Incident details
Operator, cause, commodity and consequences with raw source fields.
GD incident on 2015-12-16 — MI
Operator
Dte Gas Company
Cause
Excavation Issue
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$25,746
Incident datetime
2015-12-16 10:36
Report number
Location
MI, WAYNE
Narrative
A contractor crew performing directional boring for water main work struck a 6-inch plastic gas distribution main during pull-back of a reaming tool. The location of the gas main had not been verified prior to the work. Dte gas emergency response personnel stopped the leaking gas from the east by installing a line stopper pressure control fitting on a 12-inch section of main, and from the west by pinching the 6-inch plastic main. Leaking gas was stopped at 23:23, some 13 hours after the damage. Repairs were completed at 04:30 on december 17, 2015, using 3 feet of new 6-inch plastic pipe and two electrofusion couplings.
Detailed record list
Occurred At
2015-12-16 10:36:00
Year
2015
Report Received Date
2016-01-15 00:00:00
Iyear
2015.0
Report Number
20160003.0
Supplemental Number
16299.0
Report Type
Supplemental Final
Operator Id
12408
Name
Dte Gas Company
Operator Street Address
1 Energy Plaza
Operator City Name
Detroit
Operator State Abbreviation
MI
Operator Postal Code
48226
Local Datetime
2015-12-16 10:36:00
Location Street Address
28800 Northline Road
Location City Name
Romulus
Location County Name
Wayne
Location State Abbreviation
MI
Location Postal Code
48174
Location Latitude
42.210076
Location Longitude
-83.32151
Nrc Rpt Datetime
2015-12-16 17:45:00
Nrc Rpt Num
1135991
Commodity Released Type
Natural Gas
Unintentional Release
7991.85
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0.0
Incident Identified Datetime
2015-12-16 10:36:00
On Site Datetime
2015-12-16 10:52:00
Federal
No
Location Type
Public Property
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
120.0
Crossing
No
Pipe Facility Type
Privately Owned
System Part Involved
Main
Installation Year
2000.0
Pipe Diameter
6.0
Pipe Specification
Astm D2513
Pipe Manufacturer
Plexco
Material Involved
Plastic
Plastic Type
Polyethylene (Pe)
Plastic Sdr
11
Material Pe Pipe Code
2406
Release Type
Mechanical Puncture
Puncture Axial
6.0
Puncture Circum
10.0
Class Location Type
Class 3 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
25746.0
Est Cost Emergency
57344.0
Est Cost Other
2326.0
Est Cost Other Details
Traffic Control
Est Cost Unintentional Release
32526.0
Prpty
117942.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
0.0
Accident Psig
45.0
Normal Psig
45.0
Mop Psig
45.0
Accident Pressure
Pressure Did Not Exceed Maop
Scada In Place Ind
No
Accident Identifier
Notification From Third Party That Caused The Incident
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Excavation Damage
Cause Details
Excavation Damage By Third Party
Ex Party Type
Excavation Damage By Third Party
Prior Notification Ind
Yes
One Call System Ind
Yes
Notify Cga Dirt
No
Public Row Ind
Yes
Public Subtype
County Road
Excavator Type
Contractor
Excavator Equipment
Boring
Work Performed
Water
One Call Notified Ind
Yes
One Call Ticket Num
53430367
Locator Type
Utility Owner
Visible Marks
Yes
Root Cause Category
Excavation Issue
Root Cause Type
Improper Excavation Practice Not Listed Above
Preparer Name
R***** F*********
Preparer Title
Manager
Preparer Email
F**********@d********.com
Authorizer Name
F***** S****
Authorizer Title
Supervisor
Authorizer Telephone
313-389-7762
Authorizer Email
S******@d********.com
Narrative
A contractor crew performing directional boring for water main work struck a 6-inch plastic gas distribution main during pull-back of a reaming tool. The location of the gas main had not been verified prior to the work. Dte gas emergency response personnel stopped the leaking gas from the east by installing a line stopper pressure control fitting on a 12-inch section of main, and from the west by pinching the 6-inch plastic main. Leaking gas was stopped at 23:23, some 13 hours after the damage. Repairs were completed at 04:30 on december 17, 2015, using 3 feet of new 6-inch plastic pipe and two electrofusion couplings.
| Occurred At | 2015-12-16 10:36:00 |
|---|---|
| Year | 2015 |
| Report Received Date | 2016-01-15 00:00:00 |
| Iyear | 2015.0 |
| Report Number | 20160003.0 |
| Supplemental Number | 16299.0 |
| Report Type | Supplemental Final |
| Operator Id | 12408 PHMSA Enforcement |
| Name | Dte Gas Company |
| Operator Street Address | 1 Energy Plaza |
| Operator City Name | Detroit |
| Operator State Abbreviation | MI |
| Operator Postal Code | 48226 |
| Local Datetime | 2015-12-16 10:36:00 |
| Location Street Address | 28800 Northline Road |
| Location City Name | Romulus |
| Location County Name | Wayne |
| Location State Abbreviation | MI |
| Location Postal Code | 48174 |
| Location Latitude | 42.210076 Google Maps OpenStreetMap |
| Location Longitude | -83.32151 Google Maps OpenStreetMap |
| Nrc Rpt Datetime | 2015-12-16 17:45:00 |
| Nrc Rpt Num | 1135991 NRC Report How to search |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 7991.85 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Ignite Ind | No |
| Explode Ind | No |
| Num Pub Evacuated | 0.0 |
| Incident Identified Datetime | 2015-12-16 10:36:00 |
| On Site Datetime | 2015-12-16 10:52:00 |
| Federal | No |
| Location Type | Public Property |
| Incident Area Type | Underground |
| Incident Area Subtype | Under Soil |
| Depth Of Cover | 120.0 |
| Crossing | No |
| Pipe Facility Type | Privately Owned |
| System Part Involved | Main |
| Installation Year | 2000.0 |
| Pipe Diameter | 6.0 |
| Pipe Specification | Astm D2513 |
| Pipe Manufacturer | Plexco |
| Material Involved | Plastic |
| Plastic Type | Polyethylene (Pe) |
| Plastic Sdr | 11 |
| Material Pe Pipe Code | 2406 |
| Release Type | Mechanical Puncture |
| Puncture Axial | 6.0 |
| Puncture Circum | 10.0 |
| Class Location Type | Class 3 Location |
| Est Cost Oper Paid | 0.0 |
| Est Cost Prop Damage | 25746.0 |
| Est Cost Emergency | 57344.0 |
| Est Cost Other | 2326.0 |
| Est Cost Other Details | Traffic Control |
| Est Cost Unintentional Release | 32526.0 |
| Prpty | 117942.0 |
| Commercial Affected | 0.0 |
| Industrial Affected | 0.0 |
| Residences Affected | 0.0 |
| Accident Psig | 45.0 |
| Normal Psig | 45.0 |
| Mop Psig | 45.0 |
| Accident Pressure | Pressure Did Not Exceed Maop |
| Scada In Place Ind | No |
| Accident Identifier | Notification From Third Party That Caused The Incident |
| Investigation Status | No, the facility was not monitored by a controller(s) at the time of the incident |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Excavation Damage |
| Cause Details | Excavation Damage By Third Party |
| Ex Party Type | Excavation Damage By Third Party |
| Prior Notification Ind | Yes |
| One Call System Ind | Yes |
| Notify Cga Dirt | No |
| Public Row Ind | Yes |
| Public Subtype | County Road |
| Excavator Type | Contractor |
| Excavator Equipment | Boring |
| Work Performed | Water |
| One Call Notified Ind | Yes |
| One Call Ticket Num | 53430367 |
| Locator Type | Utility Owner |
| Visible Marks | Yes |
| Root Cause Category | Excavation Issue |
| Root Cause Type | Improper Excavation Practice Not Listed Above |
| Preparer Name | R***** F********* |
| Preparer Title | Manager |
| Preparer Email | F**********@d********.com |
| Authorizer Name | F***** S**** |
| Authorizer Title | Supervisor |
| Authorizer Telephone | 313-389-7762 |
| Authorizer Email | S******@d********.com |
| Narrative | A contractor crew performing directional boring for water main work struck a 6-inch plastic gas distribution main during pull-back of a reaming tool. The location of the gas main had not been verified prior to the work. Dte gas emergency response personnel stopped the leaking gas from the east by installing a line stopper pressure control fitting on a 12-inch section of main, and from the west by pinching the 6-inch plastic main. Leaking gas was stopped at 23:23, some 13 hours after the damage. Repairs were completed at 04:30 on december 17, 2015, using 3 feet of new 6-inch plastic pipe and two electrofusion couplings. |