Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2014-10-21 — OK
Operator
Magellan Pipeline Company, Lp
Cause
Equipment Failure
Commodity
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$200
Incident datetime
2014-10-21 07:30
Report number
Location
OK
Narrative
During shipment of product out of tank into outgoing pipeline, loose product was observed at the tank manifold by local operations personnel. Investigation determined it was coming out of an electical box at the ground area. Tank operations were shut down and response measures taken by the local operations personnel. A technician discovered product migrating from a pinhole in the tank pump fenwall switch thermowell body located downstream of the tank pump and into the liquid tight conduit. The fenwall switch and body were replaced and approximately 6 cubic yards of impacted soil was remediated.
Detailed record list
Report Received Date
2014-11-19 00:00:00
Iyear
2014
Report Number
20140399
Supplemental Number
20050
Report Type
Supplemental Final
Operator Id
22610
Name
Magellan Pipeline Company, Lp
Operator Street Address
100 West 5th Street
Operator City Name
Tulsa
Operator State Abbreviation
OK
Operator Postal Code
74103
Local Datetime
2014-10-21 07:30:00
Location Latitude
38.88162
Location Longitude
-94.74517
Commodity Released Type
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype
Gasoline (Non-Ethanol)
Unintentional Release Bbls
0.71
Recovered Bbls
0.71
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2014-10-21 07:30:00
System Part Involved
Onshore Terminal/tank Farm Equipment And Piping
On Off Shore
Onshore
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2014-10-21 07:30:00
Restart Datetime
2014-10-22 09:00:00
On Site Datetime
2014-10-21 07:30:00
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Olathe Terminal
Segment Name
Terminal #222, Tank 1424
Onshore State Abbreviation
Ks
Onshore Postal Code
66062
Onshore City Name
Olathe
Onshore County Name
Johnson
Designated Location
Milepost/valve Station
Designated Name
0
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Other
Item Involved Details
Tank Pump Fenwall Switch Thermowell Body
Installation Year
2004
Material Involved
Material Other Than Carbon Steel
Material Details
Stainless Steel
Release Type
Leak
Leak Type
Pinhole
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
Yes
Soil Remed Ind
Yes
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
High Pop Ind
Yes
High Pop Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
65
Est Cost Prop Damage
200
Est Cost Emergency
4000
Est Cost Environmental
15000
Est Cost Other
0
Prpty
19265
Accident Psig
60
Mop Psig
275
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
No
Cpm In Place Ind
No
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the accident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Pump Or Pump-Related Equipment
Eq Failure Type
Pump Or Pump-Related Equipment
Other Pump Ind
Other
Other Pump Details
Thermowell Body Housing Fenwall Switch
Eq Additional Other Ind
Yes
Eq Additional Other Details
Normal Wear
Preparer Name
K****** L* L*******
Preparer Title
Sr. Compliance Coordinator
Preparer Email
K***********@m*********.com
Preparer Telephone
918-574-7315
Preparer Fax
918-574-7377
Prepared Date
2015-01-14 00:00:00
Authorizer Name
K****** L* L*******
Authorizer Telephone
918-574-7315
Authorizer Title
Sr. Compliance Coordinator
Authorizer Email
K***********@m*********.com
Narrative
During shipment of product out of tank into outgoing pipeline, loose product was observed at the tank manifold by local operations personnel. Investigation determined it was coming out of an electical box at the ground area. Tank operations were shut down and response measures taken by the local operations personnel. A technician discovered product migrating from a pinhole in the tank pump fenwall switch thermowell body located downstream of the tank pump and into the liquid tight conduit. The fenwall switch and body were replaced and approximately 6 cubic yards of impacted soil was remediated.
| Report Received Date | 2014-11-19 00:00:00 |
|---|---|
| Iyear | 2014 |
| Report Number | 20140399 |
| Supplemental Number | 20050 |
| Report Type | Supplemental Final |
| Operator Id | 22610 PHMSA Enforcement |
| Name | Magellan Pipeline Company, Lp |
| Operator Street Address | 100 West 5th Street |
| Operator City Name | Tulsa |
| Operator State Abbreviation | OK |
| Operator Postal Code | 74103 |
| Local Datetime | 2014-10-21 07:30:00 |
| Location Latitude | 38.88162 Google Maps OpenStreetMap |
| Location Longitude | -94.74517 Google Maps OpenStreetMap |
| Commodity Released Type | Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions |
| Commodity Subtype | Gasoline (Non-Ethanol) |
| Unintentional Release Bbls | 0.71 |
| Recovered Bbls | 0.71 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Operator Employee |
| Incident Identified Datetime | 2014-10-21 07:30:00 |
| System Part Involved | Onshore Terminal/tank Farm Equipment And Piping |
| On Off Shore | Onshore |
| Shutdown Due Accident Ind | Yes |
| Shutdown Datetime | 2014-10-21 07:30:00 |
| Restart Datetime | 2014-10-22 09:00:00 |
| On Site Datetime | 2014-10-21 07:30:00 |
| Nrc Rpt Num | Nrc Notification Not Required NRC Report How to search |
| Ignite Ind | No |
| Explode Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Olathe Terminal |
| Segment Name | Terminal #222, Tank 1424 |
| Onshore State Abbreviation | Ks |
| Onshore Postal Code | 66062 |
| Onshore City Name | Olathe |
| Onshore County Name | Johnson |
| Designated Location | Milepost/valve Station |
| Designated Name | 0 |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
| Crossing | No |
| Pipe Facility Type | Interstate |
| Item Involved | Other |
| Item Involved Details | Tank Pump Fenwall Switch Thermowell Body |
| Installation Year | 2004 |
| Material Involved | Material Other Than Carbon Steel |
| Material Details | Stainless Steel |
| Release Type | Leak |
| Leak Type | Pinhole |
| Wildlife Impact Ind | No |
| Soil Contamination | Yes |
| Long Term Assessment | No |
| Remediation Ind | Yes |
| Soil Remed Ind | Yes |
| Water Contam Ind | No |
| Could Be Hca | Yes |
| Commodity Reached Hca | Yes |
| High Pop Ind | Yes |
| High Pop Yes No | Yes |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 65 |
| Est Cost Prop Damage | 200 |
| Est Cost Emergency | 4000 |
| Est Cost Environmental | 15000 |
| Est Cost Other | 0 |
| Prpty | 19265 |
| Accident Psig | 60 |
| Mop Psig | 275 |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | No |
| Cpm In Place Ind | No |
| Investigation Status | No, the facility was not monitored by a controller(s) at the time of the accident |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Equipment Failure |
| Cause Details | Pump Or Pump-Related Equipment |
| Eq Failure Type | Pump Or Pump-Related Equipment |
| Other Pump Ind | Other |
| Other Pump Details | Thermowell Body Housing Fenwall Switch |
| Eq Additional Other Ind | Yes |
| Eq Additional Other Details | Normal Wear |
| Preparer Name | K****** L* L******* |
| Preparer Title | Sr. Compliance Coordinator |
| Preparer Email | K***********@m*********.com |
| Preparer Telephone | 918-574-7315 |
| Preparer Fax | 918-574-7377 |
| Prepared Date | 2015-01-14 00:00:00 |
| Authorizer Name | K****** L* L******* |
| Authorizer Telephone | 918-574-7315 |
| Authorizer Title | Sr. Compliance Coordinator |
| Authorizer Email | K***********@m*********.com |
| Narrative | During shipment of product out of tank into outgoing pipeline, loose product was observed at the tank manifold by local operations personnel. Investigation determined it was coming out of an electical box at the ground area. Tank operations were shut down and response measures taken by the local operations personnel. A technician discovered product migrating from a pinhole in the tank pump fenwall switch thermowell body located downstream of the tank pump and into the liquid tight conduit. The fenwall switch and body were replaced and approximately 6 cubic yards of impacted soil was remediated. |
External Resources
PHMSA pipeline safety insights.
Product
Features
Company
All rights reserved. Copyright © by ClearPHMSA