HL incident on 2014-10-06 — TX
Operator
Phillips 66 Pipeline Llc
Cause
Corrosion Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$10,000
Incident datetime
2014-10-06 01:43
Report number
Location
TX
Narrative
This failure occurred on the tank manifold piping at the odessa crude terminal and did not affect mainline pipeline operations. The failure mechanism was internal corrosion. The mop in this section of pipe is 285 psig and the line was not overpressured prior to the failure. The section of pipe which failed was isolated, drained and a clamp was installed. To prevent further leakage and excess spill crude recovered via a vacuum truck. To prevent internal corrosion on this line segment in the future, a new section of pipe has been constructed, hydrotested and internally coated. The new pipe segment will be installed by december 1. Update - 12/30/2014 - the section of pipe which corroded and leak has been replaced with a new section of pipe which has been internally coated to prevent internal corrosion (which was the corrosion mechanism of this failure). Update - 5/4/2015 - this is submittal of a supplemental report at the request of jocelyn kerl so as to change the report to the long form which requires more information. No previous submitted information was changed, only new information added per the requirements of the long form.
Detailed record list
Report Received Date
2014-11-05 00:00:00
Iyear
2014
Report Number
20140389
Supplemental Number
20404
Report Type
Supplemental Final
Operator Id
31684
Name
Phillips 66 Pipeline Llc
Operator Street Address
2331 Citywest Blvd
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77042
Local Datetime
2014-10-06 01:43:00
Location Latitude
31.950527
Location Longitude
-102.603994
Commodity Released Type
Crude Oil
Unintentional Release Bbls
0.44
Recovered Bbls
0.25
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2014-10-06 01:43:00
System Part Involved
Onshore Terminal/tank Farm Equipment And Piping
On Off Shore
Onshore
Shutdown Due Accident Ind
No
Shutdown Explain
Leak In Terminal Pipe Manifold. Line Isolated, Pipelines Continue To Operate
On Site Datetime
2014-10-06 01:43:00
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Odessa Crude Terminal
Segment Name
Manifold
Onshore State Abbreviation
Tx
Onshore Postal Code
79741
Onshore City Name
Goldsmith
Onshore County Name
Ector
Designated Location
Milepost/valve Station
Designated Name
Station
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Pipe
Pipe Type
Pipe Body
Pipe Diameter
16
Pipe Wall Thickness
0.25
Pipe Smys
42000
Pipe Specification
Api-5l X-42
Pipe Seam Type
Seamless
Pipe Manufacturer
Unknown
Pipe Coating Type
Paint
Installation Year
Unknown
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
Yes
Soil Remed Ind
Yes
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
50
Est Cost Prop Damage
10000
Est Cost Emergency
0
Est Cost Environmental
5000
Est Cost Other
0
Prpty
15050
Accident Psig
65
Mop Psig
275
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
< 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
This was an internal corrosion issue, so controller actions could not have contributed to the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
Internal Corrosion
Internal External
Internal Corrosion
Int Visual Exam Results
Localized Pitting
Int Microbiological Ind
Yes
Int Field Exam Basis Ind
Yes
Int Metallurgical Basis Ind
Yes
Int Low Point Pipe Loc Ind
Yes
Corrosion Inhibitors
Yes
Corrosion Lining
No
Cleaning Dewatering
Not Applicable - Not Mainline Pipe
Corrosion Coupons
Not Applicable - Not Mainline Pipe
Collected Data Ind
No
Has Hydrtst Conduc Before Ind
No
Direct Asmnt Conducted
No
Non Destructive Exam Ind
No
Preparer Name
C**** F*****
Preparer Title
Dot Coordinator
Preparer Email
C*************@p**.com
Preparer Telephone
303-862-1189
Preparer Fax
918-977-8545
Prepared Date
2015-05-04 00:00:00
Authorizer Name
T*** T*****
Authorizer Telephone
832-765-1636
Authorizer Title
Mgr. Regulatory Compliance
Authorizer Email
T************@p**.com
Narrative
This failure occurred on the tank manifold piping at the odessa crude terminal and did not affect mainline pipeline operations. The failure mechanism was internal corrosion. The mop in this section of pipe is 285 psig and the line was not overpressured prior to the failure. The section of pipe which failed was isolated, drained and a clamp was installed. To prevent further leakage and excess spill crude recovered via a vacuum truck. To prevent internal corrosion on this line segment in the future, a new section of pipe has been constructed, hydrotested and internally coated. The new pipe segment will be installed by december 1. Update - 12/30/2014 - the section of pipe which corroded and leak has been replaced with a new section of pipe which has been internally coated to prevent internal corrosion (which was the corrosion mechanism of this failure). Update - 5/4/2015 - this is submittal of a supplemental report at the request of jocelyn kerl so as to change the report to the long form which requires more information. No previous submitted information was changed, only new information added per the requirements of the long form.
| Report Received Date | 2014-11-05 00:00:00 |
|---|---|
| Iyear | 2014 |
| Report Number | 20140389 |
| Supplemental Number | 20404 |
| Report Type | Supplemental Final |
| Operator Id | 31684 PHMSA Enforcement |
| Name | Phillips 66 Pipeline Llc |
| Operator Street Address | 2331 Citywest Blvd |
| Operator City Name | Houston |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77042 |
| Local Datetime | 2014-10-06 01:43:00 |
| Location Latitude | 31.950527 Google Maps OpenStreetMap |
| Location Longitude | -102.603994 Google Maps OpenStreetMap |
| Commodity Released Type | Crude Oil |
| Unintentional Release Bbls | 0.44 |
| Recovered Bbls | 0.25 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Operator Employee |
| Incident Identified Datetime | 2014-10-06 01:43:00 |
| System Part Involved | Onshore Terminal/tank Farm Equipment And Piping |
| On Off Shore | Onshore |
| Shutdown Due Accident Ind | No |
| Shutdown Explain | Leak In Terminal Pipe Manifold. Line Isolated, Pipelines Continue To Operate |
| On Site Datetime | 2014-10-06 01:43:00 |
| Nrc Rpt Num | Nrc Notification Not Required NRC Report How to search |
| Ignite Ind | No |
| Explode Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Odessa Crude Terminal |
| Segment Name | Manifold |
| Onshore State Abbreviation | Tx |
| Onshore Postal Code | 79741 |
| Onshore City Name | Goldsmith |
| Onshore County Name | Ector |
| Designated Location | Milepost/valve Station |
| Designated Name | Station |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
| Crossing | No |
| Pipe Facility Type | Interstate |
| Item Involved | Pipe |
| Pipe Type | Pipe Body |
| Pipe Diameter | 16 |
| Pipe Wall Thickness | 0.25 |
| Pipe Smys | 42000 |
| Pipe Specification | Api-5l X-42 |
| Pipe Seam Type | Seamless |
| Pipe Manufacturer | Unknown |
| Pipe Coating Type | Paint |
| Installation Year | Unknown |
| Manufactured Year | Unknown |
| Material Involved | Carbon Steel |
| Release Type | Leak |
| Leak Type | Pinhole |
| Wildlife Impact Ind | No |
| Soil Contamination | Yes |
| Long Term Assessment | No |
| Remediation Ind | Yes |
| Soil Remed Ind | Yes |
| Water Contam Ind | No |
| Could Be Hca | No |
| Commodity Reached Hca | No |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 50 |
| Est Cost Prop Damage | 10000 |
| Est Cost Emergency | 0 |
| Est Cost Environmental | 5000 |
| Est Cost Other | 0 |
| Prpty | 15050 |
| Accident Psig | 65 |
| Mop Psig | 275 |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | < 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Cpm In Place Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | This was an internal corrosion issue, so controller actions could not have contributed to the incident |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Corrosion Failure |
| Cause Details | Internal Corrosion |
| Internal External | Internal Corrosion |
| Int Visual Exam Results | Localized Pitting |
| Int Microbiological Ind | Yes |
| Int Field Exam Basis Ind | Yes |
| Int Metallurgical Basis Ind | Yes |
| Int Low Point Pipe Loc Ind | Yes |
| Corrosion Inhibitors | Yes |
| Corrosion Lining | No |
| Cleaning Dewatering | Not Applicable - Not Mainline Pipe |
| Corrosion Coupons | Not Applicable - Not Mainline Pipe |
| Collected Data Ind | No |
| Has Hydrtst Conduc Before Ind | No |
| Direct Asmnt Conducted | No |
| Non Destructive Exam Ind | No |
| Preparer Name | C**** F***** |
| Preparer Title | Dot Coordinator |
| Preparer Email | C*************@p**.com |
| Preparer Telephone | 303-862-1189 |
| Preparer Fax | 918-977-8545 |
| Prepared Date | 2015-05-04 00:00:00 |
| Authorizer Name | T*** T***** |
| Authorizer Telephone | 832-765-1636 |
| Authorizer Title | Mgr. Regulatory Compliance |
| Authorizer Email | T************@p**.com |
| Narrative | This failure occurred on the tank manifold piping at the odessa crude terminal and did not affect mainline pipeline operations. The failure mechanism was internal corrosion. The mop in this section of pipe is 285 psig and the line was not overpressured prior to the failure. The section of pipe which failed was isolated, drained and a clamp was installed. To prevent further leakage and excess spill crude recovered via a vacuum truck. To prevent internal corrosion on this line segment in the future, a new section of pipe has been constructed, hydrotested and internally coated. The new pipe segment will be installed by december 1. Update - 12/30/2014 - the section of pipe which corroded and leak has been replaced with a new section of pipe which has been internally coated to prevent internal corrosion (which was the corrosion mechanism of this failure). Update - 5/4/2015 - this is submittal of a supplemental report at the request of jocelyn kerl so as to change the report to the long form which requires more information. No previous submitted information was changed, only new information added per the requirements of the long form. |