HL incident on 2015-03-30 — OK

Operator
Magellan Pipeline Company, Lp
Cause
Equipment Failure
Commodity
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$130,000
Incident datetime
2015-03-30 18:10
Report number
Location
OK
Narrative
While conducting an atmospheric corrosion inspection of a mainline block valve, a magellan corrosion technician discovered product on top of water contained inside the valve can. The product was confined to the can and did not impact the surrounding soil. The valve was removed and replaced with a new valve (as the packing on the leaking valve could not be replaced). Other valve sites on the line were inspected for similar problems and no other leaks were discovered. Note: the national response center was notified after it was determined that total cost including repair exceeded the $50,000 amount listed in 49 cfr part 195.52(a)(3), not because of a threat to public safety or the environment.
Detailed record list
Report Received Date
2015-04-28 00:00:00
Iyear
2015
Report Number
20150155
Supplemental Number
20391
Report Type
Original Final
Operator Id
Name
Magellan Pipeline Company, Lp
Operator Street Address
100 West 5th Street
Operator City Name
Tulsa
Operator State Abbreviation
OK
Operator Postal Code
74103
Local Datetime
2015-03-30 17:52:00
Location Latitude
Location Longitude
Commodity Released Type
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype
Diesel, Fuel Oil, Kerosene, Jet Fuel
Unintentional Release Bbls
5
Recovered Bbls
5
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2015-03-30 18:10:00
System Part Involved
Onshore Pipeline, Including Valve Sites
On Off Shore
Onshore
Shutdown Due Accident Ind
No
Shutdown Explain
Line Was Idle When Release Was Discovered
On Site Datetime
2015-03-30 19:20:00
Nrc Rpt Datetime
2015-03-31 14:30:00
Nrc Rpt Num
Ignite Ind
No
Explode Ind
No
Upstream Valve Type Ind
Manual
Downstream Valve Type Ind
Remotely Controlled
Num Pub Evacuated
0
Pipe Fac Name
El Dorado To Wathena Jct. #7-16" Line
Segment Name
6380
Onshore State Abbreviation
Ks
Onshore Postal Code
66097
Onshore City Name
Not Within A Municipality
Onshore County Name
Jefferson
Designated Location
Milepost/valve Station
Designated Name
146.46
Federal
No
Location Type
Pipeline Right-Of-Way
Incident Area Type
Underground
Incident Area Subtype
Other
Incident Area Details
In Underground Valve Can
Depth Of Cover
108
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Valve
Valve Type
Mainline
Valve Mainline Type
Gate
Valve Manufacturer
M & J
Installation Year
1968
Manufactured Year
1968
Material Involved
Material Other Than Carbon Steel
Material Details
Valve Stem Packing Material
Release Type
Leak
Leak Type
Seal Or Packing
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
0
Est Cost Prop Damage
130000
Est Cost Emergency
7000
Est Cost Environmental
5000
Est Cost Other
0
Prpty
142000
Accident Psig
368
Mop Psig
1170
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Length Segment Isolated
137280
Internal Inspection Ind
Yes
Operation Complications Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
No official incident investigation was performed, as release volume was significantly below alarm tolerances (beyond the limits of the controller, cpm or scada system monitoring capabilities).
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Non-Threaded Connection Failure
Eq Failure Type
Non-Threaded Connection Failure
Other Non Threaded Ind
Seal (Not Pump Seal) Or Packing
Eq Additional Other Ind
Yes
Eq Additional Other Details
Valve Stem Packing Failed And Caused Product Weepage Through The Stem Packing
Preparer Name
K****** L* L*******
Preparer Title
Sr. Compliance Coordinator
Preparer Email
K***********@m*********.com
Preparer Telephone
918-574-7315
Preparer Fax
918-574-7377
Prepared Date
2015-04-28 00:00:00
Authorizer Name
K****** L* L*******
Authorizer Telephone
918-574-7315
Authorizer Title
Sr. Compliance Coordinator
Authorizer Email
K***********@m*********.com
Narrative
While conducting an atmospheric corrosion inspection of a mainline block valve, a magellan corrosion technician discovered product on top of water contained inside the valve can. The product was confined to the can and did not impact the surrounding soil. The valve was removed and replaced with a new valve (as the packing on the leaking valve could not be replaced). Other valve sites on the line were inspected for similar problems and no other leaks were discovered. Note: the national response center was notified after it was determined that total cost including repair exceeded the $50,000 amount listed in 49 cfr part 195.52(a)(3), not because of a threat to public safety or the environment.
Report Received Date 2015-04-28 00:00:00
Iyear 2015
Report Number 20150155
Supplemental Number 20391
Report Type Original Final
Operator Id 22610 PHMSA Enforcement
Name Magellan Pipeline Company, Lp
Operator Street Address 100 West 5th Street
Operator City Name Tulsa
Operator State Abbreviation OK
Operator Postal Code 74103
Local Datetime 2015-03-30 17:52:00
Location Latitude 39.37571 Google Maps OpenStreetMap
Location Longitude -95.26018 Google Maps OpenStreetMap
Commodity Released Type Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype Diesel, Fuel Oil, Kerosene, Jet Fuel
Unintentional Release Bbls 5
Recovered Bbls 5
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
Incident Identified Datetime 2015-03-30 18:10:00
System Part Involved Onshore Pipeline, Including Valve Sites
On Off Shore Onshore
Shutdown Due Accident Ind No
Shutdown Explain Line Was Idle When Release Was Discovered
On Site Datetime 2015-03-30 19:20:00
Nrc Rpt Datetime 2015-03-31 14:30:00
Nrc Rpt Num 1112216 NRC Report How to search
Ignite Ind No
Explode Ind No
Upstream Valve Type Ind Manual
Downstream Valve Type Ind Remotely Controlled
Num Pub Evacuated 0
Pipe Fac Name El Dorado To Wathena Jct. #7-16" Line
Segment Name 6380
Onshore State Abbreviation Ks
Onshore Postal Code 66097
Onshore City Name Not Within A Municipality
Onshore County Name Jefferson
Designated Location Milepost/valve Station
Designated Name 146.46
Federal No
Location Type Pipeline Right-Of-Way
Incident Area Type Underground
Incident Area Subtype Other
Incident Area Details In Underground Valve Can
Depth Of Cover 108
Crossing No
Pipe Facility Type Interstate
Item Involved Valve
Valve Type Mainline
Valve Mainline Type Gate
Valve Manufacturer M & J
Installation Year 1968
Manufactured Year 1968
Material Involved Material Other Than Carbon Steel
Material Details Valve Stem Packing Material
Release Type Leak
Leak Type Seal Or Packing
Wildlife Impact Ind No
Soil Contamination No
Long Term Assessment No
Remediation Ind No
Water Contam Ind No
Could Be Hca Yes
Commodity Reached Hca No
Est Cost Oper Paid 0
Est Cost Gas Released 0
Est Cost Prop Damage 130000
Est Cost Emergency 7000
Est Cost Environmental 5000
Est Cost Other 0
Prpty 142000
Accident Psig 368
Mop Psig 1170
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Length Segment Isolated 137280
Internal Inspection Ind Yes
Operation Complications Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Cpm In Place Ind Yes
Cpm Operating Ind Yes
Cpm Functional Ind Yes
Cpm Detection Ind No
Cpm Conf Ind No
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details No official incident investigation was performed, as release volume was significantly below alarm tolerances (beyond the limits of the controller, cpm or scada system monitoring capabilities).
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Equipment Failure
Cause Details Non-Threaded Connection Failure
Eq Failure Type Non-Threaded Connection Failure
Other Non Threaded Ind Seal (Not Pump Seal) Or Packing
Eq Additional Other Ind Yes
Eq Additional Other Details Valve Stem Packing Failed And Caused Product Weepage Through The Stem Packing
Preparer Name K****** L* L*******
Preparer Title Sr. Compliance Coordinator
Preparer Email K***********@m*********.com
Preparer Telephone 918-574-7315
Preparer Fax 918-574-7377
Prepared Date 2015-04-28 00:00:00
Authorizer Name K****** L* L*******
Authorizer Telephone 918-574-7315
Authorizer Title Sr. Compliance Coordinator
Authorizer Email K***********@m*********.com
Narrative While conducting an atmospheric corrosion inspection of a mainline block valve, a magellan corrosion technician discovered product on top of water contained inside the valve can. The product was confined to the can and did not impact the surrounding soil. The valve was removed and replaced with a new valve (as the packing on the leaking valve could not be replaced). Other valve sites on the line were inspected for similar problems and no other leaks were discovered. Note: the national response center was notified after it was determined that total cost including repair exceeded the $50,000 amount listed in 49 cfr part 195.52(a)(3), not because of a threat to public safety or the environment.