HL incident on 2014-07-25 — TX

Operator
Chevron Midstream Pipelines Llc
Cause
Corrosion Failure
Commodity
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$515,262
Incident datetime
2014-07-25 17:00
Report number
Location
TX
Narrative
During the morning of 24jul14, a routine survey detected an intermitted vapor emitting from a casing vent near la-3127 in taft, la. The vapor has been continually monitored and air samples were collected for analysis. At 1700 cdt on 25jul14, it was confirmed that the slow leak was associated with the propylene pp04 line. The line was blocked in utilizing by means of manual valves. The quantity released was found to below the reportable threshold but repair costs were a cause for reporting. The pipe/leak area was exposed to a atmosphere within the annulus between the casing and the pipe. Air movement between the casing and pipe caused moisture/condensation creating a corrosive atmosphere at the point where coating damage was evident. The smart pig run was not on a 5 year interval due to the fact it was not in a hca and therefore was based on chevron's own analysis to run the tool.
Detailed record list
Report Received Date
2014-08-22 00:00:00
Iyear
2014
Report Number
20140300
Supplemental Number
20272
Report Type
Supplemental Final
Operator Id
Name
Chevron Midstream Pipelines Llc
Operator Street Address
1400 Smith St
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2014-07-25 17:00:00
Location Latitude
Location Longitude
Commodity Released Type
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype
Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid)
Unintentional Release Bbls
0.02
Intentional Release Bbls
0
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2014-07-25 17:00:00
System Part Involved
Onshore Pipeline, Including Valve Sites
On Off Shore
Onshore
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2014-07-25 17:00:00
Restart Datetime
2014-08-15 07:00:00
On Site Datetime
2014-07-25 17:00:00
Nrc Rpt Datetime
2014-07-25 18:59:00
Nrc Rpt Num
Ignite Ind
No
Explode Ind
No
Upstream Valve Type Ind
Manual
Downstream Valve Type Ind
Manual
Num Pub Evacuated
0
Pipe Fac Name
Pp04
Segment Name
Tends Pipeline System
Onshore State Abbreviation
La
Onshore Postal Code
70057
Onshore City Name
Hahnville
Onshore County Name
St. Charles
Designated Location
Milepost/valve Station
Designated Name
Milepost 9
Federal
No
Location Type
Pipeline Right-Of-Way
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
Unknown
Crossing
Yes
Road Crossing Ind
Yes
Road Type
Cased
Pipe Facility Type
Intrastate
Item Involved
Pipe
Pipe Type
Pipe Body
Pipe Diameter
6.625
Pipe Wall Thickness
0.25
Pipe Smys
35000
Pipe Specification
Api 5lx Grade B
Pipe Seam Type
Erw - Low Frequency
Pipe Manufacturer
Unkown
Pipe Coating Type
Coal Tar
Installation Year
1966
Manufactured Year
1966
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
7
Est Cost Prop Damage
515262
Est Cost Emergency
0
Est Cost Environmental
0
Est Cost Other
0
Prpty
515269
Accident Psig
840
Mop Psig
1440
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Length Segment Isolated
48576
Internal Inspection Ind
Yes
Operation Complications Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
The leak was so small and slow that it would not be possible for control center personnel to detect the leak.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
External Corrosion
Internal External
External Corrosion
Visual Exam Results
Localized Pitting
Other Corrosion Ind
Yes
Corrosion Type Details
The Pipe/leak Area Was Exposed To A Atmosphere Within The Annulus Between The Casing And The Pipe. Air Movement Between The Casing And Pipe Caused Moisture/condensation Creating A Corrosive Atmosphere At The Point Where Coating Damage Was Evident.
Field Exam Basis Ind
Yes
Underground Location
Yes
Under Cathodic Protection Ind
Yes
Cathodic Pro Start Year
1966
Shielding Evident
Yes
Cathodic Survey Type
Yes
Cp Annual Survey Ind
Yes
Cp Annual Survey Year
2014
Prior Damage
Yes
Collected Data Ind
Yes
Geometry Deformation Ind
Yes
Geometry Recent Year
2009
Other Recent Year
2009
Has Hydrtst Conduc Before Ind
No
Direct Asmnt Conducted
No
Non Destructive Exam Ind
No
Preparer Name
G****** S* P*****
Preparer Title
Dot Specialist
Preparer Email
P******@c******.com
Preparer Telephone
7134326254
Preparer Fax
7134323477
Prepared Date
2015-03-25 00:00:00
Authorizer Name
G****** S* P*****
Authorizer Telephone
7134326254
Authorizer Title
Dot Specialist
Authorizer Email
P******@c******.com
Narrative
During the morning of 24jul14, a routine survey detected an intermitted vapor emitting from a casing vent near la-3127 in taft, la. The vapor has been continually monitored and air samples were collected for analysis. At 1700 cdt on 25jul14, it was confirmed that the slow leak was associated with the propylene pp04 line. The line was blocked in utilizing by means of manual valves. The quantity released was found to below the reportable threshold but repair costs were a cause for reporting. The pipe/leak area was exposed to a atmosphere within the annulus between the casing and the pipe. Air movement between the casing and pipe caused moisture/condensation creating a corrosive atmosphere at the point where coating damage was evident. The smart pig run was not on a 5 year interval due to the fact it was not in a hca and therefore was based on chevron's own analysis to run the tool.
Report Received Date 2014-08-22 00:00:00
Iyear 2014
Report Number 20140300
Supplemental Number 20272
Report Type Supplemental Final
Operator Id 31556 PHMSA Enforcement
Name Chevron Midstream Pipelines Llc
Operator Street Address 1400 Smith St
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Local Datetime 2014-07-25 17:00:00
Location Latitude 29.976335 Google Maps OpenStreetMap
Location Longitude -90.469736 Google Maps OpenStreetMap
Commodity Released Type Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid)
Unintentional Release Bbls 0.02
Intentional Release Bbls 0
Recovered Bbls 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
Incident Identified Datetime 2014-07-25 17:00:00
System Part Involved Onshore Pipeline, Including Valve Sites
On Off Shore Onshore
Shutdown Due Accident Ind Yes
Shutdown Datetime 2014-07-25 17:00:00
Restart Datetime 2014-08-15 07:00:00
On Site Datetime 2014-07-25 17:00:00
Nrc Rpt Datetime 2014-07-25 18:59:00
Nrc Rpt Num 1090285 NRC Report How to search
Ignite Ind No
Explode Ind No
Upstream Valve Type Ind Manual
Downstream Valve Type Ind Manual
Num Pub Evacuated 0
Pipe Fac Name Pp04
Segment Name Tends Pipeline System
Onshore State Abbreviation La
Onshore Postal Code 70057
Onshore City Name Hahnville
Onshore County Name St. Charles
Designated Location Milepost/valve Station
Designated Name Milepost 9
Federal No
Location Type Pipeline Right-Of-Way
Incident Area Type Underground
Incident Area Subtype Under Soil
Depth Of Cover Unknown
Crossing Yes
Road Crossing Ind Yes
Road Type Cased
Pipe Facility Type Intrastate
Item Involved Pipe
Pipe Type Pipe Body
Pipe Diameter 6.625
Pipe Wall Thickness 0.25
Pipe Smys 35000
Pipe Specification Api 5lx Grade B
Pipe Seam Type Erw - Low Frequency
Pipe Manufacturer Unkown
Pipe Coating Type Coal Tar
Installation Year 1966
Manufactured Year 1966
Material Involved Carbon Steel
Release Type Leak
Leak Type Pinhole
Wildlife Impact Ind No
Soil Contamination No
Long Term Assessment No
Remediation Ind No
Water Contam Ind No
Could Be Hca No
Commodity Reached Hca No
Est Cost Oper Paid 0
Est Cost Gas Released 7
Est Cost Prop Damage 515262
Est Cost Emergency 0
Est Cost Environmental 0
Est Cost Other 0
Prpty 515269
Accident Psig 840
Mop Psig 1440
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Length Segment Isolated 48576
Internal Inspection Ind Yes
Operation Complications Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Cpm In Place Ind No
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details The leak was so small and slow that it would not be possible for control center personnel to detect the leak.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Corrosion Failure
Cause Details External Corrosion
Internal External External Corrosion
Visual Exam Results Localized Pitting
Other Corrosion Ind Yes
Corrosion Type Details The Pipe/leak Area Was Exposed To A Atmosphere Within The Annulus Between The Casing And The Pipe. Air Movement Between The Casing And Pipe Caused Moisture/condensation Creating A Corrosive Atmosphere At The Point Where Coating Damage Was Evident.
Field Exam Basis Ind Yes
Underground Location Yes
Under Cathodic Protection Ind Yes
Cathodic Pro Start Year 1966
Shielding Evident Yes
Cathodic Survey Type Yes
Cp Annual Survey Ind Yes
Cp Annual Survey Year 2014
Prior Damage Yes
Collected Data Ind Yes
Geometry Deformation Ind Yes
Geometry Recent Year 2009
Other Recent Year 2009
Has Hydrtst Conduc Before Ind No
Direct Asmnt Conducted No
Non Destructive Exam Ind No
Preparer Name G****** S* P*****
Preparer Title Dot Specialist
Preparer Email P******@c******.com
Preparer Telephone 7134326254
Preparer Fax 7134323477
Prepared Date 2015-03-25 00:00:00
Authorizer Name G****** S* P*****
Authorizer Telephone 7134326254
Authorizer Title Dot Specialist
Authorizer Email P******@c******.com
Narrative During the morning of 24jul14, a routine survey detected an intermitted vapor emitting from a casing vent near la-3127 in taft, la. The vapor has been continually monitored and air samples were collected for analysis. At 1700 cdt on 25jul14, it was confirmed that the slow leak was associated with the propylene pp04 line. The line was blocked in utilizing by means of manual valves. The quantity released was found to below the reportable threshold but repair costs were a cause for reporting. The pipe/leak area was exposed to a atmosphere within the annulus between the casing and the pipe. Air movement between the casing and pipe caused moisture/condensation creating a corrosive atmosphere at the point where coating damage was evident. The smart pig run was not on a 5 year interval due to the fact it was not in a hca and therefore was based on chevron's own analysis to run the tool.

All rights reserved. Copyright © by ClearPHMSA