Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2015-11-10 — TX
Operator
Enterprise Crude Pipeline Llc
Cause
Equipment Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$3,600
Incident datetime
2015-11-10 14:30
Report number
Location
TX
Narrative
On 11/10/2015 at approximately 14:30, local operations were emptying a vacuum truck into the local sump. The level transmitter failed to respond with the correct level allowing the sump to overflow. All crude was cleaned up with on-site personnel and transmitter was replaced.
Detailed record list
Report Received Date
2015-11-30 00:00:00
Iyear
2015
Report Number
20150429
Supplemental Number
20941
Report Type
Original Final
Operator Id
30829
Name
Enterprise Crude Pipeline Llc
Operator Street Address
1100 Louisiana Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2015-11-10 14:30:00
Location Latitude
29.526883
Location Longitude
-95.104507
Commodity Released Type
Crude Oil
Unintentional Release Bbls
1.5
Recovered Bbls
1.5
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2015-11-10 14:30:00
System Part Involved
Onshore Terminal/tank Farm Equipment And Piping
On Off Shore
Onshore
Shutdown Due Accident Ind
No
Shutdown Explain
Sump Was Isolated From Facility
On Site Datetime
2015-11-10 14:30:00
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Anahuac Junction
Segment Name
Anahuac Junction
Onshore State Abbreviation
Tx
Onshore Postal Code
77598
Onshore City Name
Webster
Onshore County Name
Harris
Designated Location
Milepost/valve Station
Designated Name
Anahuac Junct
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Sump
Installation Year
2012
Material Involved
Carbon Steel
Release Type
Overfill Or Overflow
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
High Pop Ind
Yes
High Pop Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
65
Est Cost Prop Damage
3600
Est Cost Emergency
0
Est Cost Environmental
0
Est Cost Other
0
Prpty
3665
Accident Psig
5
Mop Psig
720
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Controller nor control room were a contributing factor.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Other Equipment Failure
Eq Failure Type
Other Equipment Failure
Failure Details
Transmitter Failure
Eq Additional Other Ind
Yes
Eq Additional Other Details
Transmitter Not Responding To Differental Pressure Change
Preparer Name
C**** A******
Preparer Title
Pipeline Compliance Specialist
Preparer Email
C*******@e****.com
Preparer Telephone
713-381-6426
Prepared Date
2015-11-30 00:00:00
Authorizer Name
C**** A******
Authorizer Telephone
713-381-6426
Authorizer Email
C*******@e****.com
Narrative
On 11/10/2015 at approximately 14:30, local operations were emptying a vacuum truck into the local sump. The level transmitter failed to respond with the correct level allowing the sump to overflow. All crude was cleaned up with on-site personnel and transmitter was replaced.
| Report Received Date | 2015-11-30 00:00:00 |
|---|---|
| Iyear | 2015 |
| Report Number | 20150429 |
| Supplemental Number | 20941 |
| Report Type | Original Final |
| Operator Id | 30829 PHMSA Enforcement |
| Name | Enterprise Crude Pipeline Llc |
| Operator Street Address | 1100 Louisiana Street |
| Operator City Name | Houston |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77002 |
| Local Datetime | 2015-11-10 14:30:00 |
| Location Latitude | 29.526883 Google Maps OpenStreetMap |
| Location Longitude | -95.104507 Google Maps OpenStreetMap |
| Commodity Released Type | Crude Oil |
| Unintentional Release Bbls | 1.5 |
| Recovered Bbls | 1.5 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Operator Employee |
| Incident Identified Datetime | 2015-11-10 14:30:00 |
| System Part Involved | Onshore Terminal/tank Farm Equipment And Piping |
| On Off Shore | Onshore |
| Shutdown Due Accident Ind | No |
| Shutdown Explain | Sump Was Isolated From Facility |
| On Site Datetime | 2015-11-10 14:30:00 |
| Nrc Rpt Num | Nrc Notification Not Required NRC Report How to search |
| Ignite Ind | No |
| Explode Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Anahuac Junction |
| Segment Name | Anahuac Junction |
| Onshore State Abbreviation | Tx |
| Onshore Postal Code | 77598 |
| Onshore City Name | Webster |
| Onshore County Name | Harris |
| Designated Location | Milepost/valve Station |
| Designated Name | Anahuac Junct |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
| Crossing | No |
| Pipe Facility Type | Interstate |
| Item Involved | Sump |
| Installation Year | 2012 |
| Material Involved | Carbon Steel |
| Release Type | Overfill Or Overflow |
| Wildlife Impact Ind | No |
| Soil Contamination | No |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | Yes |
| Commodity Reached Hca | Yes |
| High Pop Ind | Yes |
| High Pop Yes No | Yes |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 65 |
| Est Cost Prop Damage | 3600 |
| Est Cost Emergency | 0 |
| Est Cost Environmental | 0 |
| Est Cost Other | 0 |
| Prpty | 3665 |
| Accident Psig | 5 |
| Mop Psig | 720 |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Cpm In Place Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | Controller nor control room were a contributing factor. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Equipment Failure |
| Cause Details | Other Equipment Failure |
| Eq Failure Type | Other Equipment Failure |
| Failure Details | Transmitter Failure |
| Eq Additional Other Ind | Yes |
| Eq Additional Other Details | Transmitter Not Responding To Differental Pressure Change |
| Preparer Name | C**** A****** |
| Preparer Title | Pipeline Compliance Specialist |
| Preparer Email | C*******@e****.com |
| Preparer Telephone | 713-381-6426 |
| Prepared Date | 2015-11-30 00:00:00 |
| Authorizer Name | C**** A****** |
| Authorizer Telephone | 713-381-6426 |
| Authorizer Email | C*******@e****.com |
| Narrative | On 11/10/2015 at approximately 14:30, local operations were emptying a vacuum truck into the local sump. The level transmitter failed to respond with the correct level allowing the sump to overflow. All crude was cleaned up with on-site personnel and transmitter was replaced. |
External Resources
PHMSA pipeline safety insights.
Product
Features
Company
All rights reserved. Copyright © by ClearPHMSA