Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2014-06-21 — TX
Operator
Sfpp, Lp
Cause
Incorrect Operation
Commodity
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$0
Incident datetime
2014-06-21 06:40
Report number
Location
TX
Narrative
On 6/21 while conducting a station walk-around inspection, the operator discovered a release of diesel from a station drainage system open funnel cup at 0640. It was subsequently found that another operator had left a 3/8" water draw valve in the open position after draining breakout tank cc-15. While filling the tank with diesel, the flow from the opened valve overwhelmed the drain line leading to the separator causing the funnel cup to overflow. The release was discovered and the valve was closed at 0642. Agency notifications were made and clean up and excavation was promptly done. Note: part c, #4, tank cc-15 was built in 1984. It is not known if the drain system had been modified since then. Note: part e, #1, pressure estimated from tank head pressure through piping. Note pare e, #2, no mop established for this atmospheric pressure system, however, we listed 275 as typical instation piping. Note: part d, #4, impacted soil removed to 4 feet of depth. Remainder to be included in current rwqcb remediation order.
Detailed record list
Report Received Date
2014-07-07 00:00:00
Iyear
2014
Report Number
20140257
Supplemental Number
19946
Report Type
Supplemental Final
Operator Id
18092
Name
Sfpp, Lp
Operator Street Address
1001 Louisiana St., Suite 1000
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2014-06-21 06:40:00
Location Latitude
38.003663
Location Longitude
-122.056224
Commodity Released Type
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype
Diesel, Fuel Oil, Kerosene, Jet Fuel
Unintentional Release Bbls
7.2
Recovered Bbls
7
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2014-06-21 06:40:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Shutdown Due Accident Ind
No
Shutdown Explain
In-Station Drainage Piping
On Site Datetime
2014-06-21 06:40:00
Nrc Rpt Datetime
2014-06-21 07:32:00
Nrc Rpt Num
1086618
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Concord Station
Onshore State Abbreviation
Ca
Onshore Postal Code
94520
Onshore City Name
Concord
Onshore County Name
Contra Costa
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Auxiliary Piping (E.g. Drain Lines)
Installation Year
1984
Material Involved
Carbon Steel
Release Type
Overfill Or Overflow
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
Yes
Soil Remed Ind
Yes
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
High Pop Ind
Yes
High Pop Yes No
Yes
Usa Drinking Ind
Yes
Usa Drinking Yes No
Yes
Usa Ecological Ind
Yes
Usa Ecological Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
953
Est Cost Prop Damage
0
Est Cost Emergency
16750
Est Cost Environmental
16750
Est Cost Other
0
Prpty
34453
Accident Psig
10
Mop Psig
275
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
< 20% Smys Regulated Transmission
Scada In Place Ind
No
Cpm In Place Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
This field operations' task is not subject to controller influence.
Employee Drug Test Ind
Yes
Contractor Drug Test Ind
No
Num Employees Tested
1
Num Employees Failed
0
Cause
Incorrect Operation
Cause Details
Tank, Vessel, Or Sump/separator Allowed Or Caused To Overfill Or Overflow
Operation Type
Tank, Vessel, Or Sump/separator Allowed Or Caused To Overfill Or Overflow
Overflow Other Ind
Valve Misalignment
Related Failure Follow Ind
Yes
Category Type
Normal Operating Conditions
Operator Qualification Ind
Yes
Qualified Individuals
Yes, They Were Qualified For The Task(S)
Preparer Name
S**** M*******
Preparer Title
Mgr Ccs
Preparer Email
S*************@k***********.com
Preparer Telephone
9098735146
Preparer Fax
3039843620
Prepared Date
2014-12-09 00:00:00
Authorizer Name
E***** A* F***
Authorizer Telephone
7133699454
Authorizer Title
Director Ccs
Authorizer Email
B********@k***********.com
Narrative
On 6/21 while conducting a station walk-around inspection, the operator discovered a release of diesel from a station drainage system open funnel cup at 0640. It was subsequently found that another operator had left a 3/8" water draw valve in the open position after draining breakout tank cc-15. While filling the tank with diesel, the flow from the opened valve overwhelmed the drain line leading to the separator causing the funnel cup to overflow. The release was discovered and the valve was closed at 0642. Agency notifications were made and clean up and excavation was promptly done. Note: part c, #4, tank cc-15 was built in 1984. It is not known if the drain system had been modified since then. Note: part e, #1, pressure estimated from tank head pressure through piping. Note pare e, #2, no mop established for this atmospheric pressure system, however, we listed 275 as typical instation piping. Note: part d, #4, impacted soil removed to 4 feet of depth. Remainder to be included in current rwqcb remediation order.
| Report Received Date | 2014-07-07 00:00:00 |
|---|---|
| Iyear | 2014 |
| Report Number | 20140257 |
| Supplemental Number | 19946 |
| Report Type | Supplemental Final |
| Operator Id | 18092 PHMSA Enforcement |
| Name | Sfpp, Lp |
| Operator Street Address | 1001 Louisiana St., Suite 1000 |
| Operator City Name | Houston |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77002 |
| Local Datetime | 2014-06-21 06:40:00 |
| Location Latitude | 38.003663 Google Maps OpenStreetMap |
| Location Longitude | -122.056224 Google Maps OpenStreetMap |
| Commodity Released Type | Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions |
| Commodity Subtype | Diesel, Fuel Oil, Kerosene, Jet Fuel |
| Unintentional Release Bbls | 7.2 |
| Recovered Bbls | 7 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Operator Employee |
| Incident Identified Datetime | 2014-06-21 06:40:00 |
| System Part Involved | Onshore Pump/meter Station Equipment And Piping |
| On Off Shore | Onshore |
| Shutdown Due Accident Ind | No |
| Shutdown Explain | In-Station Drainage Piping |
| On Site Datetime | 2014-06-21 06:40:00 |
| Nrc Rpt Datetime | 2014-06-21 07:32:00 |
| Nrc Rpt Num | 1086618 NRC Report How to search |
| Ignite Ind | No |
| Explode Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Concord Station |
| Onshore State Abbreviation | Ca |
| Onshore Postal Code | 94520 |
| Onshore City Name | Concord |
| Onshore County Name | Contra Costa |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
| Crossing | No |
| Pipe Facility Type | Interstate |
| Item Involved | Auxiliary Piping (E.g. Drain Lines) |
| Installation Year | 1984 |
| Material Involved | Carbon Steel |
| Release Type | Overfill Or Overflow |
| Wildlife Impact Ind | No |
| Soil Contamination | Yes |
| Long Term Assessment | No |
| Remediation Ind | Yes |
| Soil Remed Ind | Yes |
| Water Contam Ind | No |
| Could Be Hca | Yes |
| Commodity Reached Hca | Yes |
| High Pop Ind | Yes |
| High Pop Yes No | Yes |
| Usa Drinking Ind | Yes |
| Usa Drinking Yes No | Yes |
| Usa Ecological Ind | Yes |
| Usa Ecological Yes No | Yes |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 953 |
| Est Cost Prop Damage | 0 |
| Est Cost Emergency | 16750 |
| Est Cost Environmental | 16750 |
| Est Cost Other | 0 |
| Prpty | 34453 |
| Accident Psig | 10 |
| Mop Psig | 275 |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | < 20% Smys Regulated Transmission |
| Scada In Place Ind | No |
| Cpm In Place Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | This field operations' task is not subject to controller influence. |
| Employee Drug Test Ind | Yes |
| Contractor Drug Test Ind | No |
| Num Employees Tested | 1 |
| Num Employees Failed | 0 |
| Cause | Incorrect Operation |
| Cause Details | Tank, Vessel, Or Sump/separator Allowed Or Caused To Overfill Or Overflow |
| Operation Type | Tank, Vessel, Or Sump/separator Allowed Or Caused To Overfill Or Overflow |
| Overflow Other Ind | Valve Misalignment |
| Related Failure Follow Ind | Yes |
| Category Type | Normal Operating Conditions |
| Operator Qualification Ind | Yes |
| Qualified Individuals | Yes, They Were Qualified For The Task(S) |
| Preparer Name | S**** M******* |
| Preparer Title | Mgr Ccs |
| Preparer Email | S*************@k***********.com |
| Preparer Telephone | 9098735146 |
| Preparer Fax | 3039843620 |
| Prepared Date | 2014-12-09 00:00:00 |
| Authorizer Name | E***** A* F*** |
| Authorizer Telephone | 7133699454 |
| Authorizer Title | Director Ccs |
| Authorizer Email | B********@k***********.com |
| Narrative | On 6/21 while conducting a station walk-around inspection, the operator discovered a release of diesel from a station drainage system open funnel cup at 0640. It was subsequently found that another operator had left a 3/8" water draw valve in the open position after draining breakout tank cc-15. While filling the tank with diesel, the flow from the opened valve overwhelmed the drain line leading to the separator causing the funnel cup to overflow. The release was discovered and the valve was closed at 0642. Agency notifications were made and clean up and excavation was promptly done. Note: part c, #4, tank cc-15 was built in 1984. It is not known if the drain system had been modified since then. Note: part e, #1, pressure estimated from tank head pressure through piping. Note pare e, #2, no mop established for this atmospheric pressure system, however, we listed 275 as typical instation piping. Note: part d, #4, impacted soil removed to 4 feet of depth. Remainder to be included in current rwqcb remediation order. |