GD incident on 2014-06-02 — KS
Operator
Kansas Gas Service Company, A Division Of One Gas, Inc.
Cause
Incorrect Operation
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities
1 injury
Property damage (nominal)
$7,500
Incident datetime
2014-06-02 15:47
Report number
Location
KS, SHAWNEE
Narrative
On monday, june 2, 2014, three employees were assigned to work on the regulator station in the vault at nw tyler & nw grant. The work involved replacing a weighted lever regulator with a worker/monitor regulator set style of station. The existing regulator was removed and new regulators were installed. Once installed, leakage was discovered on the new regulator station pre-assembled piping. The new station regulators were removed to make repairs. While repairs were being made to the worker/monitor set, it was discovered that a fitting used for one of the control lines was leaking. A welder was requested and dispatched to the work site to repair the leaking fitting. Blind flanges were installed where the new worker/monitor set had been removed and two employees began making a repair to the leaking fitting. A weld cone was installed into the leaking threaded fitting to stop the leak prior to finalizing the repair. During the containment of the leakage, as additional work was being conducted, a small flash fire occurred, causing superficial burns to one of the employees completing the work in the vault. The injured employee was hospitalized overnight to have his injuries examined and to confirm that the burns were external and minor in nature. The following supplemental report changes were made to this incident report - gas distribution system. 6/22/2015 bh page 1, part a, line 10. The total gas lost was 67 cu. Ft. This equates to.067 mcf. Rounding to 2 decimals gives a lost gas quantity of .07 mcf. This value was corrected as part of this supplemental report. Page 2, part a, line 13b. The local time this pipeline/facility was restarted was august 28, 2014 at 13:00 hrs. This time was added to the supplemental report. Page 2, part c, line 4a. This installation was done in 08/1953. The material checkout documentation only lists the pipe diameter and wall thickness. No other specifications were listed so the seam type is unknown. This response remains unknown. Page 3, part d line 2f. We have shown the gas lost as .07 mcf. Our cost of gas at the time of the incident was $6.5132. This equates to a cost of $.45. Since whole dollars are required, the cost of gas lost was $1.00. Page 3, part e, lines 1-3. This was a distribution line operating at 12 ounces. Because the pressure must be shown as psig, the pressure would equate to .75 psig. No changes were made to these lines. Page 4, part g1. This supplemental report corrects the cause of this incident as incorrect operation, part g7. With this change made, the information formerly shown in part g1 has been removed. See part g7 for corrected information. Page 9, part g7, line 1. Other incorrect operation was selected. The incorrect operation was not following procedures. Page 9, part g7, line 2. The selection, failure to follow procedure was selected. Page 9, part g7, line 3. The category type selected was other maintenance. A regulator/full relief valve setting was being replaced with a worker/monitor regulator station and being removed from a vault.
Detailed record list
Occurred At
2014-06-02 15:47:00
Year
2014
Report Received Date
2014-07-01 00:00:00
Iyear
2014.0
Report Number
20140053.0
Supplemental Number
16100.0
Report Type
Supplemental Final
Operator Id
31159
Name
Kansas Gas Service Company, A Division Of One Gas, Inc.
Operator Street Address
7421 W 129th
Operator City Name
Overland Park
Operator State Abbreviation
KS
Operator Postal Code
66213
Local Datetime
2014-06-02 15:47:00
Location Street Address
150'south Of The Intersection Of Nw Grant & Nw Tyler
Location City Name
Topeka
Location County Name
Shawnee
Location State Abbreviation
KS
Location Postal Code
66608
Location Latitude
39.07343
Location Longitude
-95.673023
Nrc Rpt Datetime
2014-06-02 17:10:00
Nrc Rpt Num
1084647
Commodity Released Type
Natural Gas
Unintentional Release
0.07
Fatality Ind
No
Fatal
0
Injury Ind
Yes
Num Emp Injuries
1
Num Contr Injuries
0
Num Er Injuries
0
Num Worker Injuries
0
Num Gp Injuries
0
Injure
1
Ignite Ind
Yes
Explode Ind
No
Num Pub Evacuated
0.0
Incident Identified Datetime
2014-06-02 15:47:00
On Site Datetime
2014-06-02 15:47:00
Federal
No
Location Type
Utility Right-Of-Way / Easement
Incident Area Type
Aboveground
Incident Area Subtype
In Other Enclosed Space
Crossing
No
Pipe Facility Type
Privately Owned
System Part Involved
District Regulator/metering Station
Installation Year
1953.0
Material Involved
Steel
Steel Seam Type
Other
Steel Seam Type Details
Unknown
Wt Steel
0.312
Release Type
Leak
Leak Type
Pinhole
Class Location Type
Class 3 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
7500.0
Est Cost Emergency
5000.0
Est Cost Other
20000.0
Est Cost Other Details
Permanent Repair Of Regulator Station
Est Cost Unintentional Release
1.0
Prpty
32501.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
0.0
Accident Psig
0.75
Normal Psig
0.75
Mop Psig
0.75
Accident Pressure
Pressure Did Not Exceed Maop
Scada In Place Ind
No
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
Yes
Num Employees Tested
2
Num Employees Failed
0
Contractor Drug Test Ind
No
Cause
Incorrect Operation
Cause Details
Other Incorrect Operation
Operation Type
Other Incorrect Operation
Operation Details
Incorrectly Performing A Maintenance Function, Not Following Procedures.
Related Failure Follow Ind
Yes
Category Type
Other Maintenance
Operator Qualification Ind
Yes
Qualified Individuals
Yes, They Were Qualified For The Task(S)
Preparer Name
B*** H******
Preparer Title
Regulatory Compliance Specialist
Preparer Email
B*******@k***.com
Preparer Telephone
785-431-4272
Preparer Fax
785-431-4224
Authorizer Name
R**** S******
Authorizer Title
Director Of Engineering
Authorizer Telephone
785-431-4241
Authorizer Email
R*******@k***.com
Narrative
On monday, june 2, 2014, three employees were assigned to work on the regulator station in the vault at nw tyler & nw grant. The work involved replacing a weighted lever regulator with a worker/monitor regulator set style of station. The existing regulator was removed and new regulators were installed. Once installed, leakage was discovered on the new regulator station pre-assembled piping. The new station regulators were removed to make repairs. While repairs were being made to the worker/monitor set, it was discovered that a fitting used for one of the control lines was leaking. A welder was requested and dispatched to the work site to repair the leaking fitting. Blind flanges were installed where the new worker/monitor set had been removed and two employees began making a repair to the leaking fitting. A weld cone was installed into the leaking threaded fitting to stop the leak prior to finalizing the repair. During the containment of the leakage, as additional work was being conducted, a small flash fire occurred, causing superficial burns to one of the employees completing the work in the vault. The injured employee was hospitalized overnight to have his injuries examined and to confirm that the burns were external and minor in nature. The following supplemental report changes were made to this incident report - gas distribution system. 6/22/2015 bh page 1, part a, line 10. The total gas lost was 67 cu. Ft. This equates to.067 mcf. Rounding to 2 decimals gives a lost gas quantity of .07 mcf. This value was corrected as part of this supplemental report. Page 2, part a, line 13b. The local time this pipeline/facility was restarted was august 28, 2014 at 13:00 hrs. This time was added to the supplemental report. Page 2, part c, line 4a. This installation was done in 08/1953. The material checkout documentation only lists the pipe diameter and wall thickness. No other specifications were listed so the seam type is unknown. This response remains unknown. Page 3, part d line 2f. We have shown the gas lost as .07 mcf. Our cost of gas at the time of the incident was $6.5132. This equates to a cost of $.45. Since whole dollars are required, the cost of gas lost was $1.00. Page 3, part e, lines 1-3. This was a distribution line operating at 12 ounces. Because the pressure must be shown as psig, the pressure would equate to .75 psig. No changes were made to these lines. Page 4, part g1. This supplemental report corrects the cause of this incident as incorrect operation, part g7. With this change made, the information formerly shown in part g1 has been removed. See part g7 for corrected information. Page 9, part g7, line 1. Other incorrect operation was selected. The incorrect operation was not following procedures. Page 9, part g7, line 2. The selection, failure to follow procedure was selected. Page 9, part g7, line 3. The category type selected was other maintenance. A regulator/full relief valve setting was being replaced with a worker/monitor regulator station and being removed from a vault.
| Occurred At | 2014-06-02 15:47:00 |
|---|---|
| Year | 2014 |
| Report Received Date | 2014-07-01 00:00:00 |
| Iyear | 2014.0 |
| Report Number | 20140053.0 |
| Supplemental Number | 16100.0 |
| Report Type | Supplemental Final |
| Operator Id | 31159 PHMSA Enforcement |
| Name | Kansas Gas Service Company, A Division Of One Gas, Inc. |
| Operator Street Address | 7421 W 129th |
| Operator City Name | Overland Park |
| Operator State Abbreviation | KS |
| Operator Postal Code | 66213 |
| Local Datetime | 2014-06-02 15:47:00 |
| Location Street Address | 150'south Of The Intersection Of Nw Grant & Nw Tyler |
| Location City Name | Topeka |
| Location County Name | Shawnee |
| Location State Abbreviation | KS |
| Location Postal Code | 66608 |
| Location Latitude | 39.07343 Google Maps OpenStreetMap |
| Location Longitude | -95.673023 Google Maps OpenStreetMap |
| Nrc Rpt Datetime | 2014-06-02 17:10:00 |
| Nrc Rpt Num | 1084647 NRC Report How to search |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 0.07 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | Yes |
| Num Emp Injuries | 1 |
| Num Contr Injuries | 0 |
| Num Er Injuries | 0 |
| Num Worker Injuries | 0 |
| Num Gp Injuries | 0 |
| Injure | 1 |
| Ignite Ind | Yes |
| Explode Ind | No |
| Num Pub Evacuated | 0.0 |
| Incident Identified Datetime | 2014-06-02 15:47:00 |
| On Site Datetime | 2014-06-02 15:47:00 |
| Federal | No |
| Location Type | Utility Right-Of-Way / Easement |
| Incident Area Type | Aboveground |
| Incident Area Subtype | In Other Enclosed Space |
| Crossing | No |
| Pipe Facility Type | Privately Owned |
| System Part Involved | District Regulator/metering Station |
| Installation Year | 1953.0 |
| Material Involved | Steel |
| Steel Seam Type | Other |
| Steel Seam Type Details | Unknown |
| Wt Steel | 0.312 |
| Release Type | Leak |
| Leak Type | Pinhole |
| Class Location Type | Class 3 Location |
| Est Cost Oper Paid | 0.0 |
| Est Cost Prop Damage | 7500.0 |
| Est Cost Emergency | 5000.0 |
| Est Cost Other | 20000.0 |
| Est Cost Other Details | Permanent Repair Of Regulator Station |
| Est Cost Unintentional Release | 1.0 |
| Prpty | 32501.0 |
| Commercial Affected | 0.0 |
| Industrial Affected | 0.0 |
| Residences Affected | 0.0 |
| Accident Psig | 0.75 |
| Normal Psig | 0.75 |
| Mop Psig | 0.75 |
| Accident Pressure | Pressure Did Not Exceed Maop |
| Scada In Place Ind | No |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Operator Employee |
| Investigation Status | No, the facility was not monitored by a controller(s) at the time of the incident |
| Employee Drug Test Ind | Yes |
| Num Employees Tested | 2 |
| Num Employees Failed | 0 |
| Contractor Drug Test Ind | No |
| Cause | Incorrect Operation |
| Cause Details | Other Incorrect Operation |
| Operation Type | Other Incorrect Operation |
| Operation Details | Incorrectly Performing A Maintenance Function, Not Following Procedures. |
| Related Failure Follow Ind | Yes |
| Category Type | Other Maintenance |
| Operator Qualification Ind | Yes |
| Qualified Individuals | Yes, They Were Qualified For The Task(S) |
| Preparer Name | B*** H****** |
| Preparer Title | Regulatory Compliance Specialist |
| Preparer Email | B*******@k***.com |
| Preparer Telephone | 785-431-4272 |
| Preparer Fax | 785-431-4224 |
| Authorizer Name | R**** S****** |
| Authorizer Title | Director Of Engineering |
| Authorizer Telephone | 785-431-4241 |
| Authorizer Email | R*******@k***.com |
| Narrative | On monday, june 2, 2014, three employees were assigned to work on the regulator station in the vault at nw tyler & nw grant. The work involved replacing a weighted lever regulator with a worker/monitor regulator set style of station. The existing regulator was removed and new regulators were installed. Once installed, leakage was discovered on the new regulator station pre-assembled piping. The new station regulators were removed to make repairs. While repairs were being made to the worker/monitor set, it was discovered that a fitting used for one of the control lines was leaking. A welder was requested and dispatched to the work site to repair the leaking fitting. Blind flanges were installed where the new worker/monitor set had been removed and two employees began making a repair to the leaking fitting. A weld cone was installed into the leaking threaded fitting to stop the leak prior to finalizing the repair. During the containment of the leakage, as additional work was being conducted, a small flash fire occurred, causing superficial burns to one of the employees completing the work in the vault. The injured employee was hospitalized overnight to have his injuries examined and to confirm that the burns were external and minor in nature. The following supplemental report changes were made to this incident report - gas distribution system. 6/22/2015 bh page 1, part a, line 10. The total gas lost was 67 cu. Ft. This equates to.067 mcf. Rounding to 2 decimals gives a lost gas quantity of .07 mcf. This value was corrected as part of this supplemental report. Page 2, part a, line 13b. The local time this pipeline/facility was restarted was august 28, 2014 at 13:00 hrs. This time was added to the supplemental report. Page 2, part c, line 4a. This installation was done in 08/1953. The material checkout documentation only lists the pipe diameter and wall thickness. No other specifications were listed so the seam type is unknown. This response remains unknown. Page 3, part d line 2f. We have shown the gas lost as .07 mcf. Our cost of gas at the time of the incident was $6.5132. This equates to a cost of $.45. Since whole dollars are required, the cost of gas lost was $1.00. Page 3, part e, lines 1-3. This was a distribution line operating at 12 ounces. Because the pressure must be shown as psig, the pressure would equate to .75 psig. No changes were made to these lines. Page 4, part g1. This supplemental report corrects the cause of this incident as incorrect operation, part g7. With this change made, the information formerly shown in part g1 has been removed. See part g7 for corrected information. Page 9, part g7, line 1. Other incorrect operation was selected. The incorrect operation was not following procedures. Page 9, part g7, line 2. The selection, failure to follow procedure was selected. Page 9, part g7, line 3. The category type selected was other maintenance. A regulator/full relief valve setting was being replaced with a worker/monitor regulator station and being removed from a vault. |
External Resources
PHMSA pipeline safety insights.
Product
Features
Company
All rights reserved. Copyright © by ClearPHMSA