GD incident on 2016-10-12 — OH

Operator
Columbia Gas Of Ohio Inc
Cause
Pipe, Weld, Or Joint Failure
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities 1 injury
Property damage (nominal)
$10,000
Incident datetime
2016-10-12 14:53
Report number
Location
OH, CLARK
Narrative
Narrative for part e-7: the gas controller first became aware of the incident through a low pressure alarm upstream of the event at 16:12 hours. It was determined that gas control personnel were not a contributing factor in causing or contributing to the incident. As a result of initial phone communication it was determined that discovery for gas control occurred after field operations personnel were aware and responding. Gas control does not have remote control capabilities within this market. Narrative for part h: in the process of stopping off a dead end section of 8-inch coated steel high pressure pipe an unexcavated mechanical coupling upstream of the work location pulled apart. As a result of this separation, two members of a contractor crew sustained injuries. The mechanical coupling was a seal only design but had been secured with straps welded across the joint that failed to restrain the pipe. The components in question were sent to laboratory for further analysis. The investigation determined that the straps failed due to an over load condition as a result columbia has implemented protocols to prevent a recurrence that include and are not limited to an investigation when excavating and working on metallic pipe that might include unrestrained fittings. Please consider this incident report final.
Detailed record list
Occurred At
2016-10-12 14:53:00
Year
2016
Report Received Date
2016-11-15 00:00:00
Iyear
2016.0
Report Number
20160115.0
Supplemental Number
16597.0
Report Type
Supplemental Final
Operator Id
Name
Columbia Gas Of Ohio Inc
Operator Street Address
290 W Nationwide Blvd
Operator City Name
Columbus
Operator State Abbreviation
OH
Operator Postal Code
43215
Local Datetime
2016-10-12 14:53:00
Location Street Address
2730 Columbus Ave
Location City Name
Springfield
Location County Name
Clark
Location State Abbreviation
OH
Location Postal Code
45503
Location Latitude
Location Longitude
-83.76686999
Nrc Rpt Datetime
2016-10-12 16:28:00
Nrc Rpt Num
Commodity Released Type
Natural Gas
Unintentional Release
4147.0
Fatality Ind
No
Fatal
0
Injury Ind
Yes
Num Emp Injuries
0
Num Contr Injuries
1
Num Er Injuries
0
Num Worker Injuries
0
Num Gp Injuries
0
Injure
1
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
4.0
Incident Identified Datetime
2016-10-12 14:53:00
On Site Datetime
2016-10-12 14:53:00
Federal
No
Location Type
Public Property
Incident Area Type
Underground
Incident Area Subtype
Exposed Due To Excavation
Depth Of Cover
34.0
Crossing
No
Pipe Facility Type
Investor Owned
System Part Involved
Main
Pipe Diameter
8.0
Pipe Specification
Unknown
Pipe Manufacturer
Unknown
Material Involved
Steel
Steel Seam Type
Other
Steel Seam Type Details
Unknown
Wt Steel
0.25
Release Type
Other
Release Type Details
A Metallic Strap Failed To Restrain A Unrestrained Mechanical Coupling
Class Location Type
Class 3 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
10000.0
Est Cost Emergency
27250.0
Est Cost Other
0.0
Est Cost Unintentional Release
13187.0
Prpty
50437.0
Commercial Affected
8.0
Industrial Affected
0.0
Residences Affected
0.0
Accident Psig
111.0
Normal Psig
111.0
Mop Psig
125.0
Accident Pressure
Pressure Did Not Exceed Maop
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
See narrative in section h for explanation.
Employee Drug Test Ind
No
Contractor Drug Test Ind
Yes
Num Contractors Tested
1
Num Contractors Failed
0
Cause
Pipe, Weld, Or Joint Failure
Cause Details
Mechanical Joint Failure
Pwjf Failure Type
Mechanical Joint Failure
Mec Fitting Involved
Bolted
Mec Fitting Type
Coupling
Mec Manufacturer
Dresser Style 38
Mec Fitting Material
Other
Mec Fitting Material Detail
Materials Joined: 1st Steel, 2nd Steel
Additional Other Ind
Yes
Additional Factor Details
The Mechanical Coupling Was A Seal Only Design But Had Been Secured With Straps Welded Across The Joint That Failed To Restrain The Pipe. A Laboratory Analysis Was Conducted And It Was Determined That The Straps Failed Due To An Over Load Condition.
Result Material Ind
Yes
Result Material Subtype
Other
Result Material Details
Unknown
Hydrotest Conducted Ind
No
Preparer Name
R** S****
Preparer Title
Operation Compliance Manager
Preparer Email
R******@n*******.com
Preparer Telephone
614-818-2110
Preparer Fax
614-818-2151
Authorizer Name
R** S****
Authorizer Title
Operation Compliance Manager
Authorizer Telephone
614-818-2110
Authorizer Email
R******@n*******.com
Narrative
Narrative for part e-7: the gas controller first became aware of the incident through a low pressure alarm upstream of the event at 16:12 hours. It was determined that gas control personnel were not a contributing factor in causing or contributing to the incident. As a result of initial phone communication it was determined that discovery for gas control occurred after field operations personnel were aware and responding. Gas control does not have remote control capabilities within this market. Narrative for part h: in the process of stopping off a dead end section of 8-inch coated steel high pressure pipe an unexcavated mechanical coupling upstream of the work location pulled apart. As a result of this separation, two members of a contractor crew sustained injuries. The mechanical coupling was a seal only design but had been secured with straps welded across the joint that failed to restrain the pipe. The components in question were sent to laboratory for further analysis. The investigation determined that the straps failed due to an over load condition as a result columbia has implemented protocols to prevent a recurrence that include and are not limited to an investigation when excavating and working on metallic pipe that might include unrestrained fittings. Please consider this incident report final.
Occurred At 2016-10-12 14:53:00
Year 2016
Report Received Date 2016-11-15 00:00:00
Iyear 2016.0
Report Number 20160115.0
Supplemental Number 16597.0
Report Type Supplemental Final
Operator Id 2596 PHMSA Enforcement
Name Columbia Gas Of Ohio Inc
Operator Street Address 290 W Nationwide Blvd
Operator City Name Columbus
Operator State Abbreviation OH
Operator Postal Code 43215
Local Datetime 2016-10-12 14:53:00
Location Street Address 2730 Columbus Ave
Location City Name Springfield
Location County Name Clark
Location State Abbreviation OH
Location Postal Code 45503
Location Latitude 39.936713 Google Maps OpenStreetMap
Location Longitude -83.76686999 Google Maps OpenStreetMap
Nrc Rpt Datetime 2016-10-12 16:28:00
Nrc Rpt Num 1161404 NRC Report How to search
Commodity Released Type Natural Gas
Unintentional Release 4147.0
Fatality Ind No
Fatal 0
Injury Ind Yes
Num Emp Injuries 0
Num Contr Injuries 1
Num Er Injuries 0
Num Worker Injuries 0
Num Gp Injuries 0
Injure 1
Ignite Ind No
Explode Ind No
Num Pub Evacuated 4.0
Incident Identified Datetime 2016-10-12 14:53:00
On Site Datetime 2016-10-12 14:53:00
Federal No
Location Type Public Property
Incident Area Type Underground
Incident Area Subtype Exposed Due To Excavation
Depth Of Cover 34.0
Crossing No
Pipe Facility Type Investor Owned
System Part Involved Main
Pipe Diameter 8.0
Pipe Specification Unknown
Pipe Manufacturer Unknown
Material Involved Steel
Steel Seam Type Other
Steel Seam Type Details Unknown
Wt Steel 0.25
Release Type Other
Release Type Details A Metallic Strap Failed To Restrain A Unrestrained Mechanical Coupling
Class Location Type Class 3 Location
Est Cost Oper Paid 0.0
Est Cost Prop Damage 10000.0
Est Cost Emergency 27250.0
Est Cost Other 0.0
Est Cost Unintentional Release 13187.0
Prpty 50437.0
Commercial Affected 8.0
Industrial Affected 0.0
Residences Affected 0.0
Accident Psig 111.0
Normal Psig 111.0
Mop Psig 125.0
Accident Pressure Pressure Did Not Exceed Maop
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind Yes
Scada Conf Ind Yes
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details See narrative in section h for explanation.
Employee Drug Test Ind No
Contractor Drug Test Ind Yes
Num Contractors Tested 1
Num Contractors Failed 0
Cause Pipe, Weld, Or Joint Failure
Cause Details Mechanical Joint Failure
Pwjf Failure Type Mechanical Joint Failure
Mec Fitting Involved Bolted
Mec Fitting Type Coupling
Mec Manufacturer Dresser Style 38
Mec Fitting Material Other
Mec Fitting Material Detail Materials Joined: 1st Steel, 2nd Steel
Additional Other Ind Yes
Additional Factor Details The Mechanical Coupling Was A Seal Only Design But Had Been Secured With Straps Welded Across The Joint That Failed To Restrain The Pipe. A Laboratory Analysis Was Conducted And It Was Determined That The Straps Failed Due To An Over Load Condition.
Result Material Ind Yes
Result Material Subtype Other
Result Material Details Unknown
Hydrotest Conducted Ind No
Preparer Name R** S****
Preparer Title Operation Compliance Manager
Preparer Email R******@n*******.com
Preparer Telephone 614-818-2110
Preparer Fax 614-818-2151
Authorizer Name R** S****
Authorizer Title Operation Compliance Manager
Authorizer Telephone 614-818-2110
Authorizer Email R******@n*******.com
Narrative Narrative for part e-7: the gas controller first became aware of the incident through a low pressure alarm upstream of the event at 16:12 hours. It was determined that gas control personnel were not a contributing factor in causing or contributing to the incident. As a result of initial phone communication it was determined that discovery for gas control occurred after field operations personnel were aware and responding. Gas control does not have remote control capabilities within this market. Narrative for part h: in the process of stopping off a dead end section of 8-inch coated steel high pressure pipe an unexcavated mechanical coupling upstream of the work location pulled apart. As a result of this separation, two members of a contractor crew sustained injuries. The mechanical coupling was a seal only design but had been secured with straps welded across the joint that failed to restrain the pipe. The components in question were sent to laboratory for further analysis. The investigation determined that the straps failed due to an over load condition as a result columbia has implemented protocols to prevent a recurrence that include and are not limited to an investigation when excavating and working on metallic pipe that might include unrestrained fittings. Please consider this incident report final.

All rights reserved. Copyright © by ClearPHMSA