HL incident on 2015-06-01 — TX
Operator
West Texas Gulf Pipeline Co
Cause
Equipment Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$2,000
Incident datetime
2015-06-01 11:00
Report number
Location
TX
Narrative
During a routine switch from tank #15 to tank #18 at colorado city, the mov on tank #18 failed due to a stripped valve stem nut. Therefore the valve was showing to be in the open position for scada yet was actually closed. This event triggered the manifold relief system and oil backed up the thermal relief line into an atmospheric funnel for the relief valve used for sampling and onto the concrete containment. The mov was repaired and the thermal relief valve funnel was removed and replaced with piping to the sump drain line. The system was evaluated for any additional atmospheric thermal relief valves and all valves were replaced with piping to the sump drain line.
Detailed record list
Report Received Date
2015-07-01 00:00:00
Iyear
2015
Report Number
20150239
Supplemental Number
20802
Report Type
Supplemental Final
Operator Id
22442
Name
West Texas Gulf Pipeline Co
Operator Street Address
1300 Main Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2015-06-01 11:00:00
Location Latitude
32.52944
Location Longitude
-100.83055
Commodity Released Type
Crude Oil
Unintentional Release Bbls
0.71
Recovered Bbls
0.71
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Controller
Operator Type
Operator Employee
Incident Identified Datetime
2015-06-01 11:00:00
System Part Involved
Onshore Terminal/tank Farm Equipment And Piping
On Off Shore
Onshore
Shutdown Due Accident Ind
No
Shutdown Explain
Tank Line Isolated.
On Site Datetime
2015-06-01 11:00:00
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Wtg-Colorado City Station
Segment Name
Colorado City Station Piping
Onshore State Abbreviation
Tx
Onshore Postal Code
79526
Onshore City Name
Colorado City
Onshore County Name
Scurry
Designated Location
Survey Station No.
Designated Name
0+00
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Valve
Valve Type
Relief Valve
Installation Year
2000
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Other
Leak Type Other
Thermal Relief To Containment
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
0
Est Cost Prop Damage
2000
Est Cost Emergency
3000
Est Cost Environmental
0
Est Cost Other
0
Prpty
5000
Accident Psig
267
Mop Psig
285
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
No
Cpm In Place Ind
No
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind
Yes
Invest No Controller Ind
Yes
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Malfunction Of Control/relief Equipment
Eq Failure Type
Malfunction Of Control/relief Equipment
Relief Valve Ind
Yes
Eq Additional Other Ind
Yes
Eq Additional Other Details
Thermal Relief Pop-Off Valve Vented To An Atmospheric Funnel Used For Sampling R
Preparer Name
T*** G* N*******
Preparer Title
Dot Compliance Manager
Preparer Email
T*********@s**************.com
Preparer Telephone
281-637-6576
Preparer Fax
877-917-0448
Prepared Date
2015-10-06 00:00:00
Authorizer Name
T*** G* N*******
Authorizer Telephone
281-637-6576
Authorizer Title
Dot Compliance Manager
Authorizer Email
T*********@s**************.com
Narrative
During a routine switch from tank #15 to tank #18 at colorado city, the mov on tank #18 failed due to a stripped valve stem nut. Therefore the valve was showing to be in the open position for scada yet was actually closed. This event triggered the manifold relief system and oil backed up the thermal relief line into an atmospheric funnel for the relief valve used for sampling and onto the concrete containment. The mov was repaired and the thermal relief valve funnel was removed and replaced with piping to the sump drain line. The system was evaluated for any additional atmospheric thermal relief valves and all valves were replaced with piping to the sump drain line.
| Report Received Date | 2015-07-01 00:00:00 |
|---|---|
| Iyear | 2015 |
| Report Number | 20150239 |
| Supplemental Number | 20802 |
| Report Type | Supplemental Final |
| Operator Id | 22442 PHMSA Enforcement |
| Name | West Texas Gulf Pipeline Co |
| Operator Street Address | 1300 Main Street |
| Operator City Name | Houston |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77002 |
| Local Datetime | 2015-06-01 11:00:00 |
| Location Latitude | 32.52944 Google Maps OpenStreetMap |
| Location Longitude | -100.83055 Google Maps OpenStreetMap |
| Commodity Released Type | Crude Oil |
| Unintentional Release Bbls | 0.71 |
| Recovered Bbls | 0.71 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Controller |
| Operator Type | Operator Employee |
| Incident Identified Datetime | 2015-06-01 11:00:00 |
| System Part Involved | Onshore Terminal/tank Farm Equipment And Piping |
| On Off Shore | Onshore |
| Shutdown Due Accident Ind | No |
| Shutdown Explain | Tank Line Isolated. |
| On Site Datetime | 2015-06-01 11:00:00 |
| Nrc Rpt Num | Nrc Notification Not Required NRC Report How to search |
| Ignite Ind | No |
| Explode Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Wtg-Colorado City Station |
| Segment Name | Colorado City Station Piping |
| Onshore State Abbreviation | Tx |
| Onshore Postal Code | 79526 |
| Onshore City Name | Colorado City |
| Onshore County Name | Scurry |
| Designated Location | Survey Station No. |
| Designated Name | 0+00 |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
| Crossing | No |
| Pipe Facility Type | Interstate |
| Item Involved | Valve |
| Valve Type | Relief Valve |
| Installation Year | 2000 |
| Material Involved | Carbon Steel |
| Release Type | Leak |
| Leak Type | Other |
| Leak Type Other | Thermal Relief To Containment |
| Wildlife Impact Ind | No |
| Soil Contamination | No |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | No |
| Commodity Reached Hca | No |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 0 |
| Est Cost Prop Damage | 2000 |
| Est Cost Emergency | 3000 |
| Est Cost Environmental | 0 |
| Est Cost Other | 0 |
| Prpty | 5000 |
| Accident Psig | 267 |
| Mop Psig | 285 |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | Yes |
| Scada Conf Ind | No |
| Cpm In Place Ind | No |
| Investigation Status | Yes, specify investigation result(s): (select all that apply) |
| Invest No Control Room Ind | Yes |
| Invest No Controller Ind | Yes |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Equipment Failure |
| Cause Details | Malfunction Of Control/relief Equipment |
| Eq Failure Type | Malfunction Of Control/relief Equipment |
| Relief Valve Ind | Yes |
| Eq Additional Other Ind | Yes |
| Eq Additional Other Details | Thermal Relief Pop-Off Valve Vented To An Atmospheric Funnel Used For Sampling R |
| Preparer Name | T*** G* N******* |
| Preparer Title | Dot Compliance Manager |
| Preparer Email | T*********@s**************.com |
| Preparer Telephone | 281-637-6576 |
| Preparer Fax | 877-917-0448 |
| Prepared Date | 2015-10-06 00:00:00 |
| Authorizer Name | T*** G* N******* |
| Authorizer Telephone | 281-637-6576 |
| Authorizer Title | Dot Compliance Manager |
| Authorizer Email | T*********@s**************.com |
| Narrative | During a routine switch from tank #15 to tank #18 at colorado city, the mov on tank #18 failed due to a stripped valve stem nut. Therefore the valve was showing to be in the open position for scada yet was actually closed. This event triggered the manifold relief system and oil backed up the thermal relief line into an atmospheric funnel for the relief valve used for sampling and onto the concrete containment. The mov was repaired and the thermal relief valve funnel was removed and replaced with piping to the sump drain line. The system was evaluated for any additional atmospheric thermal relief valves and all valves were replaced with piping to the sump drain line. |
External Resources
PHMSA pipeline safety insights.
Product
Features
Company
All rights reserved. Copyright © by ClearPHMSA