Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2015-04-08 — TX
Operator
Enterprise Products Operating Llc
Cause
Corrosion Failure
Commodity
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$80,000
Incident datetime
2015-04-08 13:00
Report number
Location
TX
Narrative
On 4/8/2015 at 13:00 an enterprise employee noticed an iceball on the ground at the location of a 2" riser at enterprise's mont belvieu facility. The pipeline corridor has several lines, some of which are plant piping. The line was shut down on 4/8/2015 at 16:58 to determine if it was the mont belvieu meter site to enterprise eol line. The line was blown down to 0 psi and then nitrogen was introduced. Nitrogen was found to be present at the 2" riser, giving confirmation that the mont belvieu meter site to enterprise eol line was the one leaking. The line was excavated and a pinhole leak was found on the 2" piping. The pipe with the leak was cut out and was replaced. The line was put back in service on 4/12/2015 at 02:30. At 14:28 on 4/11/2015 the nrc was called after the repair cost was determined to be greater than $50,000 dollars.
Detailed record list
Report Received Date
2015-05-07 00:00:00
Iyear
2015
Report Number
20150164
Supplemental Number
20418
Report Type
Original Final
Operator Id
31618
Name
Enterprise Products Operating Llc
Operator Street Address
1100 Louisiana Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2015-04-11 13:51:00
Location Latitude
29.862472
Location Longitude
-94.905644
Commodity Released Type
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype
Other Hvl
Commodity Details
Y-Grade
Unintentional Release Bbls
5
Intentional Release Bbls
2000
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2015-04-08 13:00:00
System Part Involved
Onshore Pipeline, Including Valve Sites
On Off Shore
Onshore
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2015-04-08 16:58:00
Restart Datetime
2015-04-12 02:30:00
On Site Datetime
2015-04-08 13:00:00
Nrc Rpt Datetime
2015-04-11 14:28:00
Nrc Rpt Num
1113327
Ignite Ind
No
Explode Ind
No
Upstream Valve Type Ind
Remotely Controlled
Downstream Valve Type Ind
Manual
Num Pub Evacuated
0
Pipe Fac Name
Mont Belvieu Meter Site To Enterprise Eol
Segment Name
26
Onshore State Abbreviation
Tx
Onshore Postal Code
77580
Onshore City Name
Mont Belvieu
Onshore County Name
Chambers County
Designated Location
Survey Station No.
Designated Name
19+54
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
10
Crossing
No
Pipe Facility Type
Intrastate
Item Involved
Pipe
Pipe Type
Pipe Body
Pipe Diameter
2.416
Pipe Wall Thickness
0.208
Pipe Smys
Unknown
Pipe Specification
Api-5l
Pipe Seam Type
Other
Pipe Seam Details
Unknown
Pipe Manufacturer
Unknown
Pipe Coating Type
Other
Pipe Coating Details
Polyken Wrap
Installation Year
1981
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
Other Pop Ind
Yes
Other Pop Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
200
Est Cost Prop Damage
80000
Est Cost Emergency
0
Est Cost Environmental
0
Est Cost Other
0
Prpty
80200
Accident Psig
675
Mop Psig
1440
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Length Segment Isolated
6336
Internal Inspection Ind
No
Diameter Change Ind
Yes
Operation Complications Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
No
Cpm In Place Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
The line was not in scada.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
External Corrosion
Internal External
External Corrosion
Visual Exam Results
Localized Pitting
Galvanic Corrosion Ind
Yes
Field Exam Basis Ind
Yes
Underground Location
Yes
Under Cathodic Protection Ind
Yes
Cathodic Pro Start Year
1981
Shielding Evident
No
Cathodic Survey Type
Yes
Cp Annual Survey Ind
Yes
Cp Annual Survey Year
2015
Prior Damage
Yes
Collected Data Ind
No
Has Hydrtst Conduc Before Ind
Yes
Hydrtst Most Rcnt Year
2005
Hydrtst Most Rcnt Pressure
2111
Direct Asmnt Conducted
No
Non Destructive Exam Ind
Yes
Exm Radiography Rcnt Year
2015
Exm Radiography Rcnt Ind
Yes
Preparer Name
R** L**
Preparer Title
Pipeline Compliance Engineer
Preparer Email
R***@e****.com
Preparer Telephone
713-381-6741
Prepared Date
2015-05-07 00:00:00
Authorizer Name
R** L**
Authorizer Telephone
713-381-6741
Authorizer Title
Pipeline Compliance Engineer
Authorizer Email
R***@e****.com
Narrative
On 4/8/2015 at 13:00 an enterprise employee noticed an iceball on the ground at the location of a 2" riser at enterprise's mont belvieu facility. The pipeline corridor has several lines, some of which are plant piping. The line was shut down on 4/8/2015 at 16:58 to determine if it was the mont belvieu meter site to enterprise eol line. The line was blown down to 0 psi and then nitrogen was introduced. Nitrogen was found to be present at the 2" riser, giving confirmation that the mont belvieu meter site to enterprise eol line was the one leaking. The line was excavated and a pinhole leak was found on the 2" piping. The pipe with the leak was cut out and was replaced. The line was put back in service on 4/12/2015 at 02:30. At 14:28 on 4/11/2015 the nrc was called after the repair cost was determined to be greater than $50,000 dollars.
| Report Received Date | 2015-05-07 00:00:00 |
|---|---|
| Iyear | 2015 |
| Report Number | 20150164 |
| Supplemental Number | 20418 |
| Report Type | Original Final |
| Operator Id | 31618 PHMSA Enforcement |
| Name | Enterprise Products Operating Llc |
| Operator Street Address | 1100 Louisiana Street |
| Operator City Name | Houston |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77002 |
| Local Datetime | 2015-04-11 13:51:00 |
| Location Latitude | 29.862472 Google Maps OpenStreetMap |
| Location Longitude | -94.905644 Google Maps OpenStreetMap |
| Commodity Released Type | Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions |
| Commodity Subtype | Other Hvl |
| Commodity Details | Y-Grade |
| Unintentional Release Bbls | 5 |
| Intentional Release Bbls | 2000 |
| Recovered Bbls | 0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Operator Employee |
| Incident Identified Datetime | 2015-04-08 13:00:00 |
| System Part Involved | Onshore Pipeline, Including Valve Sites |
| On Off Shore | Onshore |
| Shutdown Due Accident Ind | Yes |
| Shutdown Datetime | 2015-04-08 16:58:00 |
| Restart Datetime | 2015-04-12 02:30:00 |
| On Site Datetime | 2015-04-08 13:00:00 |
| Nrc Rpt Datetime | 2015-04-11 14:28:00 |
| Nrc Rpt Num | 1113327 NRC Report How to search |
| Ignite Ind | No |
| Explode Ind | No |
| Upstream Valve Type Ind | Remotely Controlled |
| Downstream Valve Type Ind | Manual |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Mont Belvieu Meter Site To Enterprise Eol |
| Segment Name | 26 |
| Onshore State Abbreviation | Tx |
| Onshore Postal Code | 77580 |
| Onshore City Name | Mont Belvieu |
| Onshore County Name | Chambers County |
| Designated Location | Survey Station No. |
| Designated Name | 19+54 |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Underground |
| Incident Area Subtype | Under Soil |
| Depth Of Cover | 10 |
| Crossing | No |
| Pipe Facility Type | Intrastate |
| Item Involved | Pipe |
| Pipe Type | Pipe Body |
| Pipe Diameter | 2.416 |
| Pipe Wall Thickness | 0.208 |
| Pipe Smys | Unknown |
| Pipe Specification | Api-5l |
| Pipe Seam Type | Other |
| Pipe Seam Details | Unknown |
| Pipe Manufacturer | Unknown |
| Pipe Coating Type | Other |
| Pipe Coating Details | Polyken Wrap |
| Installation Year | 1981 |
| Manufactured Year | Unknown |
| Material Involved | Carbon Steel |
| Release Type | Leak |
| Leak Type | Pinhole |
| Wildlife Impact Ind | No |
| Soil Contamination | No |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | Yes |
| Commodity Reached Hca | Yes |
| Other Pop Ind | Yes |
| Other Pop Yes No | Yes |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 200 |
| Est Cost Prop Damage | 80000 |
| Est Cost Emergency | 0 |
| Est Cost Environmental | 0 |
| Est Cost Other | 0 |
| Prpty | 80200 |
| Accident Psig | 675 |
| Mop Psig | 1440 |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Length Segment Isolated | 6336 |
| Internal Inspection Ind | No |
| Diameter Change Ind | Yes |
| Operation Complications Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | No |
| Cpm In Place Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | The line was not in scada. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Corrosion Failure |
| Cause Details | External Corrosion |
| Internal External | External Corrosion |
| Visual Exam Results | Localized Pitting |
| Galvanic Corrosion Ind | Yes |
| Field Exam Basis Ind | Yes |
| Underground Location | Yes |
| Under Cathodic Protection Ind | Yes |
| Cathodic Pro Start Year | 1981 |
| Shielding Evident | No |
| Cathodic Survey Type | Yes |
| Cp Annual Survey Ind | Yes |
| Cp Annual Survey Year | 2015 |
| Prior Damage | Yes |
| Collected Data Ind | No |
| Has Hydrtst Conduc Before Ind | Yes |
| Hydrtst Most Rcnt Year | 2005 |
| Hydrtst Most Rcnt Pressure | 2111 |
| Direct Asmnt Conducted | No |
| Non Destructive Exam Ind | Yes |
| Exm Radiography Rcnt Year | 2015 |
| Exm Radiography Rcnt Ind | Yes |
| Preparer Name | R** L** |
| Preparer Title | Pipeline Compliance Engineer |
| Preparer Email | R***@e****.com |
| Preparer Telephone | 713-381-6741 |
| Prepared Date | 2015-05-07 00:00:00 |
| Authorizer Name | R** L** |
| Authorizer Telephone | 713-381-6741 |
| Authorizer Title | Pipeline Compliance Engineer |
| Authorizer Email | R***@e****.com |
| Narrative | On 4/8/2015 at 13:00 an enterprise employee noticed an iceball on the ground at the location of a 2" riser at enterprise's mont belvieu facility. The pipeline corridor has several lines, some of which are plant piping. The line was shut down on 4/8/2015 at 16:58 to determine if it was the mont belvieu meter site to enterprise eol line. The line was blown down to 0 psi and then nitrogen was introduced. Nitrogen was found to be present at the 2" riser, giving confirmation that the mont belvieu meter site to enterprise eol line was the one leaking. The line was excavated and a pinhole leak was found on the 2" piping. The pipe with the leak was cut out and was replaced. The line was put back in service on 4/12/2015 at 02:30. At 14:28 on 4/11/2015 the nrc was called after the repair cost was determined to be greater than $50,000 dollars. |
External Resources
PHMSA pipeline safety insights.
Product