Incident details
Operator, cause, commodity and consequences with raw source fields.
GD incident on 2015-11-27 — MO
Operator
Amerenue
Cause
Pipe, Weld, Or Joint Failure
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$500
Incident datetime
2015-11-27 14:45
Report number
Location
MO, PIKE
Narrative
On 11/27/15 at 13:09, ameren received a report of an outside gas odor at 3404 georgia st, louisiana, mo from the business owner. An ameren gas service worker was dispatched to the location and arrived at 13:19. The service worker talked with the business owner and conducted a leak investigation. Small leaks were found on the above ground piping on each side of the service regulator. The service worker shut off the service at the riser valve, repaired the leaks and then turned the service on and tested his repairs with leak soap solution. He found no leaks and was preparing to go inside to relight customer's equipment and a fire broke out outside at the meterset location at approximately 14:45. The business owner and service worker attempted to extinguish the fire but were unable to do so and 911 was called. The fire spread quickly and the fire departments were unable to extinguish the fire before the building was a total loss. The ignition sources has not been determined. At 16:10 ameren gas personnel arrived, located emergency valves, and conducted bar-hole testing around the perimeter of 3404 georgia and the adjacent strip mall next door. No indications of gas were found. Emergency valves were not utilized due to the building already was engulfed in fire and natural gas was no longer fueling the fire. Once the fire was controlled, the riser was excavated. During excavation of the riser, bubbles began to appear in water within the excavation approximately 24"-30" from where the riser went into the ground. No gas readings could be obtained due to excessive water in the excavation. Ameren crew personnel continued to excavate in order to expose the riser and service pipe and discovered a 1/2" compression coupling leaking on the 1/2" cts pe service. The service was squeezed off at approximately 21:15. This supplemental report was submitted to correct information on part b, part c, part d and part g from previously submitted reports. Although the source of the gas release cannot be conclusively determined, the leaking coupling could not be discounted as a possible source and is therefore identified as the source in this supplemental report.
Detailed record list
Occurred At
2015-11-27 14:45:00
Year
2015
Report Received Date
2015-12-27 00:00:00
Iyear
2015.0
Report Number
20150108.0
Supplemental Number
16463.0
Report Type
Supplemental Final
Operator Id
20050
Name
Amerenue
Operator Street Address
1901 Chouteau
Operator City Name
Saint Louis
Operator State Abbreviation
MO
Operator Postal Code
63103
Local Datetime
2015-11-27 14:45:00
Location Street Address
3404 Georgia St
Location City Name
Louisiana
Location County Name
Pike
Location State Abbreviation
MO
Location Postal Code
63353
Location Latitude
39.43055556
Location Longitude
-91.07305556
Nrc Rpt Datetime
2015-11-27 21:55:00
Nrc Rpt Num
1134407
Commodity Released Type
Natural Gas
Unintentional Release
11.83
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
Yes
Explode Ind
No
Num Pub Evacuated
5.0
Incident Identified Datetime
2015-11-27 14:45:00
On Site Datetime
2015-11-27 13:19:00
Federal
No
Location Type
Private Property
Incident Area Type
Underground
Incident Area Subtype
Under Pavement
Depth Of Cover
30.0
Crossing
No
Pipe Facility Type
Investor Owned
System Part Involved
Service
Pipe Diameter
0.5
Pipe Specification
Unknown
Pipe Manufacturer
Unknown
Material Involved
Plastic
Plastic Type
Polyethylene (Pe)
Plastic Sdr
7
Material Pe Pipe Code
3408
Release Type
Leak
Leak Type
Connection Failure
Class Location Type
Class 3 Location
Est Cost Oper Paid
200000.0
Est Cost Prop Damage
500.0
Est Cost Emergency
4500.0
Est Cost Other
0.0
Est Cost Unintentional Release
60.0
Prpty
205060.0
Commercial Affected
1.0
Industrial Affected
0.0
Residences Affected
0.0
Accident Psig
30.0
Normal Psig
30.0
Mop Psig
40.0
Accident Pressure
Pressure Did Not Exceed Maop
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
No scada-based information assisted with indication of incident.
Employee Drug Test Ind
Yes
Num Employees Tested
1
Num Employees Failed
0
Contractor Drug Test Ind
No
Cause
Pipe, Weld, Or Joint Failure
Cause Details
Mechanical Joint Failure
Pwjf Failure Type
Mechanical Joint Failure
Mec Fitting Involved
Nut Follower
Mec Manufacturer
Continental
Mec Fitting Material
Other
Mec Fitting Material Detail
Materials Joined: 1st Plastic, 2nd Plastic
Additional Other Ind
Yes
Additional Factor Details
No Additional Factors Were Found To Contribute.
Result Material Ind
Yes
Result Material Subtype
Other
Result Material Details
Could Not Determine Subcause For The Coupling Failure.
Hydrotest Conducted Ind
Yes
Hydrotest Conducted Year
2003
Hydrotest Pressure
100
Preparer Name
J** D*****
Preparer Title
Superintendent Gas Operations And Engineering
Preparer Email
J******@a*****.com
Preparer Telephone
636-639-8208
Authorizer Name
P** H*******
Authorizer Title
Superintendent Gas Operations And Engineering
Authorizer Telephone
573-619-3124
Authorizer Email
P********@a*****.com
Narrative
On 11/27/15 at 13:09, ameren received a report of an outside gas odor at 3404 georgia st, louisiana, mo from the business owner. An ameren gas service worker was dispatched to the location and arrived at 13:19. The service worker talked with the business owner and conducted a leak investigation. Small leaks were found on the above ground piping on each side of the service regulator. The service worker shut off the service at the riser valve, repaired the leaks and then turned the service on and tested his repairs with leak soap solution. He found no leaks and was preparing to go inside to relight customer's equipment and a fire broke out outside at the meterset location at approximately 14:45. The business owner and service worker attempted to extinguish the fire but were unable to do so and 911 was called. The fire spread quickly and the fire departments were unable to extinguish the fire before the building was a total loss. The ignition sources has not been determined. At 16:10 ameren gas personnel arrived, located emergency valves, and conducted bar-hole testing around the perimeter of 3404 georgia and the adjacent strip mall next door. No indications of gas were found. Emergency valves were not utilized due to the building already was engulfed in fire and natural gas was no longer fueling the fire. Once the fire was controlled, the riser was excavated. During excavation of the riser, bubbles began to appear in water within the excavation approximately 24"-30" from where the riser went into the ground. No gas readings could be obtained due to excessive water in the excavation. Ameren crew personnel continued to excavate in order to expose the riser and service pipe and discovered a 1/2" compression coupling leaking on the 1/2" cts pe service. The service was squeezed off at approximately 21:15. This supplemental report was submitted to correct information on part b, part c, part d and part g from previously submitted reports. Although the source of the gas release cannot be conclusively determined, the leaking coupling could not be discounted as a possible source and is therefore identified as the source in this supplemental report.
| Occurred At | 2015-11-27 14:45:00 |
|---|---|
| Year | 2015 |
| Report Received Date | 2015-12-27 00:00:00 |
| Iyear | 2015.0 |
| Report Number | 20150108.0 |
| Supplemental Number | 16463.0 |
| Report Type | Supplemental Final |
| Operator Id | 20050 PHMSA Enforcement |
| Name | Amerenue |
| Operator Street Address | 1901 Chouteau |
| Operator City Name | Saint Louis |
| Operator State Abbreviation | MO |
| Operator Postal Code | 63103 |
| Local Datetime | 2015-11-27 14:45:00 |
| Location Street Address | 3404 Georgia St |
| Location City Name | Louisiana |
| Location County Name | Pike |
| Location State Abbreviation | MO |
| Location Postal Code | 63353 |
| Location Latitude | 39.43055556 Google Maps OpenStreetMap |
| Location Longitude | -91.07305556 Google Maps OpenStreetMap |
| Nrc Rpt Datetime | 2015-11-27 21:55:00 |
| Nrc Rpt Num | 1134407 NRC Report How to search |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 11.83 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Ignite Ind | Yes |
| Explode Ind | No |
| Num Pub Evacuated | 5.0 |
| Incident Identified Datetime | 2015-11-27 14:45:00 |
| On Site Datetime | 2015-11-27 13:19:00 |
| Federal | No |
| Location Type | Private Property |
| Incident Area Type | Underground |
| Incident Area Subtype | Under Pavement |
| Depth Of Cover | 30.0 |
| Crossing | No |
| Pipe Facility Type | Investor Owned |
| System Part Involved | Service |
| Pipe Diameter | 0.5 |
| Pipe Specification | Unknown |
| Pipe Manufacturer | Unknown |
| Material Involved | Plastic |
| Plastic Type | Polyethylene (Pe) |
| Plastic Sdr | 7 |
| Material Pe Pipe Code | 3408 |
| Release Type | Leak |
| Leak Type | Connection Failure |
| Class Location Type | Class 3 Location |
| Est Cost Oper Paid | 200000.0 |
| Est Cost Prop Damage | 500.0 |
| Est Cost Emergency | 4500.0 |
| Est Cost Other | 0.0 |
| Est Cost Unintentional Release | 60.0 |
| Prpty | 205060.0 |
| Commercial Affected | 1.0 |
| Industrial Affected | 0.0 |
| Residences Affected | 0.0 |
| Accident Psig | 30.0 |
| Normal Psig | 30.0 |
| Mop Psig | 40.0 |
| Accident Pressure | Pressure Did Not Exceed Maop |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Operator Employee |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | No scada-based information assisted with indication of incident. |
| Employee Drug Test Ind | Yes |
| Num Employees Tested | 1 |
| Num Employees Failed | 0 |
| Contractor Drug Test Ind | No |
| Cause | Pipe, Weld, Or Joint Failure |
| Cause Details | Mechanical Joint Failure |
| Pwjf Failure Type | Mechanical Joint Failure |
| Mec Fitting Involved | Nut Follower |
| Mec Manufacturer | Continental |
| Mec Fitting Material | Other |
| Mec Fitting Material Detail | Materials Joined: 1st Plastic, 2nd Plastic |
| Additional Other Ind | Yes |
| Additional Factor Details | No Additional Factors Were Found To Contribute. |
| Result Material Ind | Yes |
| Result Material Subtype | Other |
| Result Material Details | Could Not Determine Subcause For The Coupling Failure. |
| Hydrotest Conducted Ind | Yes |
| Hydrotest Conducted Year | 2003 |
| Hydrotest Pressure | 100 |
| Preparer Name | J** D***** |
| Preparer Title | Superintendent Gas Operations And Engineering |
| Preparer Email | J******@a*****.com |
| Preparer Telephone | 636-639-8208 |
| Authorizer Name | P** H******* |
| Authorizer Title | Superintendent Gas Operations And Engineering |
| Authorizer Telephone | 573-619-3124 |
| Authorizer Email | P********@a*****.com |
| Narrative | On 11/27/15 at 13:09, ameren received a report of an outside gas odor at 3404 georgia st, louisiana, mo from the business owner. An ameren gas service worker was dispatched to the location and arrived at 13:19. The service worker talked with the business owner and conducted a leak investigation. Small leaks were found on the above ground piping on each side of the service regulator. The service worker shut off the service at the riser valve, repaired the leaks and then turned the service on and tested his repairs with leak soap solution. He found no leaks and was preparing to go inside to relight customer's equipment and a fire broke out outside at the meterset location at approximately 14:45. The business owner and service worker attempted to extinguish the fire but were unable to do so and 911 was called. The fire spread quickly and the fire departments were unable to extinguish the fire before the building was a total loss. The ignition sources has not been determined. At 16:10 ameren gas personnel arrived, located emergency valves, and conducted bar-hole testing around the perimeter of 3404 georgia and the adjacent strip mall next door. No indications of gas were found. Emergency valves were not utilized due to the building already was engulfed in fire and natural gas was no longer fueling the fire. Once the fire was controlled, the riser was excavated. During excavation of the riser, bubbles began to appear in water within the excavation approximately 24"-30" from where the riser went into the ground. No gas readings could be obtained due to excessive water in the excavation. Ameren crew personnel continued to excavate in order to expose the riser and service pipe and discovered a 1/2" compression coupling leaking on the 1/2" cts pe service. The service was squeezed off at approximately 21:15. This supplemental report was submitted to correct information on part b, part c, part d and part g from previously submitted reports. Although the source of the gas release cannot be conclusively determined, the leaking coupling could not be discounted as a possible source and is therefore identified as the source in this supplemental report. |