Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2015-06-02 — TX
Operator
Phillips 66 Pipeline Llc
Cause
Corrosion Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$10,000
Incident datetime
2015-06-02 21:44
Report number
Location
TX
Narrative
A crude oil release was reported to the control center at 21:42 on 06-02-2015 by an individual in the area. The pipeline was shutdown, excavated, examined, repaired and returned to service at 18:30 on 06-04-2015 with a total release of 38 gallons. 06-22-2015 no update, finalized report.
Detailed record list
Report Received Date
2015-06-19 00:00:00
Iyear
2015
Report Number
20150227
Supplemental Number
20538
Report Type
Supplemental Final
Operator Id
31684
Name
Phillips 66 Pipeline Llc
Operator Street Address
2331 Citywest Blvd
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77042
Local Datetime
2015-06-02 21:42:00
Location Latitude
34.882052
Location Longitude
-120.445707
Commodity Released Type
Crude Oil
Unintentional Release Bbls
0.91
Recovered Bbls
0.91
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Notification From Public
Incident Identified Datetime
2015-06-02 21:44:00
System Part Involved
Onshore Pipeline, Including Valve Sites
On Off Shore
Onshore
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2015-06-02 21:44:00
Restart Datetime
2015-06-04 18:30:00
On Site Datetime
2015-06-02 22:00:00
Nrc Rpt Datetime
2015-06-02 22:07:00
Nrc Rpt Num
1118470
Ignite Ind
No
Explode Ind
No
Upstream Valve Type Ind
Remotely Controlled
Downstream Valve Type Ind
Manual
Num Pub Evacuated
0
Pipe Fac Name
Orcutt 8"
Segment Name
Cc-30
Onshore State Abbreviation
Ca
Onshore Postal Code
92455
Onshore City Name
Santa Maria
Onshore County Name
Santa Barbara
Designated Location
Milepost/valve Station
Designated Name
Mp 1.5
Federal
No
Location Type
Pipeline Right-Of-Way
Incident Area Type
Underground
Incident Area Subtype
Under Pavement
Depth Of Cover
42
Crossing
No
Pipe Facility Type
Intrastate
Item Involved
Pipe
Pipe Type
Pipe Body
Pipe Diameter
8.5
Pipe Wall Thickness
0.25
Pipe Smys
35000
Pipe Specification
Grade B
Pipe Seam Type
Erw � Unknown Frequency
Pipe Manufacturer
Unk
Pipe Coating Type
Coal Tar
Installation Year
1952
Manufactured Year
1951
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
High Pop Ind
Yes
High Pop Yes No
Yes
Usa Drinking Ind
Yes
Usa Drinking Yes No
Yes
Usa Ecological Ind
Yes
Usa Ecological Yes No
Yes
Est Cost Oper Paid
5000
Est Cost Gas Released
45
Est Cost Prop Damage
10000
Est Cost Emergency
60000
Est Cost Environmental
5000
Est Cost Other
0
Prpty
80045
Accident Psig
590
Mop Psig
875
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Length Segment Isolated
13200
Internal Inspection Ind
Yes
Operation Complications Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Due to the small size of the release and being discovered early by a third party. The small size of the release could not have been detected by the controller or the scada system.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
External Corrosion
Internal External
External Corrosion
Visual Exam Results
Localized Pitting
Galvanic Corrosion Ind
Yes
Field Exam Basis Ind
Yes
Underground Location
Yes
Under Cathodic Protection Ind
Yes
Cathodic Pro Start Year
1952
Shielding Evident
Yes
Cathodic Survey Type
Yes
Cp Annual Survey Ind
Yes
Cp Annual Survey Year
2015
Prior Damage
No
Collected Data Ind
Yes
Axial Magnetic Flx Lkg Ind
Yes
Axial Recent Year
2010
Has Hydrtst Conduc Before Ind
Yes
Hydrtst Most Rcnt Year
2001
Hydrtst Most Rcnt Pressure
1212
Direct Asmnt Conducted
No
Non Destructive Exam Ind
No
Preparer Name
B**** G****
Preparer Title
Dot Coordinator
Preparer Email
B**********@p**.com
Preparer Telephone
9092413358
Preparer Fax
5622901580
Prepared Date
2015-06-22 00:00:00
Authorizer Name
T*** T*****
Authorizer Telephone
8327651636
Authorizer Title
Manager Regulatory Compliance
Authorizer Email
T************@p**.com
Narrative
A crude oil release was reported to the control center at 21:42 on 06-02-2015 by an individual in the area. The pipeline was shutdown, excavated, examined, repaired and returned to service at 18:30 on 06-04-2015 with a total release of 38 gallons. 06-22-2015 no update, finalized report.
| Report Received Date | 2015-06-19 00:00:00 |
|---|---|
| Iyear | 2015 |
| Report Number | 20150227 |
| Supplemental Number | 20538 |
| Report Type | Supplemental Final |
| Operator Id | 31684 PHMSA Enforcement |
| Name | Phillips 66 Pipeline Llc |
| Operator Street Address | 2331 Citywest Blvd |
| Operator City Name | Houston |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77042 |
| Local Datetime | 2015-06-02 21:42:00 |
| Location Latitude | 34.882052 Google Maps OpenStreetMap |
| Location Longitude | -120.445707 Google Maps OpenStreetMap |
| Commodity Released Type | Crude Oil |
| Unintentional Release Bbls | 0.91 |
| Recovered Bbls | 0.91 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Notification From Public |
| Incident Identified Datetime | 2015-06-02 21:44:00 |
| System Part Involved | Onshore Pipeline, Including Valve Sites |
| On Off Shore | Onshore |
| Shutdown Due Accident Ind | Yes |
| Shutdown Datetime | 2015-06-02 21:44:00 |
| Restart Datetime | 2015-06-04 18:30:00 |
| On Site Datetime | 2015-06-02 22:00:00 |
| Nrc Rpt Datetime | 2015-06-02 22:07:00 |
| Nrc Rpt Num | 1118470 NRC Report How to search |
| Ignite Ind | No |
| Explode Ind | No |
| Upstream Valve Type Ind | Remotely Controlled |
| Downstream Valve Type Ind | Manual |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Orcutt 8" |
| Segment Name | Cc-30 |
| Onshore State Abbreviation | Ca |
| Onshore Postal Code | 92455 |
| Onshore City Name | Santa Maria |
| Onshore County Name | Santa Barbara |
| Designated Location | Milepost/valve Station |
| Designated Name | Mp 1.5 |
| Federal | No |
| Location Type | Pipeline Right-Of-Way |
| Incident Area Type | Underground |
| Incident Area Subtype | Under Pavement |
| Depth Of Cover | 42 |
| Crossing | No |
| Pipe Facility Type | Intrastate |
| Item Involved | Pipe |
| Pipe Type | Pipe Body |
| Pipe Diameter | 8.5 |
| Pipe Wall Thickness | 0.25 |
| Pipe Smys | 35000 |
| Pipe Specification | Grade B |
| Pipe Seam Type | Erw � Unknown Frequency |
| Pipe Manufacturer | Unk |
| Pipe Coating Type | Coal Tar |
| Installation Year | 1952 |
| Manufactured Year | 1951 |
| Material Involved | Carbon Steel |
| Release Type | Leak |
| Leak Type | Pinhole |
| Wildlife Impact Ind | No |
| Soil Contamination | Yes |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | Yes |
| Commodity Reached Hca | Yes |
| High Pop Ind | Yes |
| High Pop Yes No | Yes |
| Usa Drinking Ind | Yes |
| Usa Drinking Yes No | Yes |
| Usa Ecological Ind | Yes |
| Usa Ecological Yes No | Yes |
| Est Cost Oper Paid | 5000 |
| Est Cost Gas Released | 45 |
| Est Cost Prop Damage | 10000 |
| Est Cost Emergency | 60000 |
| Est Cost Environmental | 5000 |
| Est Cost Other | 0 |
| Prpty | 80045 |
| Accident Psig | 590 |
| Mop Psig | 875 |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Length Segment Isolated | 13200 |
| Internal Inspection Ind | Yes |
| Operation Complications Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Cpm In Place Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | Due to the small size of the release and being discovered early by a third party. The small size of the release could not have been detected by the controller or the scada system. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Corrosion Failure |
| Cause Details | External Corrosion |
| Internal External | External Corrosion |
| Visual Exam Results | Localized Pitting |
| Galvanic Corrosion Ind | Yes |
| Field Exam Basis Ind | Yes |
| Underground Location | Yes |
| Under Cathodic Protection Ind | Yes |
| Cathodic Pro Start Year | 1952 |
| Shielding Evident | Yes |
| Cathodic Survey Type | Yes |
| Cp Annual Survey Ind | Yes |
| Cp Annual Survey Year | 2015 |
| Prior Damage | No |
| Collected Data Ind | Yes |
| Axial Magnetic Flx Lkg Ind | Yes |
| Axial Recent Year | 2010 |
| Has Hydrtst Conduc Before Ind | Yes |
| Hydrtst Most Rcnt Year | 2001 |
| Hydrtst Most Rcnt Pressure | 1212 |
| Direct Asmnt Conducted | No |
| Non Destructive Exam Ind | No |
| Preparer Name | B**** G**** |
| Preparer Title | Dot Coordinator |
| Preparer Email | B**********@p**.com |
| Preparer Telephone | 9092413358 |
| Preparer Fax | 5622901580 |
| Prepared Date | 2015-06-22 00:00:00 |
| Authorizer Name | T*** T***** |
| Authorizer Telephone | 8327651636 |
| Authorizer Title | Manager Regulatory Compliance |
| Authorizer Email | T************@p**.com |
| Narrative | A crude oil release was reported to the control center at 21:42 on 06-02-2015 by an individual in the area. The pipeline was shutdown, excavated, examined, repaired and returned to service at 18:30 on 06-04-2015 with a total release of 38 gallons. 06-22-2015 no update, finalized report. |
External Resources
PHMSA pipeline safety insights.
Product
Features
Company