Incident details
Operator, cause, commodity and consequences with raw source fields.
GTG incident on 2015-10-16 — TX
Operator
Atmos Energy Corporation - Ky/mid-States (Kentucky)
Cause
Notification Issue
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$93,766
Incident datetime
2015-10-16 11:00
Report number
Location
TX
Narrative
Farmer damaged 8" line wile cleaning and extending pond near his property. The farmer (property owner) did not call 811 to have facilities located prior to excavation. Mueller stop fittings were installed and temporary bypass installed to maintain gas service. First responders and atmos energy emergency responders worked closely together to protect life and property during the entire repair process. Atmos energy was also assisted by 25-30 large industrial customers to help maintain gas service to 12,500 residential and small commercial customers.
Detailed record list
Report Received Date
2015-11-13 00:00:00
Iyear
2015
Report Number
20150135
Supplemental Number
17021
Report Type
Supplemental Final
Operator Id
22476
Name
Atmos Energy Corporation - Ky/mid-States (Kentucky)
Operator Street Address
5430 Lbj Freeway Suite 1800
Operator City Name
Dallas
Operator State Abbreviation
TX
Operator Postal Code
75240
Local Datetime
2015-10-16 11:30:00
Location Latitude
38.19113928
Location Longitude
-85.30107642
Nrc Rpt Num
1131004
Nrc Rpt Datetime
2015-10-16 12:53:00
Commodity Released Type
Natural Gas
Unintentional Release
16500
Intentional Release
0
Accompanying Liquid
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Shutdown Due Accident Ind
No
Shutdown Explain
Bypass Was Built Around Damaged Line To Maintain Service To 12,500 Customers
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
15
Incident Identified Datetime
2015-10-16 11:00:00
On Site Datetime
2015-10-16 11:22:00
On Off Shore
Onshore
Onshore State Abbreviation
Ky
Onshore Postal Code
40065
Onshore City Name
Shelbyville
Onshore County Name
Shelby
Designated Location
Survey Station No.
Designated Name
Lksurv968
Pipe Fac Name
Pim9013308
Federal
No
Location Type
Pipeline Right-Of-Way
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
50
Crossing
No
Pipe Facility Type
Intrastate
System Part Involved
Onshore Pipeline, Including Valve Sites
Item Involved
Pipe
Pipe Type
Pipe Body
Pipe Diameter
8
Pipe Wall Thickness
0.188
Pipe Smys
42000
Pipe Seam Type
Seamless
Pipe Coating Type
Epoxy
Installation Year
1974
Manufactured Year
1973
Material Involved
Carbon Steel
Release Type
Mechanical Puncture
Puncture Axial
2
Puncture Circum
4
Class Location Type
Class 1 Location
Could Be Hca
No
Pir Radius
110
Heat Damage Ind
No
Non Heat Damage Ind
No
Hca Fatalities Ind
No
Est Cost Oper Paid
0
Est Cost Unintentional Release
54058
Est Cost Intentional Release
0
Est Cost Prop Damage
93766
Est Cost Emergency
40185
Est Cost Other
0
Prpty
188009
Accident Psig
380
Mop Psig
394
Mop Cfr Section
192.619(A)(1)
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Upstream Valve Type Ind
Manual
Downstream Valve Type Ind
Manual
Length Segment Isolated
350
Internal Inspection Ind
No
Other Restrictions Ind
Yes
Operation Complications Ind
Yes
Other Complications Ind
Yes
Inspect Comp Details
Pipeline Not Set Up For Internal Insp.
Pipeline Function
Transmission Line Of Distribution System
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Accident Identifier
Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Damage occurred due to excavation damage to pipeline (no locate was requested prior to excavation)
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Excavation Damage
Cause Details
Excavation Damage By Third Party
Ex Party Type
Excavation Damage By Third Party
Prior Notification Ind
No
Notify Cga Dirt
Yes
Private Row Ind
Yes
Private Subtype
Private Easement
Pipeline Easement Row Ind
Yes
Excavator Type
Farmer
Excavator Equipment
Backhoe/trackhoe
Work Performed
Drainage
One Call Notified Ind
No
Root Cause Category
Notification Issue
Root Cause Type
No Notification Made To The One-Call Center/811
Preparer Name
G***** T*****
Preparer Title
Compliance Manager
Preparer Email
G************@a**********.com
Preparer Telephone
270-685-8137
Preparer Fax
270-685-8025
Authorizer Name
G***** T*****
Authorizer Title
Compliance Manager
Authorizer Telephone
270-685-8137
Authorizer Email
G************@a**********.com
Narrative
Farmer damaged 8" line wile cleaning and extending pond near his property. The farmer (property owner) did not call 811 to have facilities located prior to excavation. Mueller stop fittings were installed and temporary bypass installed to maintain gas service. First responders and atmos energy emergency responders worked closely together to protect life and property during the entire repair process. Atmos energy was also assisted by 25-30 large industrial customers to help maintain gas service to 12,500 residential and small commercial customers.
| Report Received Date | 2015-11-13 00:00:00 |
|---|---|
| Iyear | 2015 |
| Report Number | 20150135 |
| Supplemental Number | 17021 |
| Report Type | Supplemental Final |
| Operator Id | 22476 PHMSA Enforcement |
| Name | Atmos Energy Corporation - Ky/mid-States (Kentucky) |
| Operator Street Address | 5430 Lbj Freeway Suite 1800 |
| Operator City Name | Dallas |
| Operator State Abbreviation | TX |
| Operator Postal Code | 75240 |
| Local Datetime | 2015-10-16 11:30:00 |
| Location Latitude | 38.19113928 Google Maps OpenStreetMap |
| Location Longitude | -85.30107642 Google Maps OpenStreetMap |
| Nrc Rpt Num | 1131004 NRC Report How to search |
| Nrc Rpt Datetime | 2015-10-16 12:53:00 |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 16500 |
| Intentional Release | 0 |
| Accompanying Liquid | 0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Shutdown Due Accident Ind | No |
| Shutdown Explain | Bypass Was Built Around Damaged Line To Maintain Service To 12,500 Customers |
| Ignite Ind | No |
| Explode Ind | No |
| Num Pub Evacuated | 15 |
| Incident Identified Datetime | 2015-10-16 11:00:00 |
| On Site Datetime | 2015-10-16 11:22:00 |
| On Off Shore | Onshore |
| Onshore State Abbreviation | Ky |
| Onshore Postal Code | 40065 |
| Onshore City Name | Shelbyville |
| Onshore County Name | Shelby |
| Designated Location | Survey Station No. |
| Designated Name | Lksurv968 |
| Pipe Fac Name | Pim9013308 |
| Federal | No |
| Location Type | Pipeline Right-Of-Way |
| Incident Area Type | Underground |
| Incident Area Subtype | Under Soil |
| Depth Of Cover | 50 |
| Crossing | No |
| Pipe Facility Type | Intrastate |
| System Part Involved | Onshore Pipeline, Including Valve Sites |
| Item Involved | Pipe |
| Pipe Type | Pipe Body |
| Pipe Diameter | 8 |
| Pipe Wall Thickness | 0.188 |
| Pipe Smys | 42000 |
| Pipe Seam Type | Seamless |
| Pipe Coating Type | Epoxy |
| Installation Year | 1974 |
| Manufactured Year | 1973 |
| Material Involved | Carbon Steel |
| Release Type | Mechanical Puncture |
| Puncture Axial | 2 |
| Puncture Circum | 4 |
| Class Location Type | Class 1 Location |
| Could Be Hca | No |
| Pir Radius | 110 |
| Heat Damage Ind | No |
| Non Heat Damage Ind | No |
| Hca Fatalities Ind | No |
| Est Cost Oper Paid | 0 |
| Est Cost Unintentional Release | 54058 |
| Est Cost Intentional Release | 0 |
| Est Cost Prop Damage | 93766 |
| Est Cost Emergency | 40185 |
| Est Cost Other | 0 |
| Prpty | 188009 |
| Accident Psig | 380 |
| Mop Psig | 394 |
| Mop Cfr Section | 192.619(A)(1) View CFR 49 §192 |
| Accident Pressure | Pressure Did Not Exceed Maop |
| Pressure Restriction Ind | No |
| Upstream Valve Type Ind | Manual |
| Downstream Valve Type Ind | Manual |
| Length Segment Isolated | 350 |
| Internal Inspection Ind | No |
| Other Restrictions Ind | Yes |
| Operation Complications Ind | Yes |
| Other Complications Ind | Yes |
| Inspect Comp Details | Pipeline Not Set Up For Internal Insp. |
| Pipeline Function | Transmission Line Of Distribution System |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | Yes |
| Scada Conf Ind | Yes |
| Accident Identifier | Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations) |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | Damage occurred due to excavation damage to pipeline (no locate was requested prior to excavation) |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Excavation Damage |
| Cause Details | Excavation Damage By Third Party |
| Ex Party Type | Excavation Damage By Third Party |
| Prior Notification Ind | No |
| Notify Cga Dirt | Yes |
| Private Row Ind | Yes |
| Private Subtype | Private Easement |
| Pipeline Easement Row Ind | Yes |
| Excavator Type | Farmer |
| Excavator Equipment | Backhoe/trackhoe |
| Work Performed | Drainage |
| One Call Notified Ind | No |
| Root Cause Category | Notification Issue |
| Root Cause Type | No Notification Made To The One-Call Center/811 |
| Preparer Name | G***** T***** |
| Preparer Title | Compliance Manager |
| Preparer Email | G************@a**********.com |
| Preparer Telephone | 270-685-8137 |
| Preparer Fax | 270-685-8025 |
| Authorizer Name | G***** T***** |
| Authorizer Title | Compliance Manager |
| Authorizer Telephone | 270-685-8137 |
| Authorizer Email | G************@a**********.com |
| Narrative | Farmer damaged 8" line wile cleaning and extending pond near his property. The farmer (property owner) did not call 811 to have facilities located prior to excavation. Mueller stop fittings were installed and temporary bypass installed to maintain gas service. First responders and atmos energy emergency responders worked closely together to protect life and property during the entire repair process. Atmos energy was also assisted by 25-30 large industrial customers to help maintain gas service to 12,500 residential and small commercial customers. |