Incident details
Operator, cause, commodity and consequences with raw source fields.
GD incident on 2014-11-12 — MS
Operator
Atmos Energy Corporation - Mississippi
Cause
Equipment Failure
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$8,846
Incident datetime
2014-11-12 16:45
Report number
Location
MS, ATTALLA
Narrative
During a change of weather from very warm weather to very cold weather, metal particles in the line were entrained in the gas stream. The metal particles cut and damaged the rubber diaphragm controlling pressure and settled in the pressure reilef pilot. Rising pressure caused the service regulator at a grocery store to fail, which then caused excessive pilot light flames at the appliances inside the store. These flames caused a fire, which damaged the building and contents. The store was closed at that time. There were no evacuations. There were no injuries or deaths.
Detailed record list
Occurred At
2014-11-12 16:45:00
Year
2014
Report Received Date
2014-12-18 00:00:00
Iyear
2014.0
Report Number
20140115.0
Supplemental Number
30562.0
Report Type
Supplemental Final
Operator Id
12582
Name
Atmos Energy Corporation - Mississippi
Operator Street Address
5430 Lbj Freeway Suite 1800
Operator City Name
Dallas
Operator State Abbreviation
TX
Operator Postal Code
75240
Local Datetime
2014-11-12 16:45:00
Location Street Address
516 West Jefferson St
Location City Name
Kosciusko
Location County Name
Attalla
Location State Abbreviation
MS
Location Postal Code
39090
Location Latitude
33.05555
Location Longitude
-89.6013
Nrc Rpt Datetime
2014-11-12 19:16:00
Nrc Rpt Num
1100900
Commodity Released Type
Natural Gas
Unintentional Release
2.0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
Yes
Explode Ind
No
Num Pub Evacuated
0.0
Incident Identified Datetime
2014-11-12 16:45:00
On Site Datetime
2014-11-12 17:15:00
Federal
No
Location Type
Private Property
Incident Area Type
Aboveground
Incident Area Subtype
Inside A Building
Crossing
No
Pipe Facility Type
Other
Pipe Type Other
Investor Owned
System Part Involved
Outside Meter/regulator Set
Material Involved
Other
Material Details
Regualtor Diaphragm
Release Type
Other
Release Type Details
Regulator Diaphragm Failed
Class Location Type
Class 3 Location
Est Cost Oper Paid
115000.0
Est Cost Prop Damage
8846.0
Est Cost Emergency
3701.0
Est Cost Other
6821.0
Est Cost Other Details
Cleanup
Est Cost Unintentional Release
8.0
Prpty
134376.0
Commercial Affected
1.0
Industrial Affected
0.0
Residences Affected
0.0
Accident Psig
250.0
Normal Psig
60.0
Mop Psig
60.0
Accident Pressure
Pressure Exceeded The Applicable Allowance In 192.201
Scada In Place Ind
No
Accident Identifier
Notification From Public
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Malfunction Of Control/relief Equipment
Eq Failure Type
Malfunction Of Control/relief Equipment
Relief Valve Ind
Yes
Pressure Regulator Ind
Yes
Preparer Name
D*** G* M*****
Preparer Title
Manager Of Compliance
Preparer Email
D**********@a**********.com
Preparer Telephone
6015925360
Authorizer Name
D*** D*******
Authorizer Title
Vice President Of Tech Services
Authorizer Telephone
601-420-5030
Authorizer Email
D************@a**********.com
Narrative
During a change of weather from very warm weather to very cold weather, metal particles in the line were entrained in the gas stream. The metal particles cut and damaged the rubber diaphragm controlling pressure and settled in the pressure reilef pilot. Rising pressure caused the service regulator at a grocery store to fail, which then caused excessive pilot light flames at the appliances inside the store. These flames caused a fire, which damaged the building and contents. The store was closed at that time. There were no evacuations. There were no injuries or deaths.
| Occurred At | 2014-11-12 16:45:00 |
|---|---|
| Year | 2014 |
| Report Received Date | 2014-12-18 00:00:00 |
| Iyear | 2014.0 |
| Report Number | 20140115.0 |
| Supplemental Number | 30562.0 |
| Report Type | Supplemental Final |
| Operator Id | 12582 PHMSA Enforcement |
| Name | Atmos Energy Corporation - Mississippi |
| Operator Street Address | 5430 Lbj Freeway Suite 1800 |
| Operator City Name | Dallas |
| Operator State Abbreviation | TX |
| Operator Postal Code | 75240 |
| Local Datetime | 2014-11-12 16:45:00 |
| Location Street Address | 516 West Jefferson St |
| Location City Name | Kosciusko |
| Location County Name | Attalla |
| Location State Abbreviation | MS |
| Location Postal Code | 39090 |
| Location Latitude | 33.05555 Google Maps OpenStreetMap |
| Location Longitude | -89.6013 Google Maps OpenStreetMap |
| Nrc Rpt Datetime | 2014-11-12 19:16:00 |
| Nrc Rpt Num | 1100900 NRC Report How to search |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 2.0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Ignite Ind | Yes |
| Explode Ind | No |
| Num Pub Evacuated | 0.0 |
| Incident Identified Datetime | 2014-11-12 16:45:00 |
| On Site Datetime | 2014-11-12 17:15:00 |
| Federal | No |
| Location Type | Private Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Inside A Building |
| Crossing | No |
| Pipe Facility Type | Other |
| Pipe Type Other | Investor Owned |
| System Part Involved | Outside Meter/regulator Set |
| Material Involved | Other |
| Material Details | Regualtor Diaphragm |
| Release Type | Other |
| Release Type Details | Regulator Diaphragm Failed |
| Class Location Type | Class 3 Location |
| Est Cost Oper Paid | 115000.0 |
| Est Cost Prop Damage | 8846.0 |
| Est Cost Emergency | 3701.0 |
| Est Cost Other | 6821.0 |
| Est Cost Other Details | Cleanup |
| Est Cost Unintentional Release | 8.0 |
| Prpty | 134376.0 |
| Commercial Affected | 1.0 |
| Industrial Affected | 0.0 |
| Residences Affected | 0.0 |
| Accident Psig | 250.0 |
| Normal Psig | 60.0 |
| Mop Psig | 60.0 |
| Accident Pressure | Pressure Exceeded The Applicable Allowance In 192.201 |
| Scada In Place Ind | No |
| Accident Identifier | Notification From Public |
| Investigation Status | No, the facility was not monitored by a controller(s) at the time of the incident |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Equipment Failure |
| Cause Details | Malfunction Of Control/relief Equipment |
| Eq Failure Type | Malfunction Of Control/relief Equipment |
| Relief Valve Ind | Yes |
| Pressure Regulator Ind | Yes |
| Preparer Name | D*** G* M***** |
| Preparer Title | Manager Of Compliance |
| Preparer Email | D**********@a**********.com |
| Preparer Telephone | 6015925360 |
| Authorizer Name | D*** D******* |
| Authorizer Title | Vice President Of Tech Services |
| Authorizer Telephone | 601-420-5030 |
| Authorizer Email | D************@a**********.com |
| Narrative | During a change of weather from very warm weather to very cold weather, metal particles in the line were entrained in the gas stream. The metal particles cut and damaged the rubber diaphragm controlling pressure and settled in the pressure reilef pilot. Rising pressure caused the service regulator at a grocery store to fail, which then caused excessive pilot light flames at the appliances inside the store. These flames caused a fire, which damaged the building and contents. The store was closed at that time. There were no evacuations. There were no injuries or deaths. |