Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2015-09-16 — OH
Operator
Tesoro Logistics Operations Llc - Southern California
Cause
Equipment Failure
Commodity
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$6,000
Incident datetime
2015-09-16 06:35
Report number
Location
OH
Narrative
On september 16, 2015 a contractor working at the tesoro long beach terminal (lbt) noted vacuum gas oil (vgo) in the secondary containment of the aboveground piping vault. Pipelines running through the vault were idle when the loss of containment was discovered. There were no injuries or impact to the community. It was calculated from average gauges of the oil and water interface within the vault that approximately 70 bbl of vgo leaked from an isolating flange on mov-824 on the t-14 pipeline and was fully contained within secondary containment. It was immediately cleaned up, and the pipeline returned to service at 09:35 on september 18, 2015. A pressure of at least 200 psi was experienced by the t-14 line on september 15, 2015. However, the exact pressure cannot be determined. The monitoring system at lbt was only configured to register pressures up to 200 psi on the t-14 line.
Detailed record list
Report Received Date
2015-10-14 00:00:00
Iyear
2015
Report Number
20150363
Supplemental Number
21317
Report Type
Supplemental Final
Operator Id
38933
Name
Tesoro Logistics Operations Llc - Southern California
Operator Street Address
539 South Main Street
Operator City Name
Findlay
Operator State Abbreviation
OH
Operator Postal Code
45840
Local Datetime
2015-09-15 12:30:00
Location Latitude
33.771038
Location Longitude
-118.225012
Commodity Released Type
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype
Other
Commodity Details
Vacuum Gas Oil
Unintentional Release Bbls
70
Recovered Bbls
70
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Contractor Working For The Operator
Incident Identified Datetime
2015-09-16 06:35:00
System Part Involved
Onshore Pipeline, Including Valve Sites
On Off Shore
Onshore
Shutdown Due Accident Ind
No
Shutdown Explain
The Line Was Already Shut Down At The Time Of Discovery.
On Site Datetime
2015-09-16 07:00:00
Nrc Rpt Datetime
2015-09-16 07:28:00
Nrc Rpt Num
1128627
Ignite Ind
No
Explode Ind
No
Upstream Valve Type Ind
Manual
Downstream Valve Type Ind
Automatic
Num Pub Evacuated
0
Pipe Fac Name
Long Beach Terminal
Segment Name
T-14
Onshore State Abbreviation
Ca
Onshore Postal Code
90813
Onshore City Name
Long Beach
Onshore County Name
Los Angeles County
Designated Location
Milepost/valve Station
Designated Name
Vault 312
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Intrastate
Item Involved
Flange Assembly
Installation Year
2015
Material Involved
Material Other Than Carbon Steel
Material Details
G10 Gasket With Steel Washers
Release Type
Leak
Leak Type
Connection Failure
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
High Pop Ind
Yes
High Pop Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
3500
Est Cost Prop Damage
6000
Est Cost Emergency
6000
Est Cost Environmental
0
Est Cost Other
0
Prpty
15500
Accident Psig
200
Mop Psig
275
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Length Segment Isolated
2600
Internal Inspection Ind
Yes
Operation Complications Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
Yes
Cpm In Place Ind
Yes
Cpm Operating Ind
No
Cpm Functional Ind
No
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest No Controller Ind
Yes
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Non-Threaded Connection Failure
Eq Failure Type
Non-Threaded Connection Failure
Other Non Threaded Ind
Gasket
Additional Overpressure Ind
Yes
Preparer Name
H**** M****
Preparer Title
Senior Regulatory Compliance Specialist
Preparer Email
H************@t******.com
Preparer Telephone
210-626-4901
Prepared Date
2016-04-18 00:00:00
Authorizer Name
A**** W* M*******
Authorizer Telephone
210-626-6343
Authorizer Title
Director Compliance-Logistics
Authorizer Email
A***************@t******.com
Narrative
On september 16, 2015 a contractor working at the tesoro long beach terminal (lbt) noted vacuum gas oil (vgo) in the secondary containment of the aboveground piping vault. Pipelines running through the vault were idle when the loss of containment was discovered. There were no injuries or impact to the community. It was calculated from average gauges of the oil and water interface within the vault that approximately 70 bbl of vgo leaked from an isolating flange on mov-824 on the t-14 pipeline and was fully contained within secondary containment. It was immediately cleaned up, and the pipeline returned to service at 09:35 on september 18, 2015. A pressure of at least 200 psi was experienced by the t-14 line on september 15, 2015. However, the exact pressure cannot be determined. The monitoring system at lbt was only configured to register pressures up to 200 psi on the t-14 line.
| Report Received Date | 2015-10-14 00:00:00 |
|---|---|
| Iyear | 2015 |
| Report Number | 20150363 |
| Supplemental Number | 21317 |
| Report Type | Supplemental Final |
| Operator Id | 38933 PHMSA Enforcement |
| Name | Tesoro Logistics Operations Llc - Southern California |
| Operator Street Address | 539 South Main Street |
| Operator City Name | Findlay |
| Operator State Abbreviation | OH |
| Operator Postal Code | 45840 |
| Local Datetime | 2015-09-15 12:30:00 |
| Location Latitude | 33.771038 Google Maps OpenStreetMap |
| Location Longitude | -118.225012 Google Maps OpenStreetMap |
| Commodity Released Type | Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions |
| Commodity Subtype | Other |
| Commodity Details | Vacuum Gas Oil |
| Unintentional Release Bbls | 70 |
| Recovered Bbls | 70 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Contractor Working For The Operator |
| Incident Identified Datetime | 2015-09-16 06:35:00 |
| System Part Involved | Onshore Pipeline, Including Valve Sites |
| On Off Shore | Onshore |
| Shutdown Due Accident Ind | No |
| Shutdown Explain | The Line Was Already Shut Down At The Time Of Discovery. |
| On Site Datetime | 2015-09-16 07:00:00 |
| Nrc Rpt Datetime | 2015-09-16 07:28:00 |
| Nrc Rpt Num | 1128627 NRC Report How to search |
| Ignite Ind | No |
| Explode Ind | No |
| Upstream Valve Type Ind | Manual |
| Downstream Valve Type Ind | Automatic |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Long Beach Terminal |
| Segment Name | T-14 |
| Onshore State Abbreviation | Ca |
| Onshore Postal Code | 90813 |
| Onshore City Name | Long Beach |
| Onshore County Name | Los Angeles County |
| Designated Location | Milepost/valve Station |
| Designated Name | Vault 312 |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
| Crossing | No |
| Pipe Facility Type | Intrastate |
| Item Involved | Flange Assembly |
| Installation Year | 2015 |
| Material Involved | Material Other Than Carbon Steel |
| Material Details | G10 Gasket With Steel Washers |
| Release Type | Leak |
| Leak Type | Connection Failure |
| Wildlife Impact Ind | No |
| Soil Contamination | No |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | Yes |
| Commodity Reached Hca | Yes |
| High Pop Ind | Yes |
| High Pop Yes No | Yes |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 3500 |
| Est Cost Prop Damage | 6000 |
| Est Cost Emergency | 6000 |
| Est Cost Environmental | 0 |
| Est Cost Other | 0 |
| Prpty | 15500 |
| Accident Psig | 200 |
| Mop Psig | 275 |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Length Segment Isolated | 2600 |
| Internal Inspection Ind | Yes |
| Operation Complications Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | Yes |
| Cpm In Place Ind | Yes |
| Cpm Operating Ind | No |
| Cpm Functional Ind | No |
| Cpm Detection Ind | No |
| Cpm Conf Ind | No |
| Investigation Status | Yes, specify investigation result(s): (select all that apply) |
| Invest No Controller Ind | Yes |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Equipment Failure |
| Cause Details | Non-Threaded Connection Failure |
| Eq Failure Type | Non-Threaded Connection Failure |
| Other Non Threaded Ind | Gasket |
| Additional Overpressure Ind | Yes |
| Preparer Name | H**** M**** |
| Preparer Title | Senior Regulatory Compliance Specialist |
| Preparer Email | H************@t******.com |
| Preparer Telephone | 210-626-4901 |
| Prepared Date | 2016-04-18 00:00:00 |
| Authorizer Name | A**** W* M******* |
| Authorizer Telephone | 210-626-6343 |
| Authorizer Title | Director Compliance-Logistics |
| Authorizer Email | A***************@t******.com |
| Narrative | On september 16, 2015 a contractor working at the tesoro long beach terminal (lbt) noted vacuum gas oil (vgo) in the secondary containment of the aboveground piping vault. Pipelines running through the vault were idle when the loss of containment was discovered. There were no injuries or impact to the community. It was calculated from average gauges of the oil and water interface within the vault that approximately 70 bbl of vgo leaked from an isolating flange on mov-824 on the t-14 pipeline and was fully contained within secondary containment. It was immediately cleaned up, and the pipeline returned to service at 09:35 on september 18, 2015. A pressure of at least 200 psi was experienced by the t-14 line on september 15, 2015. However, the exact pressure cannot be determined. The monitoring system at lbt was only configured to register pressures up to 200 psi on the t-14 line. |