GD incident on 2016-05-11 — IL

Operator
Ameren Illinois Company
Cause
Locating Issue
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities 1 injury
Property damage (nominal)
$3,689
Incident datetime
2016-05-11 10:42
Report number
Location
IL, MACOUPIN
Narrative
A 1/2" plastic gas service to 419 n west street was cut by a third party contractor, resulting in gas blowing to atmosphere. The ameren illinois first responder stopped the blowing gas using an expandable plug into the cut 1/2" service. Approximately 80 minutes later, after the cut gas service had been plugged and an ameren illinois crew was on site to make repairs, an explosion occurred at the structure located at 430 n west street. The post investigation of the area required a temporary outage to 33 gas customers. Revision as of (12/20/2016): the likely cause of the incident, given the relatively short timeframe between the damaged gas service at 419 n west st and the incident occurring at 430 n west st, is attributed to the third party damage of the gas service. The contractor installing a water main in the street had a valid dig ticket, but the service was inaccurately marked inaccurately marked in the field by the locator. Additional post-incident investigation at the 430 n west street location determined that the sewer trap for the sewer lateral into the structure was dry. Ameren illinois, however, was not able to establish that natural gas from the hit service location migrated into the home at 430 n west st. Part a, line 10 - lost gas estimate was updated to 5.4 mcf, with an associated lost gas cost of $21 updated in part d. Part a, line 12 - there were two injuries reported, however ameren illinois could only confirm that one required inpatient hospitalization. Part a, line 13 - the gas main was shut down after the incident occurred. The ameren illinois first responder had removed the plug stopper after the incident, and then the adjacent 1-1/4" plastic gas main was excavated and squeezed off interrupting service to the 400 block of n west st. The gas main serving the 200 and 300 block of n west st was also taken out of service as a precautionary measure. The gas mains were reenergized upon completion of air pressure testing of the gas facilities in the 200 - 400 block of n west st. Part g - the primary cause of the incident was updated to g3, third party damage, with additional supporting information provided. Revision as of 12/31/2016 part a, line 13b - clarifying the time restoration to gas mains is correctly stated as 5/13/2016 00:00, which was right at midnight. Part a, line 14 - revised to "yes" part c, line 5 - revised to "mechanical", with dimensions intended to show the circumference of the cut 1/2" service..
Detailed record list
Occurred At
2016-05-11 10:42:00
Year
2016
Report Received Date
2016-06-10 00:00:00
Iyear
2016.0
Report Number
20160053.0
Supplemental Number
16467.0
Report Type
Supplemental Final
Operator Id
Name
Ameren Illinois Company
Operator Street Address
10 Executive Dr.
Operator City Name
Collinsville
Operator State Abbreviation
IL
Operator Postal Code
62234
Local Datetime
2016-05-11 10:42:00
Location Street Address
430 N West Street
Location City Name
Carlinville
Location County Name
Macoupin
Location State Abbreviation
IL
Location Postal Code
62626
Location Latitude
Location Longitude
Nrc Rpt Datetime
2016-05-11 11:37:00
Nrc Rpt Num
Commodity Released Type
Natural Gas
Unintentional Release
5.4
Fatality Ind
No
Fatal
0
Injury Ind
Yes
Num Emp Injuries
0
Num Contr Injuries
0
Num Er Injuries
0
Num Worker Injuries
0
Num Gp Injuries
1
Injure
1
Ignite Ind
Yes
Explode Ind
Yes
Num Pub Evacuated
14.0
Incident Identified Datetime
2016-05-11 10:42:00
On Site Datetime
2016-05-11 09:22:00
Federal
No
Location Type
Public Property
Incident Area Type
Aboveground
Incident Area Subtype
Inside A Building
Crossing
No
Pipe Facility Type
Investor Owned
System Part Involved
Service
Installation Year
1982.0
Pipe Diameter
0.625
Pipe Specification
Aldyl A
Pipe Manufacturer
Dupont
Material Involved
Plastic
Plastic Type
Polyethylene (Pe)
Wt Plastic
0.09
Material Pe Pipe Code
2306
Release Type
Mechanical Puncture
Puncture Axial
0.5
Puncture Circum
2.0
Class Location Type
Class 3 Location
Est Cost Oper Paid
125000.0
Est Cost Prop Damage
3689.0
Est Cost Emergency
155668.0
Est Cost Other
0.0
Est Cost Unintentional Release
21.0
Prpty
284378.0
Commercial Affected
1.0
Industrial Affected
0.0
Residences Affected
32.0
Accident Psig
50.0
Normal Psig
50.0
Mop Psig
60.0
Accident Pressure
Pressure Did Not Exceed Maop
Scada In Place Ind
No
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
Yes
Num Employees Tested
4
Num Employees Failed
0
Contractor Drug Test Ind
No
Cause
Excavation Damage
Cause Details
Excavation Damage By Third Party
Ex Party Type
Excavation Damage By Third Party
Prior Notification Ind
Yes
One Call System Ind
Yes
Notify Cga Dirt
Yes
Public Row Ind
Yes
Public Subtype
City Street
Excavator Type
Contractor
Excavator Equipment
Backhoe/trackhoe
Work Performed
Water
One Call Notified Ind
Yes
One Call Ticket Num
1111116
One Call Center Name
Illinois Julie One Call Center
Locator Type
Contract Locator
Visible Marks
Yes
Service Interruption
Yes
Service Interruption Hours
36.0
Root Cause Category
Locating Issue
Root Cause Type
Facility Not Marked Due To Incomplete Marks At Damage Location
Preparer Name
J*** B******
Preparer Title
Manager Gas Compliance And Training
Preparer Email
J*******@a*****.com
Preparer Telephone
217-625-6854
Preparer Fax
314-613-2640
Authorizer Name
J*** B******
Authorizer Title
Manager Gas Compliance And Training
Authorizer Telephone
217-625-6854
Authorizer Email
J*******@a*****.com
Narrative
A 1/2" plastic gas service to 419 n west street was cut by a third party contractor, resulting in gas blowing to atmosphere. The ameren illinois first responder stopped the blowing gas using an expandable plug into the cut 1/2" service. Approximately 80 minutes later, after the cut gas service had been plugged and an ameren illinois crew was on site to make repairs, an explosion occurred at the structure located at 430 n west street. The post investigation of the area required a temporary outage to 33 gas customers. Revision as of (12/20/2016): the likely cause of the incident, given the relatively short timeframe between the damaged gas service at 419 n west st and the incident occurring at 430 n west st, is attributed to the third party damage of the gas service. The contractor installing a water main in the street had a valid dig ticket, but the service was inaccurately marked inaccurately marked in the field by the locator. Additional post-incident investigation at the 430 n west street location determined that the sewer trap for the sewer lateral into the structure was dry. Ameren illinois, however, was not able to establish that natural gas from the hit service location migrated into the home at 430 n west st. Part a, line 10 - lost gas estimate was updated to 5.4 mcf, with an associated lost gas cost of $21 updated in part d. Part a, line 12 - there were two injuries reported, however ameren illinois could only confirm that one required inpatient hospitalization. Part a, line 13 - the gas main was shut down after the incident occurred. The ameren illinois first responder had removed the plug stopper after the incident, and then the adjacent 1-1/4" plastic gas main was excavated and squeezed off interrupting service to the 400 block of n west st. The gas main serving the 200 and 300 block of n west st was also taken out of service as a precautionary measure. The gas mains were reenergized upon completion of air pressure testing of the gas facilities in the 200 - 400 block of n west st. Part g - the primary cause of the incident was updated to g3, third party damage, with additional supporting information provided. Revision as of 12/31/2016 part a, line 13b - clarifying the time restoration to gas mains is correctly stated as 5/13/2016 00:00, which was right at midnight. Part a, line 14 - revised to "yes" part c, line 5 - revised to "mechanical", with dimensions intended to show the circumference of the cut 1/2" service..
Occurred At 2016-05-11 10:42:00
Year 2016
Report Received Date 2016-06-10 00:00:00
Iyear 2016.0
Report Number 20160053.0
Supplemental Number 16467.0
Report Type Supplemental Final
Operator Id 32513 PHMSA Enforcement
Name Ameren Illinois Company
Operator Street Address 10 Executive Dr.
Operator City Name Collinsville
Operator State Abbreviation IL
Operator Postal Code 62234
Local Datetime 2016-05-11 10:42:00
Location Street Address 430 N West Street
Location City Name Carlinville
Location County Name Macoupin
Location State Abbreviation IL
Location Postal Code 62626
Location Latitude 39.284661 Google Maps OpenStreetMap
Location Longitude -89.883213 Google Maps OpenStreetMap
Nrc Rpt Datetime 2016-05-11 11:37:00
Nrc Rpt Num 1147479 NRC Report How to search
Commodity Released Type Natural Gas
Unintentional Release 5.4
Fatality Ind No
Fatal 0
Injury Ind Yes
Num Emp Injuries 0
Num Contr Injuries 0
Num Er Injuries 0
Num Worker Injuries 0
Num Gp Injuries 1
Injure 1
Ignite Ind Yes
Explode Ind Yes
Num Pub Evacuated 14.0
Incident Identified Datetime 2016-05-11 10:42:00
On Site Datetime 2016-05-11 09:22:00
Federal No
Location Type Public Property
Incident Area Type Aboveground
Incident Area Subtype Inside A Building
Crossing No
Pipe Facility Type Investor Owned
System Part Involved Service
Installation Year 1982.0
Pipe Diameter 0.625
Pipe Specification Aldyl A
Pipe Manufacturer Dupont
Material Involved Plastic
Plastic Type Polyethylene (Pe)
Wt Plastic 0.09
Material Pe Pipe Code 2306
Release Type Mechanical Puncture
Puncture Axial 0.5
Puncture Circum 2.0
Class Location Type Class 3 Location
Est Cost Oper Paid 125000.0
Est Cost Prop Damage 3689.0
Est Cost Emergency 155668.0
Est Cost Other 0.0
Est Cost Unintentional Release 21.0
Prpty 284378.0
Commercial Affected 1.0
Industrial Affected 0.0
Residences Affected 32.0
Accident Psig 50.0
Normal Psig 50.0
Mop Psig 60.0
Accident Pressure Pressure Did Not Exceed Maop
Scada In Place Ind No
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
Investigation Status No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind Yes
Num Employees Tested 4
Num Employees Failed 0
Contractor Drug Test Ind No
Cause Excavation Damage
Cause Details Excavation Damage By Third Party
Ex Party Type Excavation Damage By Third Party
Prior Notification Ind Yes
One Call System Ind Yes
Notify Cga Dirt Yes
Public Row Ind Yes
Public Subtype City Street
Excavator Type Contractor
Excavator Equipment Backhoe/trackhoe
Work Performed Water
One Call Notified Ind Yes
One Call Ticket Num 1111116
One Call Center Name Illinois Julie One Call Center
Locator Type Contract Locator
Visible Marks Yes
Service Interruption Yes
Service Interruption Hours 36.0
Root Cause Category Locating Issue
Root Cause Type Facility Not Marked Due To Incomplete Marks At Damage Location
Preparer Name J*** B******
Preparer Title Manager Gas Compliance And Training
Preparer Email J*******@a*****.com
Preparer Telephone 217-625-6854
Preparer Fax 314-613-2640
Authorizer Name J*** B******
Authorizer Title Manager Gas Compliance And Training
Authorizer Telephone 217-625-6854
Authorizer Email J*******@a*****.com
Narrative A 1/2" plastic gas service to 419 n west street was cut by a third party contractor, resulting in gas blowing to atmosphere. The ameren illinois first responder stopped the blowing gas using an expandable plug into the cut 1/2" service. Approximately 80 minutes later, after the cut gas service had been plugged and an ameren illinois crew was on site to make repairs, an explosion occurred at the structure located at 430 n west street. The post investigation of the area required a temporary outage to 33 gas customers. Revision as of (12/20/2016): the likely cause of the incident, given the relatively short timeframe between the damaged gas service at 419 n west st and the incident occurring at 430 n west st, is attributed to the third party damage of the gas service. The contractor installing a water main in the street had a valid dig ticket, but the service was inaccurately marked inaccurately marked in the field by the locator. Additional post-incident investigation at the 430 n west street location determined that the sewer trap for the sewer lateral into the structure was dry. Ameren illinois, however, was not able to establish that natural gas from the hit service location migrated into the home at 430 n west st. Part a, line 10 - lost gas estimate was updated to 5.4 mcf, with an associated lost gas cost of $21 updated in part d. Part a, line 12 - there were two injuries reported, however ameren illinois could only confirm that one required inpatient hospitalization. Part a, line 13 - the gas main was shut down after the incident occurred. The ameren illinois first responder had removed the plug stopper after the incident, and then the adjacent 1-1/4" plastic gas main was excavated and squeezed off interrupting service to the 400 block of n west st. The gas main serving the 200 and 300 block of n west st was also taken out of service as a precautionary measure. The gas mains were reenergized upon completion of air pressure testing of the gas facilities in the 200 - 400 block of n west st. Part g - the primary cause of the incident was updated to g3, third party damage, with additional supporting information provided. Revision as of 12/31/2016 part a, line 13b - clarifying the time restoration to gas mains is correctly stated as 5/13/2016 00:00, which was right at midnight. Part a, line 14 - revised to "yes" part c, line 5 - revised to "mechanical", with dimensions intended to show the circumference of the cut 1/2" service..