HL incident on 2013-08-08 — TX

Operator
Sfpp, Lp
Cause
Material Failure Of Pipe Or Weld
Commodity
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$392,745
Incident datetime
2013-08-08 12:42
Report number
Location
TX
Narrative
At 1242, 8/8/13, during a station walk-around inspection, the operator noticed a visual indication from the tank leak sensor system at breakout tank cc 9. There was also a noticeable odor of gasoline near the tank, but no staining. Threatened release notifications were made and local operations began emptying the tank. At 1404, while swabbing the sensor tube, it was discovered that the cables were wet with product and indicated 100% lel. Follow-up release notifications were made and the tank was emptied by 1700 that afternoon. Subsequent investigation found a lap-seam weld cracked most likely due to filling/emptying of this drain-dry style breakout tank. 'note: part a, #6. Original nrc 'threatened release' notification report #1056503 made @ 1304, follow-up nrc report #1056510 made at 1415 confirming the release. 'note: part a, #9. We recovered 1.36 bbls and do not know if the entire amount was recovered because the location of the release was under the tank. The site is under a current rwqcb order and this release is being investigated by that agency therefore, if a better estimate is attained in the future, we will supplement this report. 'note: part e, #6. Tank leak detection system is not associated with the scada system.
Detailed record list
Report Received Date
2013-09-06 00:00:00
Iyear
2013
Report Number
20130304
Supplemental Number
18799
Report Type
Supplemental Final
Operator Id
Name
Sfpp, Lp
Operator Street Address
1001 Louisiana St., Suite 1000
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2013-08-08 12:42:00
Location Latitude
Location Longitude
Commodity Released Type
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype
Gasoline (Non-Ethanol)
Unintentional Release Bbls
1.36
Recovered Bbls
1.36
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2013-08-08 12:42:00
System Part Involved
Onshore Breakout Tank Or Storage Vessel, Including Attached Appurtenances
On Off Shore
Onshore
Shutdown Due Accident Ind
No
On Site Datetime
2013-08-08 12:42:00
Nrc Rpt Datetime
2013-08-08 13:04:00
Nrc Rpt Num
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Concord Station
Segment Name
Inside Pump Station
Onshore State Abbreviation
Ca
Onshore Postal Code
94520
Onshore City Name
Concord
Onshore County Name
Contra Costa
Designated Location
Milepost/valve Station
Designated Name
Concord Sta.
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Tank, Including Attached Appurtenances
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Weld, Including Heat-Affected Zone
Weld Subtype
Other
Weld Details
Tank Bottom Weld-Seam Failure
Tank Type
Atmospheric
Installation Year
1963
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Crack
Leak Type Other
To Be Determined
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
Yes
Remediation Ind
Yes
Soil Remed Ind
Yes
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
High Pop Ind
Yes
High Pop Yes No
Yes
Usa Drinking Ind
Yes
Usa Drinking Yes No
Yes
Usa Ecological Ind
Yes
Usa Ecological Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
168
Est Cost Prop Damage
392745
Est Cost Emergency
20000
Est Cost Environmental
15000
Est Cost Other
0
Prpty
427913
Accident Psig
12.3
Mop Psig
13.8
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
No
Cpm In Place Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
The tank leak detection system is not associated with the scada system and not subject to controller action.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Material Failure Of Pipe Or Weld
Cause Details
Design-, Construction-, Installation-, Or Fabrication-Related
Field Exam Ind
Yes
Failure Type
Design-, Construction-, Installation-, Or Fabrication-Related
Fatigue Vibr Related
Yes
Failure Subtype
Mechanical Vibration
Additional Crack Ind
Yes
Collected Data Ind
No
Has Hydrtst Conduc Before Ind
No
Direct Asmnt Conducted
No
Non Destructive Exam Ind
No
Preparer Name
S**** M*******
Preparer Title
Mgr Ccs Pacific Region
Preparer Email
S*************@k***********.com
Preparer Telephone
909-873-5146
Preparer Fax
303-984-3620
Prepared Date
2013-12-06 00:00:00
Authorizer Name
E***** A* F***
Authorizer Telephone
713-369-9454
Authorizer Title
Dir Ccs
Authorizer Email
B********@k***********.com
Narrative
A***********************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************@ 1304, follow-up nrc report #1056510 made at 1415 confirming the release. 'note: part a, #9. We recovered 1.36 bbls and do not know if the entire amount was recovered because the location of the release was under the tank. The site is under a current rwqcb order and this release is being investigated by that agency therefore, if a better estimate is attained in the future, we will supplement this report. 'note: part e, #6. ******************************************************************.
Report Received Date 2013-09-06 00:00:00
Iyear 2013
Report Number 20130304
Supplemental Number 18799
Report Type Supplemental Final
Operator Id 18092 PHMSA Enforcement
Name Sfpp, Lp
Operator Street Address 1001 Louisiana St., Suite 1000
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Local Datetime 2013-08-08 12:42:00
Location Latitude 38.003663 Google Maps OpenStreetMap
Location Longitude -122.056224 Google Maps OpenStreetMap
Commodity Released Type Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype Gasoline (Non-Ethanol)
Unintentional Release Bbls 1.36
Recovered Bbls 1.36
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
Incident Identified Datetime 2013-08-08 12:42:00
System Part Involved Onshore Breakout Tank Or Storage Vessel, Including Attached Appurtenances
On Off Shore Onshore
Shutdown Due Accident Ind No
On Site Datetime 2013-08-08 12:42:00
Nrc Rpt Datetime 2013-08-08 13:04:00
Nrc Rpt Num 1056503 NRC Report How to search
Ignite Ind No
Explode Ind No
Num Pub Evacuated 0
Pipe Fac Name Concord Station
Segment Name Inside Pump Station
Onshore State Abbreviation Ca
Onshore Postal Code 94520
Onshore City Name Concord
Onshore County Name Contra Costa
Designated Location Milepost/valve Station
Designated Name Concord Sta.
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Tank, Including Attached Appurtenances
Crossing No
Pipe Facility Type Interstate
Item Involved Weld, Including Heat-Affected Zone
Weld Subtype Other
Weld Details Tank Bottom Weld-Seam Failure
Tank Type Atmospheric
Installation Year 1963
Material Involved Carbon Steel
Release Type Leak
Leak Type Crack
Leak Type Other To Be Determined
Wildlife Impact Ind No
Soil Contamination Yes
Long Term Assessment Yes
Remediation Ind Yes
Soil Remed Ind Yes
Water Contam Ind No
Could Be Hca Yes
Commodity Reached Hca Yes
High Pop Ind Yes
High Pop Yes No Yes
Usa Drinking Ind Yes
Usa Drinking Yes No Yes
Usa Ecological Ind Yes
Usa Ecological Yes No Yes
Est Cost Oper Paid 0
Est Cost Gas Released 168
Est Cost Prop Damage 392745
Est Cost Emergency 20000
Est Cost Environmental 15000
Est Cost Other 0
Prpty 427913
Accident Psig 12.3
Mop Psig 13.8
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind No
Cpm In Place Ind No
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details The tank leak detection system is not associated with the scada system and not subject to controller action.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Material Failure Of Pipe Or Weld
Cause Details Design-, Construction-, Installation-, Or Fabrication-Related
Field Exam Ind Yes
Failure Type Design-, Construction-, Installation-, Or Fabrication-Related
Fatigue Vibr Related Yes
Failure Subtype Mechanical Vibration
Additional Crack Ind Yes
Collected Data Ind No
Has Hydrtst Conduc Before Ind No
Direct Asmnt Conducted No
Non Destructive Exam Ind No
Preparer Name S**** M*******
Preparer Title Mgr Ccs Pacific Region
Preparer Email S*************@k***********.com
Preparer Telephone 909-873-5146
Preparer Fax 303-984-3620
Prepared Date 2013-12-06 00:00:00
Authorizer Name E***** A* F***
Authorizer Telephone 713-369-9454
Authorizer Title Dir Ccs
Authorizer Email B********@k***********.com
Narrative A***********************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************@ 1304, follow-up nrc report #1056510 made at 1415 confirming the release. 'note: part a, #9. We recovered 1.36 bbls and do not know if the entire amount was recovered because the location of the release was under the tank. The site is under a current rwqcb order and this release is being investigated by that agency therefore, if a better estimate is attained in the future, we will supplement this report. 'note: part e, #6. ******************************************************************.

All rights reserved. Copyright © by ClearPHMSA