HL incident on 2015-06-23 — TX
Operator
Phillips 66 Pipeline Llc
Cause
Equipment Failure
Commodity
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$80,000
Incident datetime
2015-06-23 08:30
Report number
Location
TX
Narrative
As part of an anomoly repair at mp-221 on the borger denver pipeline, a welded sleeve was being installed on the pipeline. The sleeve was being welded on the line, while the line was in operation. The pipeline flow and pressures were set at proper levels per engineering requirements. The welding of the longitudinal welds had been completed. At approximately 08:30 on june 23, 2015, while welding the circumferencial welds on the sleeve, the welders remote unit failed causing the welding unit amps to go to maximum (400 amps). This high amp even caused the welder to blow-though the pipe wall into the line. There was a small release (of gasoline) and a small fire associated with the release. All the released material burned in the fire. The blow-through sealed off and the release stopped with-in seconds after starting. The line was shutdown immediately, and the situation was assessed. Although the pipeline was shutdown, the release had stopped and so there was no need to isolate the section of pipeline since the release had stopped. To repair the section of pipe where the blow-through occurred, eventually it was decided to cut the section of pipe out and replace it. The final restart of the line occurred at approximately 09:30 on saturday, june 27.
Detailed record list
Report Received Date
2015-07-20 00:00:00
Iyear
2015
Report Number
20150262
Supplemental Number
20602
Report Type
Original Final
Operator Id
31684
Name
Phillips 66 Pipeline Llc
Operator Street Address
2331 Citywest Blvd
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77042
Local Datetime
2015-06-23 08:30:00
Location Latitude
38.215783
Location Longitude
-103.562679
Commodity Released Type
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype
Gasoline (Non-Ethanol)
Unintentional Release Bbls
0.01
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Contractor Working For The Operator
Incident Identified Datetime
2015-06-23 08:30:00
System Part Involved
Onshore Pipeline, Including Valve Sites
On Off Shore
Onshore
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2015-06-23 08:30:00
Restart Datetime
2015-06-27 09:30:00
On Site Datetime
2015-06-23 08:30:00
Nrc Rpt Datetime
2015-06-23 09:40:00
Nrc Rpt Num
1120667
Ignite Ind
Yes
Explode Ind
No
Upstream Valve Type Ind
Manual
Downstream Valve Type Ind
Manual
Num Pub Evacuated
0
Pipe Fac Name
Borger-Denver
Segment Name
Bd-01
Onshore State Abbreviation
Co
Onshore Postal Code
81076
Onshore City Name
Not Within A Municipality
Onshore County Name
Crowley
Designated Location
Milepost/valve Station
Designated Name
Mp 221
Federal
No
Location Type
Pipeline Right-Of-Way
Incident Area Type
Underground
Incident Area Subtype
Exposed Due To Excavation
Depth Of Cover
36
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Pipe
Pipe Type
Pipe Body
Pipe Diameter
8
Pipe Wall Thickness
0.156
Pipe Smys
52000
Pipe Specification
Api-5l
Pipe Seam Type
Erw - High Frequency
Pipe Manufacturer
Republic
Pipe Coating Type
Extruded Polyehylene
Installation Year
1971
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Other
Release Type Details
Welding Blow-Through Puncture.
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
0
Est Cost Prop Damage
80000
Est Cost Emergency
0
Est Cost Environmental
0
Est Cost Other
0
Prpty
80000
Accident Psig
600
Mop Psig
1330
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
Yes
Exceed Restriction Ind
No
Phmsa Restriction Ind
Not Mandated
Length Segment Isolated
61560
Internal Inspection Ind
Yes
Operation Complications Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
The pipeline was being operated properly at the time of the incident. The incident was a weld blow-through which occurred in the field. The control center had nothing to do with the incident.
Employee Drug Test Ind
No
Contractor Drug Test Ind
Yes
Num Contractors Tested
1
Num Contractors Failed
0
Cause
Equipment Failure
Cause Details
Other Equipment Failure
Eq Failure Type
Other Equipment Failure
Failure Details
The Welder's Remote Control Unit Failed Which Caused Welding Amps To Go To Maximum (400 Amps) Which Resulted In A Burn-Through On The Pipeline.
Eq Additional Other Ind
Yes
Eq Additional Other Details
It Is Not Clear Why The Welder Remote Unit Failed.
Preparer Name
C**** F*****
Preparer Title
Dot Coordinator
Preparer Email
C*************@p**.com
Preparer Telephone
303-862-1189
Prepared Date
2015-07-20 00:00:00
Authorizer Name
T*** T*****
Authorizer Telephone
832-765-1636
Authorizer Title
Manager Regulatory Compliance
Authorizer Email
T************@p**.com
Narrative
As part of an anomoly repair at mp-221 on the borger denver pipeline, a welded sleeve was being installed on the pipeline. The sleeve was being welded on the line, while the line was in operation. The pipeline flow and pressures were set at proper levels per engineering requirements. The welding of the longitudinal welds had been completed. At approximately 08:30 on june 23, 2015, while welding the circumferencial welds on the sleeve, the welders remote unit failed causing the welding unit amps to go to maximum (400 amps). This high amp even caused the welder to blow-though the pipe wall into the line. There was a small release (of gasoline) and a small fire associated with the release. All the released material burned in the fire. The blow-through sealed off and the release stopped with-in seconds after starting. The line was shutdown immediately, and the situation was assessed. Although the pipeline was shutdown, the release had stopped and so there was no need to isolate the section of pipeline since the release had stopped. To repair the section of pipe where the blow-through occurred, eventually it was decided to cut the section of pipe out and replace it. The final restart of the line occurred at approximately 09:30 on saturday, june 27.
| Report Received Date | 2015-07-20 00:00:00 |
|---|---|
| Iyear | 2015 |
| Report Number | 20150262 |
| Supplemental Number | 20602 |
| Report Type | Original Final |
| Operator Id | 31684 PHMSA Enforcement |
| Name | Phillips 66 Pipeline Llc |
| Operator Street Address | 2331 Citywest Blvd |
| Operator City Name | Houston |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77042 |
| Local Datetime | 2015-06-23 08:30:00 |
| Location Latitude | 38.215783 Google Maps OpenStreetMap |
| Location Longitude | -103.562679 Google Maps OpenStreetMap |
| Commodity Released Type | Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions |
| Commodity Subtype | Gasoline (Non-Ethanol) |
| Unintentional Release Bbls | 0.01 |
| Recovered Bbls | 0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Contractor Working For The Operator |
| Incident Identified Datetime | 2015-06-23 08:30:00 |
| System Part Involved | Onshore Pipeline, Including Valve Sites |
| On Off Shore | Onshore |
| Shutdown Due Accident Ind | Yes |
| Shutdown Datetime | 2015-06-23 08:30:00 |
| Restart Datetime | 2015-06-27 09:30:00 |
| On Site Datetime | 2015-06-23 08:30:00 |
| Nrc Rpt Datetime | 2015-06-23 09:40:00 |
| Nrc Rpt Num | 1120667 NRC Report How to search |
| Ignite Ind | Yes |
| Explode Ind | No |
| Upstream Valve Type Ind | Manual |
| Downstream Valve Type Ind | Manual |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Borger-Denver |
| Segment Name | Bd-01 |
| Onshore State Abbreviation | Co |
| Onshore Postal Code | 81076 |
| Onshore City Name | Not Within A Municipality |
| Onshore County Name | Crowley |
| Designated Location | Milepost/valve Station |
| Designated Name | Mp 221 |
| Federal | No |
| Location Type | Pipeline Right-Of-Way |
| Incident Area Type | Underground |
| Incident Area Subtype | Exposed Due To Excavation |
| Depth Of Cover | 36 |
| Crossing | No |
| Pipe Facility Type | Interstate |
| Item Involved | Pipe |
| Pipe Type | Pipe Body |
| Pipe Diameter | 8 |
| Pipe Wall Thickness | 0.156 |
| Pipe Smys | 52000 |
| Pipe Specification | Api-5l |
| Pipe Seam Type | Erw - High Frequency |
| Pipe Manufacturer | Republic |
| Pipe Coating Type | Extruded Polyehylene |
| Installation Year | 1971 |
| Manufactured Year | Unknown |
| Material Involved | Carbon Steel |
| Release Type | Other |
| Release Type Details | Welding Blow-Through Puncture. |
| Wildlife Impact Ind | No |
| Soil Contamination | No |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | No |
| Commodity Reached Hca | No |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 0 |
| Est Cost Prop Damage | 80000 |
| Est Cost Emergency | 0 |
| Est Cost Environmental | 0 |
| Est Cost Other | 0 |
| Prpty | 80000 |
| Accident Psig | 600 |
| Mop Psig | 1330 |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | Yes |
| Exceed Restriction Ind | No |
| Phmsa Restriction Ind | Not Mandated |
| Length Segment Isolated | 61560 |
| Internal Inspection Ind | Yes |
| Operation Complications Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Cpm In Place Ind | Yes |
| Cpm Operating Ind | Yes |
| Cpm Functional Ind | Yes |
| Cpm Detection Ind | No |
| Cpm Conf Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | The pipeline was being operated properly at the time of the incident. The incident was a weld blow-through which occurred in the field. The control center had nothing to do with the incident. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | Yes |
| Num Contractors Tested | 1 |
| Num Contractors Failed | 0 |
| Cause | Equipment Failure |
| Cause Details | Other Equipment Failure |
| Eq Failure Type | Other Equipment Failure |
| Failure Details | The Welder's Remote Control Unit Failed Which Caused Welding Amps To Go To Maximum (400 Amps) Which Resulted In A Burn-Through On The Pipeline. |
| Eq Additional Other Ind | Yes |
| Eq Additional Other Details | It Is Not Clear Why The Welder Remote Unit Failed. |
| Preparer Name | C**** F***** |
| Preparer Title | Dot Coordinator |
| Preparer Email | C*************@p**.com |
| Preparer Telephone | 303-862-1189 |
| Prepared Date | 2015-07-20 00:00:00 |
| Authorizer Name | T*** T***** |
| Authorizer Telephone | 832-765-1636 |
| Authorizer Title | Manager Regulatory Compliance |
| Authorizer Email | T************@p**.com |
| Narrative | As part of an anomoly repair at mp-221 on the borger denver pipeline, a welded sleeve was being installed on the pipeline. The sleeve was being welded on the line, while the line was in operation. The pipeline flow and pressures were set at proper levels per engineering requirements. The welding of the longitudinal welds had been completed. At approximately 08:30 on june 23, 2015, while welding the circumferencial welds on the sleeve, the welders remote unit failed causing the welding unit amps to go to maximum (400 amps). This high amp even caused the welder to blow-though the pipe wall into the line. There was a small release (of gasoline) and a small fire associated with the release. All the released material burned in the fire. The blow-through sealed off and the release stopped with-in seconds after starting. The line was shutdown immediately, and the situation was assessed. Although the pipeline was shutdown, the release had stopped and so there was no need to isolate the section of pipeline since the release had stopped. To repair the section of pipe where the blow-through occurred, eventually it was decided to cut the section of pipe out and replace it. The final restart of the line occurred at approximately 09:30 on saturday, june 27. |
External Resources
PHMSA pipeline safety insights.
Product
Features
Company
All rights reserved. Copyright © by ClearPHMSA