Street Address
500 Nw 23rd Ave
Location City Name
Portland
Location County Name
Multnomah
Location State Abbreviation
OR
Location Postal Code
97210-3712
Location Latitude
Location Longitude
Nrc Rpt Datetime
2016-10-19 11:30:00
Nrc Rpt Num
Commodity Released Type
Natural Gas
Unintentional Release
52.0
Fatality Ind
No
Fatal
0
Injury Ind
Yes
Num Emp Injuries
0
Num Contr Injuries
0
Num Er Injuries
1
Num Worker Injuries
0
Num Gp Injuries
0
Injure
1
Ignite Ind
Yes
Explode Ind
Yes
Num Pub Evacuated
50.0
Incident Identified Datetime
2016-10-19 08:51:00
On Site Datetime
2016-10-19 09:10:00
Federal
No
Location Type
Public Property
Incident Area Type
Underground
Incident Area Subtype
Exposed Due To Excavation
Depth Of Cover
30.0
Crossing
No
Pipe Facility Type
Investor Owned
System Part Involved
Service
Installation Year
1985.0
Pipe Diameter
1.0
Pipe Specification
Unknown
Pipe Manufacturer
Unknown
Material Involved
Steel
Wt Steel
0.133
Release Type
Leak
Leak Type
Connection Failure
Class Location Type
Class 3 Location
Est Cost Oper Paid
15000000.0
Est Cost Prop Damage
35000.0
Est Cost Emergency
85000.0
Est Cost Other
0.0
Est Cost Unintentional Release
182.0
Prpty
15120182.0
Commercial Affected
15.0
Industrial Affected
0.0
Residences Affected
111.0
Accident Psig
50.0
Normal Psig
50.0
Mop Psig
57.0
Accident Pressure
Pressure Did Not Exceed Maop
Scada In Place Ind
No
Accident Identifier
Notification From Third Party That Caused The Incident
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
Yes
Num Employees Tested
5
Num Employees Failed
0
Contractor Drug Test Ind
No
Cause
Excavation Damage
Cause Details
Excavation Damage By Third Party
Ex Party Type
Excavation Damage By Third Party
Prior Notification Ind
Yes
One Call System Ind
Yes
Notify Cga Dirt
No
Public Row Ind
Yes
Public Subtype
City Street
Excavator Type
Contractor
Excavator Equipment
Backhoe/trackhoe
Work Performed
Cable Tv
One Call Notified Ind
Yes
One Call Ticket Num
16229204
Locator Type
Contract Locator
Visible Marks
No
Service Interruption
Yes
Service Interruption Hours
32.0
Root Cause Category
Notification Issue
Root Cause Type
No Notification Made To The One-Call Center/811
Preparer Name
J** K*****
Preparer Title
Senior Manager Code Compliance
Preparer Email
J**@n********.com
Preparer Telephone
503-226-4211
Authorizer Name
J* R* G*******
Authorizer Title
Senior Manager Code Compliance
Authorizer Telephone
503-226-4211
Authorizer Email
J**@n********.com
Narrative
At approximately 8:51am on october 19, 2016 nw natural received notification of damage to a 1" service line at nw 23rd avenue and glisan street in portland. The service was damaged by loy clark during the course of their excavation for a third party. The natural gas ignited at 9:38am resulting in the loss of a structure at 500/510 nw 23rd avenue. A nw natural first responder arrived on site at 9:10am. Gas was controlled at 9:52am by closing a 2-inch valve located at the intersection of nw 22nd avenue and nw glisan street. Gas service was interrupted to 126 customers. All costs reported in part d are preliminary estimates and will be updated on supplemental reports. Historical perspective: on july 12th 2016, a locate request (ticket 16173103) for installing electric primary and service was called in by loy clark and, was accurately marked by locating inc. For the area where loy clark was excavating on october 19th, 2016. Marks from this ticket were still visible and accurate. On september 12th, 2016, a locate request for replacing telephone and cable tv mainline was called in by loy clark. The locate description for this request was close to, but did not cover, the area where loy clark was excavating on october 19th, 2016. Locate ticket number 16229204. On october 19th, 2016, during the course of excavation on part of the sidewalk on nw glisan within the area covered by the july 12th, 2016 locate, an employee with loy clark pipeline hit the gas service to 500 nw 23rd with a back hoe causing the service line to be pulled out of and separated from the fitting of the dresser valve. The operator did not employ hand tools or other non-invasive methods to determine the exact location of the underground service. Loy clark reported they were performing communication work on october 19th, 2016. The loy clark employees were digging outside of the locate area that had been called in by loy clark for communications work (locate ticket number 16229204).
Occurred At 2016-10-19 08:51:00
Year 2016
Report Received Date 2016-11-18 00:00:00
Iyear 2016.0
Report Number 20160118.0
Supplemental Number 16728.0
Report Type Supplemental Final
Operator Id 13840 PHMSA Enforcement
Name Northwest Natural Gas Co
Operator Street Address 250 Sw Taylor St
Operator City Name Portland
Operator State Abbreviation OR
Operator Postal Code 97204
Local Datetime 2016-10-19 09:38:00
Location Street Address 500 Nw 23rd Ave
Location City Name Portland
Location County Name Multnomah
Location State Abbreviation OR
Location Postal Code 97210-3712
Location Latitude 45.526403 Google Maps OpenStreetMap
Location Longitude -122.698367 Google Maps OpenStreetMap
Nrc Rpt Datetime 2016-10-19 11:30:00
Nrc Rpt Num 1161960 NRC Report How to search
Commodity Released Type Natural Gas
Unintentional Release 52.0
Fatality Ind No
Fatal 0
Injury Ind Yes
Num Emp Injuries 0
Num Contr Injuries 0
Num Er Injuries 1
Num Worker Injuries 0
Num Gp Injuries 0
Injure 1
Ignite Ind Yes
Explode Ind Yes
Num Pub Evacuated 50.0
Incident Identified Datetime 2016-10-19 08:51:00
On Site Datetime 2016-10-19 09:10:00
Federal No
Location Type Public Property
Incident Area Type Underground
Incident Area Subtype Exposed Due To Excavation
Depth Of Cover 30.0
Crossing No
Pipe Facility Type Investor Owned
System Part Involved Service
Installation Year 1985.0
Pipe Diameter 1.0
Pipe Specification Unknown
Pipe Manufacturer Unknown
Material Involved Steel
Wt Steel 0.133
Release Type Leak
Leak Type Connection Failure
Class Location Type Class 3 Location
Est Cost Oper Paid 15000000.0
Est Cost Prop Damage 35000.0
Est Cost Emergency 85000.0
Est Cost Other 0.0
Est Cost Unintentional Release 182.0
Prpty 15120182.0
Commercial Affected 15.0
Industrial Affected 0.0
Residences Affected 111.0
Accident Psig 50.0
Normal Psig 50.0
Mop Psig 57.0
Accident Pressure Pressure Did Not Exceed Maop
Scada In Place Ind No
Accident Identifier Notification From Third Party That Caused The Incident
Investigation Status No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind Yes
Num Employees Tested 5
Num Employees Failed 0
Contractor Drug Test Ind No
Cause Excavation Damage
Cause Details Excavation Damage By Third Party
Ex Party Type Excavation Damage By Third Party
Prior Notification Ind Yes
One Call System Ind Yes
Notify Cga Dirt No
Public Row Ind Yes
Public Subtype City Street
Excavator Type Contractor
Excavator Equipment Backhoe/trackhoe
Work Performed Cable Tv
One Call Notified Ind Yes
One Call Ticket Num 16229204
Locator Type Contract Locator
Visible Marks No
Service Interruption Yes
Service Interruption Hours 32.0
Root Cause Category Notification Issue
Root Cause Type No Notification Made To The One-Call Center/811
Preparer Name J** K*****
Preparer Title Senior Manager Code Compliance
Preparer Email J**@n********.com
Preparer Telephone 503-226-4211
Authorizer Name J* R* G*******
Authorizer Title Senior Manager Code Compliance
Authorizer Telephone 503-226-4211
Authorizer Email J**@n********.com
Narrative At approximately 8:51am on october 19, 2016 nw natural received notification of damage to a 1" service line at nw 23rd avenue and glisan street in portland. The service was damaged by loy clark during the course of their excavation for a third party. The natural gas ignited at 9:38am resulting in the loss of a structure at 500/510 nw 23rd avenue. A nw natural first responder arrived on site at 9:10am. Gas was controlled at 9:52am by closing a 2-inch valve located at the intersection of nw 22nd avenue and nw glisan street. Gas service was interrupted to 126 customers. All costs reported in part d are preliminary estimates and will be updated on supplemental reports. Historical perspective: on july 12th 2016, a locate request (ticket 16173103) for installing electric primary and service was called in by loy clark and, was accurately marked by locating inc. For the area where loy clark was excavating on october 19th, 2016. Marks from this ticket were still visible and accurate. On september 12th, 2016, a locate request for replacing telephone and cable tv mainline was called in by loy clark. The locate description for this request was close to, but did not cover, the area where loy clark was excavating on october 19th, 2016. Locate ticket number 16229204. On october 19th, 2016, during the course of excavation on part of the sidewalk on nw glisan within the area covered by the july 12th, 2016 locate, an employee with loy clark pipeline hit the gas service to 500 nw 23rd with a back hoe causing the service line to be pulled out of and separated from the fitting of the dresser valve. The operator did not employ hand tools or other non-invasive methods to determine the exact location of the underground service. Loy clark reported they were performing communication work on october 19th, 2016. The loy clark employees were digging outside of the locate area that had been called in by loy clark for communications work (locate ticket number 16229204).

All rights reserved. Copyright © by ClearPHMSA