Incident details
Operator, cause, commodity and consequences with raw source fields.
GD incident on 2014-02-22 — WA
Operator
Cascade Natural Gas Corp
Cause
Equipment Failure
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$0
Incident datetime
2014-02-22 17:26
Report number
Location
WA, YAKIMA
Narrative
Debris, metal shavings flowing downstream from the pipeline built up in the regulator boot causing it to malfunction.
Detailed record list
Occurred At
2014-02-22 17:26:00
Year
2014
Report Received Date
2014-03-24 00:00:00
Iyear
2014.0
Report Number
20140026.0
Supplemental Number
15828.0
Report Type
Supplemental Final
Operator Id
2128
Name
Cascade Natural Gas Corp
Operator Street Address
8113 W. Grandridge Blvd
Operator City Name
Kennewick
Operator State Abbreviation
WA
Operator Postal Code
99336
Local Datetime
2014-02-22 17:26:00
Location Street Address
S. Camas Behind Wapato Irrigation
Location City Name
Wapato
Location County Name
Yakima
Location State Abbreviation
WA
Location Postal Code
98951
Location Latitude
46.4335
Location Longitude
-120.414
Nrc Rpt Datetime
2014-02-28 18:21:00
Nrc Rpt Num
1075436
Commodity Released Type
Natural Gas
Unintentional Release
4823.75
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0.0
Incident Identified Datetime
2014-02-22 17:26:00
On Site Datetime
2014-02-22 17:45:00
Federal
No
Location Type
Utility Right-Of-Way / Easement
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance (E.g. Value Or Regulator Station, Outdoor Meter Set)
Crossing
No
Pipe Facility Type
Privately Owned
System Part Involved
District Regulator/metering Station
Installation Year
1966.0
Material Involved
Steel
Wt Steel
0.237
Release Type
Leak
Leak Type
Other
Leak Type Other
Debris In Regulator
Class Location Type
Class 2 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
0.0
Est Cost Emergency
290.0
Est Cost Other
0.0
Est Cost Unintentional Release
30388.0
Prpty
30678.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
0.0
Accident Psig
64.0
Normal Psig
56.0
Mop Psig
60.0
Accident Pressure
Pressure Exceeded Maop, But Did Not Exceed The Applicable Allowance In 192.201
Scada In Place Ind
No
Accident Identifier
Notification From Public
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Malfunction Of Control/relief Equipment
Eq Failure Type
Malfunction Of Control/relief Equipment
Pressure Regulator Ind
Yes
Preparer Name
K**** M*******
Preparer Title
Pipeline Safety Specialist
Preparer Email
K*************@c***.com
Preparer Telephone
5097365542
Preparer Fax
5094578112
Authorizer Name
T*** B****
Authorizer Title
Manager Standards And Compliance
Authorizer Telephone
5097344576
Authorizer Email
T*********@c***.com
Narrative
Debris, metal shavings flowing downstream from the pipeline built up in the regulator boot causing it to malfunction.
| Occurred At | 2014-02-22 17:26:00 |
|---|---|
| Year | 2014 |
| Report Received Date | 2014-03-24 00:00:00 |
| Iyear | 2014.0 |
| Report Number | 20140026.0 |
| Supplemental Number | 15828.0 |
| Report Type | Supplemental Final |
| Operator Id | 2128 PHMSA Enforcement |
| Name | Cascade Natural Gas Corp |
| Operator Street Address | 8113 W. Grandridge Blvd |
| Operator City Name | Kennewick |
| Operator State Abbreviation | WA |
| Operator Postal Code | 99336 |
| Local Datetime | 2014-02-22 17:26:00 |
| Location Street Address | S. Camas Behind Wapato Irrigation |
| Location City Name | Wapato |
| Location County Name | Yakima |
| Location State Abbreviation | WA |
| Location Postal Code | 98951 |
| Location Latitude | 46.4335 Google Maps OpenStreetMap |
| Location Longitude | -120.414 Google Maps OpenStreetMap |
| Nrc Rpt Datetime | 2014-02-28 18:21:00 |
| Nrc Rpt Num | 1075436 NRC Report How to search |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 4823.75 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Ignite Ind | No |
| Explode Ind | No |
| Num Pub Evacuated | 0.0 |
| Incident Identified Datetime | 2014-02-22 17:26:00 |
| On Site Datetime | 2014-02-22 17:45:00 |
| Federal | No |
| Location Type | Utility Right-Of-Way / Easement |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance (E.g. Value Or Regulator Station, Outdoor Meter Set) |
| Crossing | No |
| Pipe Facility Type | Privately Owned |
| System Part Involved | District Regulator/metering Station |
| Installation Year | 1966.0 |
| Material Involved | Steel |
| Wt Steel | 0.237 |
| Release Type | Leak |
| Leak Type | Other |
| Leak Type Other | Debris In Regulator |
| Class Location Type | Class 2 Location |
| Est Cost Oper Paid | 0.0 |
| Est Cost Prop Damage | 0.0 |
| Est Cost Emergency | 290.0 |
| Est Cost Other | 0.0 |
| Est Cost Unintentional Release | 30388.0 |
| Prpty | 30678.0 |
| Commercial Affected | 0.0 |
| Industrial Affected | 0.0 |
| Residences Affected | 0.0 |
| Accident Psig | 64.0 |
| Normal Psig | 56.0 |
| Mop Psig | 60.0 |
| Accident Pressure | Pressure Exceeded Maop, But Did Not Exceed The Applicable Allowance In 192.201 |
| Scada In Place Ind | No |
| Accident Identifier | Notification From Public |
| Investigation Status | No, the facility was not monitored by a controller(s) at the time of the incident |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Equipment Failure |
| Cause Details | Malfunction Of Control/relief Equipment |
| Eq Failure Type | Malfunction Of Control/relief Equipment |
| Pressure Regulator Ind | Yes |
| Preparer Name | K**** M******* |
| Preparer Title | Pipeline Safety Specialist |
| Preparer Email | K*************@c***.com |
| Preparer Telephone | 5097365542 |
| Preparer Fax | 5094578112 |
| Authorizer Name | T*** B**** |
| Authorizer Title | Manager Standards And Compliance |
| Authorizer Telephone | 5097344576 |
| Authorizer Email | T*********@c***.com |
| Narrative | Debris, metal shavings flowing downstream from the pipeline built up in the regulator boot causing it to malfunction. |
External Resources
PHMSA pipeline safety insights.
Product
Features
Company
All rights reserved. Copyright © by ClearPHMSA