Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2013-05-15 — TX
Operator
Enterprise Products Operating Llc
Cause
Equipment Failure
Commodity
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$15,000
Incident datetime
2013-05-15 11:49
Report number
Location
TX
Narrative
At 08:20 on 5/15/13, a third party operator reported a leak on a valve bonnet at the manual block valve site (milepost 62.5) near levelland, texas. A technician was dispatched and arrived onsite at 09:47. Upon arrival, the technician noticed a minor leak on the valve and attempted to repair the leak. However, the leak could not be stopped and the line was shut-down and blocked in at 10:55. Note: the particular valve in question was not blocked initially. The pipeline was shut down by pipeline control at 1055 consistent with pl control protocol in an effort to reduce the pressure as attempts were made to re-pack the valve that was leaking. Line pressure @ 1055 was approximately 200 psi when repair attempts commenced. At 11:49 it was determined the leak had met the definition of an accident and the estimated cost to repair the leak would exceed $50,000 and the nrc was notified at 12:23 local time. At 08:00 on 5/16/2013, nitrogen inert was injected at levelland station for approximately 23 miles. The valve at milepost 62.5 was removed and replaced with a flanged type valve. The line was restarted at approximately 0035 5/17/2013.
Detailed record list
Report Received Date
2013-06-11 00:00:00
Iyear
2013
Report Number
20130204
Supplemental Number
18182
Report Type
Original Final
Operator Id
31618
Name
Enterprise Products Operating Llc
Operator Street Address
1100 Louisiana Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2013-05-15 11:49:00
Location Latitude
33.5890316
Location Longitude
-102.4290155
Commodity Released Type
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype
Other Hvl
Commodity Details
Propane
Unintentional Release Bbls
1
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Other
Accident Details
Third Party Operator
Incident Identified Datetime
2013-05-15 11:49:00
System Part Involved
Onshore Pipeline, Including Valve Sites
On Off Shore
Onshore
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2013-05-15 11:49:00
Restart Datetime
2013-05-17 00:35:00
On Site Datetime
2013-05-15 11:49:00
Nrc Rpt Datetime
2013-05-15 12:23:00
Nrc Rpt Num
1047225
Ignite Ind
No
Explode Ind
No
Upstream Valve Type Ind
Remotely Controlled
Downstream Valve Type Ind
Manual
Num Pub Evacuated
0
Pipe Fac Name
South Leg Loop (Blue Line)
Segment Name
Lid 220
Onshore State Abbreviation
Tx
Onshore Postal Code
79336
Onshore City Name
Levelland
Onshore County Name
Hockley
Designated Location
Milepost/valve Station
Designated Name
62.5
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Valve
Valve Type
Mainline
Valve Mainline Type
Gate
Valve Manufacturer
M And J
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Seal Or Packing
Leak Type Other
Bonnet O-Ring
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
0
Est Cost Prop Damage
15000
Est Cost Emergency
51000
Est Cost Environmental
0
Est Cost Other
0
Prpty
66000
Accident Psig
300
Mop Psig
1295
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Length Segment Isolated
124000
Internal Inspection Ind
Yes
Operation Complications Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest Schedule Ind
Yes
Invest No Control Room Ind
Yes
Invest No Controller Ind
Yes
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Non-Threaded Connection Failure
Eq Failure Type
Non-Threaded Connection Failure
Other Non Threaded Ind
Seal (Not Pump Seal) Or Packing
Eq Additional Other Ind
Yes
Eq Additional Other Details
Dried Packing Due To Several Decades Of Service.
Preparer Name
N*** T*****
Preparer Title
Pipeline Compliance Engineer
Preparer Email
N*******@e****.com
Preparer Telephone
713-381-2493
Prepared Date
2013-06-11 00:00:00
Authorizer Name
N*** T*****
Authorizer Telephone
713-381-2493
Authorizer Title
Pipeline Compliance Engineer
Authorizer Email
N*******@e****.com
Narrative
A***********************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************@ 1055 was approximately 200 psi when repair attempts commenced. At 11:49 it was determined the leak had met the definition of an accident and the estimated cost to repair the leak would exceed $50,000 and the nrc was notified at 12:23 local time. At 08:00 on 5/16/2013, nitrogen inert was injected at levelland station for approximately 23 miles. The valve at milepost 62.5 was removed and replaced with a flanged type valve. *******************************************************.
| Report Received Date | 2013-06-11 00:00:00 |
|---|---|
| Iyear | 2013 |
| Report Number | 20130204 |
| Supplemental Number | 18182 |
| Report Type | Original Final |
| Operator Id | 31618 PHMSA Enforcement |
| Name | Enterprise Products Operating Llc |
| Operator Street Address | 1100 Louisiana Street |
| Operator City Name | Houston |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77002 |
| Local Datetime | 2013-05-15 11:49:00 |
| Location Latitude | 33.5890316 Google Maps OpenStreetMap |
| Location Longitude | -102.4290155 Google Maps OpenStreetMap |
| Commodity Released Type | Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions |
| Commodity Subtype | Other Hvl |
| Commodity Details | Propane |
| Unintentional Release Bbls | 1 |
| Recovered Bbls | 0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Other |
| Accident Details | Third Party Operator |
| Incident Identified Datetime | 2013-05-15 11:49:00 |
| System Part Involved | Onshore Pipeline, Including Valve Sites |
| On Off Shore | Onshore |
| Shutdown Due Accident Ind | Yes |
| Shutdown Datetime | 2013-05-15 11:49:00 |
| Restart Datetime | 2013-05-17 00:35:00 |
| On Site Datetime | 2013-05-15 11:49:00 |
| Nrc Rpt Datetime | 2013-05-15 12:23:00 |
| Nrc Rpt Num | 1047225 NRC Report How to search |
| Ignite Ind | No |
| Explode Ind | No |
| Upstream Valve Type Ind | Remotely Controlled |
| Downstream Valve Type Ind | Manual |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | South Leg Loop (Blue Line) |
| Segment Name | Lid 220 |
| Onshore State Abbreviation | Tx |
| Onshore Postal Code | 79336 |
| Onshore City Name | Levelland |
| Onshore County Name | Hockley |
| Designated Location | Milepost/valve Station |
| Designated Name | 62.5 |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
| Crossing | No |
| Pipe Facility Type | Interstate |
| Item Involved | Valve |
| Valve Type | Mainline |
| Valve Mainline Type | Gate |
| Valve Manufacturer | M And J |
| Material Involved | Carbon Steel |
| Release Type | Leak |
| Leak Type | Seal Or Packing |
| Leak Type Other | Bonnet O-Ring |
| Wildlife Impact Ind | No |
| Soil Contamination | No |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | No |
| Commodity Reached Hca | No |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 0 |
| Est Cost Prop Damage | 15000 |
| Est Cost Emergency | 51000 |
| Est Cost Environmental | 0 |
| Est Cost Other | 0 |
| Prpty | 66000 |
| Accident Psig | 300 |
| Mop Psig | 1295 |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Length Segment Isolated | 124000 |
| Internal Inspection Ind | Yes |
| Operation Complications Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Cpm In Place Ind | Yes |
| Cpm Operating Ind | Yes |
| Cpm Functional Ind | Yes |
| Cpm Detection Ind | No |
| Cpm Conf Ind | No |
| Investigation Status | Yes, specify investigation result(s): (select all that apply) |
| Invest Schedule Ind | Yes |
| Invest No Control Room Ind | Yes |
| Invest No Controller Ind | Yes |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Equipment Failure |
| Cause Details | Non-Threaded Connection Failure |
| Eq Failure Type | Non-Threaded Connection Failure |
| Other Non Threaded Ind | Seal (Not Pump Seal) Or Packing |
| Eq Additional Other Ind | Yes |
| Eq Additional Other Details | Dried Packing Due To Several Decades Of Service. |
| Preparer Name | N*** T***** |
| Preparer Title | Pipeline Compliance Engineer |
| Preparer Email | N*******@e****.com |
| Preparer Telephone | 713-381-2493 |
| Prepared Date | 2013-06-11 00:00:00 |
| Authorizer Name | N*** T***** |
| Authorizer Telephone | 713-381-2493 |
| Authorizer Title | Pipeline Compliance Engineer |
| Authorizer Email | N*******@e****.com |
| Narrative | A***********************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************************@ 1055 was approximately 200 psi when repair attempts commenced. At 11:49 it was determined the leak had met the definition of an accident and the estimated cost to repair the leak would exceed $50,000 and the nrc was notified at 12:23 local time. At 08:00 on 5/16/2013, nitrogen inert was injected at levelland station for approximately 23 miles. The valve at milepost 62.5 was removed and replaced with a flanged type valve. *******************************************************. |
External Resources
PHMSA pipeline safety insights.