Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2014-10-03 — TX
Operator
Dcp Midstream
Cause
Natural Force Damage
Commodity
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$0
Incident datetime
2014-10-03 02:15
Report number
Location
TX
Narrative
At approximately 2:15 am, at dcp midstream wilbreeze pump station located near edna, tx, the shutdown valve esd120 inadvertently went closed causing a thermal relief valve to lift and vent approximately 34.6 barrels of ngl to atmosphere. The operator at the houston control center called an ngl technician at approximately 2:30 am to investigate. The ngl technician arrived at the site at 3:20 am and began to investigate the closure and returned the valve to the open position. At approximately 3:30 am, the technician saw a flame on top of the vent stack. It is presumed that static electricity or a lightning strike from a storm in the area ignited the ngl vapors on top of the vent stack. The technician then notified the operations supervisor at approximately 4:01am. The investigation determined that esd120 inadvertently closed due to a transient voltage spike/dip from the bad weather.
Detailed record list
Report Received Date
2014-10-14 00:00:00
Iyear
2014
Report Number
20140364
Supplemental Number
19792
Report Type
Original Final
Operator Id
31130
Name
Dcp Midstream
Operator Street Address
2331 Citywest Blvd. Hq-08-S812-02
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77042
Local Datetime
2014-10-03 02:15:00
Location Latitude
29.08966
Location Longitude
-96.62664
Commodity Released Type
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype
Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid)
Unintentional Release Bbls
34.6
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Cpm Leak Detection System Or Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Calculations)
Incident Identified Datetime
2014-10-03 02:15:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Shutdown Due Accident Ind
No
On Site Datetime
2014-10-03 03:20:00
Nrc Rpt Datetime
2014-10-03 14:43:00
Nrc Rpt Num
1097310
Ignite Ind
Yes
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Wilbreeze Pump Station
Onshore State Abbreviation
Tx
Onshore Postal Code
77957
Onshore City Name
Edna
Onshore County Name
Jackson
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Intrastate
Item Involved
Valve
Valve Type
Mainline
Valve Mainline Type
Ball
Installation Year
2012
Material Involved
Carbon Steel
Release Type
Other
Release Type Details
Inadvertent Closure Of Esd.
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
1500
Est Cost Prop Damage
0
Est Cost Emergency
0
Est Cost Environmental
0
Est Cost Other
0
Prpty
1500
Accident Psig
1344
Mop Psig
1440
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
The cause of the valve closure was weather related, and the controller acted in a timely manner to respond.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Natural Force Damage
Cause Details
Lightning
Natural Force Type
Lightning
Lightning Subtype
Secondary Impact Such As Resulting Nearby Fires
Nf Extreme Weather Ind
No
Preparer Name
T**** S******
Preparer Title
Pipeline Compliance Specialist
Preparer Email
T*******@d***********.com
Preparer Telephone
713-268-7447
Preparer Fax
713-735-3141
Prepared Date
2014-10-13 00:00:00
Authorizer Name
D**** M*****
Authorizer Telephone
303-605-2214
Authorizer Title
Director Of Pipeline Compliance And Integrity
Authorizer Email
D*******@d***********.com
Narrative
At approximately 2:15 am, at dcp midstream wilbreeze pump station located near edna, tx, the shutdown valve esd120 inadvertently went closed causing a thermal relief valve to lift and vent approximately 34.6 barrels of ngl to atmosphere. The operator at the houston control center called an ngl technician at approximately 2:30 am to investigate. The ngl technician arrived at the site at 3:20 am and began to investigate the closure and returned the valve to the open position. At approximately 3:30 am, the technician saw a flame on top of the vent stack. It is presumed that static electricity or a lightning strike from a storm in the area ignited the ngl vapors on top of the vent stack. The technician then notified the operations supervisor at approximately 4:01am. The investigation determined that esd120 inadvertently closed due to a transient voltage spike/dip from the bad weather.
| Report Received Date | 2014-10-14 00:00:00 |
|---|---|
| Iyear | 2014 |
| Report Number | 20140364 |
| Supplemental Number | 19792 |
| Report Type | Original Final |
| Operator Id | 31130 PHMSA Enforcement |
| Name | Dcp Midstream |
| Operator Street Address | 2331 Citywest Blvd. Hq-08-S812-02 |
| Operator City Name | Houston |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77042 |
| Local Datetime | 2014-10-03 02:15:00 |
| Location Latitude | 29.08966 Google Maps OpenStreetMap |
| Location Longitude | -96.62664 Google Maps OpenStreetMap |
| Commodity Released Type | Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions |
| Commodity Subtype | Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid) |
| Unintentional Release Bbls | 34.6 |
| Recovered Bbls | 0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Cpm Leak Detection System Or Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Calculations) |
| Incident Identified Datetime | 2014-10-03 02:15:00 |
| System Part Involved | Onshore Pump/meter Station Equipment And Piping |
| On Off Shore | Onshore |
| Shutdown Due Accident Ind | No |
| On Site Datetime | 2014-10-03 03:20:00 |
| Nrc Rpt Datetime | 2014-10-03 14:43:00 |
| Nrc Rpt Num | 1097310 NRC Report How to search |
| Ignite Ind | Yes |
| Explode Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Wilbreeze Pump Station |
| Onshore State Abbreviation | Tx |
| Onshore Postal Code | 77957 |
| Onshore City Name | Edna |
| Onshore County Name | Jackson |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
| Crossing | No |
| Pipe Facility Type | Intrastate |
| Item Involved | Valve |
| Valve Type | Mainline |
| Valve Mainline Type | Ball |
| Installation Year | 2012 |
| Material Involved | Carbon Steel |
| Release Type | Other |
| Release Type Details | Inadvertent Closure Of Esd. |
| Wildlife Impact Ind | No |
| Soil Contamination | No |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | No |
| Commodity Reached Hca | No |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 1500 |
| Est Cost Prop Damage | 0 |
| Est Cost Emergency | 0 |
| Est Cost Environmental | 0 |
| Est Cost Other | 0 |
| Prpty | 1500 |
| Accident Psig | 1344 |
| Mop Psig | 1440 |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | Yes |
| Scada Conf Ind | Yes |
| Cpm In Place Ind | Yes |
| Cpm Operating Ind | Yes |
| Cpm Functional Ind | Yes |
| Cpm Detection Ind | No |
| Cpm Conf Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | The cause of the valve closure was weather related, and the controller acted in a timely manner to respond. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Natural Force Damage |
| Cause Details | Lightning |
| Natural Force Type | Lightning |
| Lightning Subtype | Secondary Impact Such As Resulting Nearby Fires |
| Nf Extreme Weather Ind | No |
| Preparer Name | T**** S****** |
| Preparer Title | Pipeline Compliance Specialist |
| Preparer Email | T*******@d***********.com |
| Preparer Telephone | 713-268-7447 |
| Preparer Fax | 713-735-3141 |
| Prepared Date | 2014-10-13 00:00:00 |
| Authorizer Name | D**** M***** |
| Authorizer Telephone | 303-605-2214 |
| Authorizer Title | Director Of Pipeline Compliance And Integrity |
| Authorizer Email | D*******@d***********.com |
| Narrative | At approximately 2:15 am, at dcp midstream wilbreeze pump station located near edna, tx, the shutdown valve esd120 inadvertently went closed causing a thermal relief valve to lift and vent approximately 34.6 barrels of ngl to atmosphere. The operator at the houston control center called an ngl technician at approximately 2:30 am to investigate. The ngl technician arrived at the site at 3:20 am and began to investigate the closure and returned the valve to the open position. At approximately 3:30 am, the technician saw a flame on top of the vent stack. It is presumed that static electricity or a lightning strike from a storm in the area ignited the ngl vapors on top of the vent stack. The technician then notified the operations supervisor at approximately 4:01am. The investigation determined that esd120 inadvertently closed due to a transient voltage spike/dip from the bad weather. |
External Resources
PHMSA pipeline safety insights.
Product